ILC 330.../350...
82
PHOENIX CONTACT
6959_en_07
24 V segment supply U
S
Connection technology
Spring-cage terminals
Nominal value
24 V DC
Tolerance
-20% / +20%
Ripple
±5%
Current consumption at nominal voltage (typical)
10 mA + 10 mA for each output set + load
Current consumption at nominal voltage (maximum)
8 A
Continuation
Through potential routing
Protective measures
Surge voltage
Input protective diodes (can be destroyed by permanent overload)
Pulse loads up to 1500 W are short circuited by the input protective diode.
Polarity reversal
Parallel diodes for protection against polarity reversal; in the event of an error
the high current flowing through the diodes causes the fuse connected
upstream to blow.
NOTE:
Provide external protection for the 24 V area. The power supply unit must be able to supply four times (400%) the nominal current of the
external fuse, to ensure that the fuse blows safely in the event of an error.
24 V supply U
ILC
Connection technology
Spring-cage terminals
Nominal value
24 V DC
Tolerance
-15% / +20%
Ripple
±5%
Permissible range
20.4 V DC to 30 V DC
Current consumption at nominal voltage (typical)
200 mA
Protective measures
Surge voltage
Input protective diodes (can be destroyed by permanent overload)
Pulse loads up to 1500 W are short circuited by the input protective diode.
Polarity reversal
Serial diode in the lead path of the power supply unit; in the event of an error
only a low current flows. In the event of an error, no fuse trips within the
external power supply unit.
NOTE:
Observe current consumption of the Inline terminals
Observe the logic current consumption of each device when configuring an Inline station. It is specified in every terminal-specific data sheet.
The current consumption can differ depending on the individual terminal. The permissible number of devices that can be connected therefore
depends on the specific station structure.
Protection by the external power supply unit
Ensure protection of 2 A by means of the external power supply unit.
Содержание ILC 330 Series
Страница 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Страница 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Страница 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Страница 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Страница 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...
Страница 80: ...ILC 330 350 80 PHOENIX CONTACT 6959_en_07...
Страница 96: ...ILC 330 350 96 PHOENIX CONTACT 6959_en_07 T Terminal box 27 U Update 9 43 Updating the firmware 89...