User manual

Installing and operating the 
ILC 330... and ILC 350... 
Inline controllers

Содержание ILC 330 Series

Страница 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...

Страница 2: ...EN ILC 330 350 07 Designation As of version HW As of version FW Order No ILC 330 ETH 01 4 6F 1 41 2737193 ILC 330 PN 01 4 6F 3 11 2988191 ILC 350 ETH 01 4 6F 1 11 2737203 ILC 350 ETH M 02 4 6F 1 20 29...

Страница 3: ...phoenixcontact com Published by PHOENIX CONTACT GmbH Co KG Flachsmarktstra e 8 32825 Blomberg GERMANY Should you have any suggestions or recommendations for improvement of the contents and layout of o...

Страница 4: ...ific application in particular with regard to observing the applicable standards and regulations All information made available in the technical data is supplied without any accompanying guarantee whe...

Страница 5: ...erization memory and Internet Explorer 23 2 9 4 Internet Explorer FTP functionality 24 2 9 5 Activating deactivating the FTP server 25 2 9 6 Activating deactivating the HTTP server ILC 330 ETH ILC 350...

Страница 6: ...System variables 69 4 1 1 General notes 69 4 1 2 Status register for local digital inputs and outputs 70 4 1 3 Status register of a PROFINET controller ILC 330 PN ILC 350 PN 71 4 1 4 INTERBUS register...

Страница 7: ...chnical appendix service and maintenance 89 A 1 Error causes and remedies 89 A 2 Updating the Inline controller firmware 89 A 3 Connecting unshielded cables 90 B Appendix for document lists 91 B 1 Lis...

Страница 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...

Страница 9: ...oftware Suite 2007 1 30 Service Pack 1 ILC 330 PN PC Worx Version 6 00 Service Pack 4 or later part of the AUTOMATIONWORX Software Suite 1 50 ILC 350 ETH PC Worx Version 3 03 or later When using PC Wo...

Страница 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...

Страница 11: ...een Inline controllers via Ethernet This enables distributed modular automation solutions to be configured When using the AX OPC server provided in the AUTOMATIONWORX Software Suite Inline controller...

Страница 12: ...ected Inline local bus Figure 2 2 Connected remote bus Ethernet 6959B001 1 PLC RUN FAIL RUN PROG MRESET STP INLINE CONTROL ILC 350 ETH Ord No 27 37 203 IL RDY RUN BSA FAIL PF PRG ETH LNK ACT 100 10 10...

Страница 13: ...4 E Q1 1 2 1 2 3 4 1 2 3 4 5 6 5 6 1 2 I9 I10 I11 I12 1 2 1 2 3 4 1 2 3 4 5 6 5 6 1 2 I5 I6 I7 I8 68740008 LNK MODE 1 2 X1 LNK MODE 1 2 X2 LNK MODE 1 2 X3 LNK MODE 1 2 X4 US1 US2 Fail Reset MODE ACT 1...

Страница 14: ...before unpacking the Inline controller To avoid possible damage to the Inline controller unpack and pack the controller in accordance with the ESD regulations NOTE Electrostatic discharge The device...

Страница 15: ...ace 5 Connectors 1 to 3 input terminal points 6 Connector 4 output terminal points 7 Connector 5 terminal points for voltage supply 8 Mode selector switch 9 Card holder for the parameterization memory...

Страница 16: ...PLC ETH IL I O PWR IN 6959B008 Des Color Status Meaning ETH state of the Ethernet interface LNK Green On Connection established successfully link the Inline controller is able to contact another netwo...

Страница 17: ...ed Bus error in the connected bus remote bus local bus Controller error Off No error has occurred PF Yellow Peripheral fault On Peripheral fault on a device in the connected bus local bus or remote bu...

Страница 18: ...X CONTACT 6959_en_07 UL Green 24 V supply UILC for generating voltages UL and UANA On Supply voltage is present indication if 24 V supply voltage UILC is present Off Supply voltage is not present Des...

Страница 19: ...or the online monitoring function STP The controller is in the STOP state Application program processing has been stopped MRESET Retain data and the application program are deleted For safety reasons...

Страница 20: ...cted against accidental activation The reset button restarts the Inline controller Figure 2 7 Reset button TH 10 100 I5 I6 I7 I8 I9 I10 I11 I12 Q2 Q4 E Q1 Q3 US UM UL I1 I2 I3 I4 STP RUN FAIL RDY RUN...

Страница 21: ...user specific files can also be stored on the parameterization memory See Parameterization memory and Internet Explorer on page 23 NOTE Only use a parameterization memory provided by Phoenix Contact...

Страница 22: ...You can enter the file name for your project in the marking field for example Applying light pressure push the parameterization memory into the slot until it engages with a click in the card holder I...

Страница 23: ...us configuration workspace in PC Worx Select the controller e g ILC 350 ETH 0 0 in the Bus Structure window Select the Extended Settings tab in the Device Details window Open Internet Explorer from th...

Страница 24: ...ivate this setting in Internet Explorer under Options Internet Properties Advanced Figure 2 10 Internet Properties Enable folder view for FTP sites Data may only be copied or deleted on the parameteri...

Страница 25: ...11 Deactivating the FTP server 2 9 6 Activating deactivating the HTTP server ILC 330 ETH ILC 350 ETH ILC 350 ETH M To protect the Inline controller ILC 330 ETH ILC 350 ETH or ILC 350 ETH M against un...

Страница 26: ...volatile read write memory RJ45 socket Non volatile RAM Transmitter Dual port memory Reset button Mode selector switch Reset block Connection for parameterization memory Battery RS 232 interface Realt...

Страница 27: ...angerous contact voltages The end plate is supplied together with the Inline controller and does not need to be ordered separately Mounting position Mount the Inline controller horizontally as shown i...

Страница 28: ...Observe the information provided in the aforementioned user manuals Once all the bases have been snapped on insert the connectors in the corresponding bases First place the front connector shaft latc...

Страница 29: ...efore recommended that all connectors be removed prior to removing the Inline controller Lever up the connectors by pressing on the back connector shaft latching Figure 2 15 detail A1 NOTE Damage to e...

Страница 30: ...ing and mounting the Inline controller Only reinstall this terminal once the Inline controller is mounted Observe the following when replacing an Inline controller If you want to use the parameterizat...

Страница 31: ...OM 4 of your PC is directly connected to the Inline controller TH 10 100 I5 I6 I7 I8 I9 I10 I11 I12 US UM UL I1 I2 I3 I4 Q1 Q2 Q3 Q4 E RE SET STP RUN FAIL RDY RUN BSA FAIL PF PRG MRE SET RU N PR OG PL...

Страница 32: ...A Industrial Ethernet Planning and Installation Guide see iaona eu com Transmit data T 1 Transmit data T 2 Receive data R 3 4 5 Receive data R 6 7 8 Figure 2 17 Ethernet interface 8 pos RJ45 socket 10...

Страница 33: ...rogramming interface of the Inline controller PRG and the serial interface of the PC COM1 to COM4 Assembly instruction Figure 2 19 Connecting cable between PC and Inline controller Ordering data Conne...

Страница 34: ...LM MULTI PAC terminals at the IBS IL 24 RB T PAC terminal The first branch terminal must be placed directly after the Inline controller In terms of topology it opens a remote bus If additional branch...

Страница 35: ...l back characteristic curve from the QUINT POWER range see INTERFACE catalog from Phoenix Contact is recommended for Inline controller operation A power supply without a fall back characteristic curve...

Страница 36: ...Inline controller is now fully initialized If the LEDs do not light up or start flashing there is a serious fault on the Inline controller In this case please contact Phoenix Contact Figure 2 23 Supp...

Страница 37: ...is simultaneously reference ground for the main and segment supply 1 4 2 4 FE Functional earth ground FE Functional earth ground must be connected through the power supply The contacts are directly c...

Страница 38: ...voltage It does not have short circuit protection The user must provide short circuit protection The rating of the fuse connected upstream must be such that the maximum permissible load current of 8...

Страница 39: ...an be used as interrupt inputs In the event of a defined edge at an input an IEC 61131 freely programmable event task can be called Inputs I9 to I12 are standard inputs Figure 2 24 Terminal point assi...

Страница 40: ...put 5 2 1 I6 Input 6 1 2 2 2 24 V Supply voltage UM for 2 and 3 conductor connection 1 3 2 3 GND Ground contact for 3 conductor connection 1 4 I7 Input 7 2 4 I8 Input 8 1 5 2 5 24 V Supply voltage UM...

Страница 41: ...nctional earth ground for 3 conductor connection 1 4 O3 Output 3 2 4 O4 Output 4 1 5 2 5 GND Ground contact for 2 and 3 conductor connection 1 6 2 6 FE Functional earth ground for 3 conductor connecti...

Страница 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...

Страница 43: ...for later versions ILC 350 ETH M PC Worx Version 3 12 Service Pack 1 or later part of the AUTOMATIONWORX Software Suite 2005 1 10 ILC 350 PN PC Worx Version 5 00 or later part of the AUTOMATIONWORX So...

Страница 44: ...efault setting the system attempts to execute the Download Changes function without violating the realtime conditions of the tasks executed on the controller If the modifications cannot be sent for ex...

Страница 45: ...blocks or firmware services can be detected Technical properties limit values The string for a file name for opening deleting and monitoring modifications must not exceed 80 characters in length Up t...

Страница 46: ...r occurred during execution the value at the Error output 1 ErrorID indicates the number of the cause of the error When using the block please note the following This block can activate up to eight in...

Страница 47: ...block was not executed TRUE The function block was executed Handle UINT Output File handle of file opened or created Error BOOL Output FALSE No errors occurred when opening creating the file TRUE An e...

Страница 48: ...tus of the Done Error and ErrorID outputs is maintained until a falling edge is detected at the Execute input 7018B027 FILE_CLOSE Execute Handle Error Done ErrorID Table 3 3 FILE_CLOSE function block...

Страница 49: ...t first be saved in an array and then converted into a string using the BUF_TO_STRING function block Enter the number of bytes to be read at the MaxLength input Activate the block on a rising edge at...

Страница 50: ...NT Input Number of characters to be read Done BOOL Output FALSE The function block was not executed TRUE The function block was executed LengthRead UDINT Output Number of characters read Error BOOL Ou...

Страница 51: ...ing must first be saved in an array using the STRING_TO_BUF function block Assign the number of bytes to be written to the Length input Activate the block on a rising edge at the Execute input The exe...

Страница 52: ...of characters to be written Done BOOL Output FALSE The function block was not executed TRUE The function block was executed Length Written UDINT Output Number of characters written Error BOOL Output F...

Страница 53: ...file to be deleted to the Name input The file name must not exceed 80 characters in length Activate the block on a rising edge at the Execute input The execution of the function block is complete when...

Страница 54: ...e function block was not executed TRUE The function block was executed Error BOOL Output FALSE No errors occurred when deleting TRUE An error occurred when deleting ErrorID UINT Output Error number of...

Страница 55: ...ber of the cause of the error The status of the Done Position Error and ErrorID outputs is maintained until a falling edge is detected at the Execute input 7018B031 FILE_TELL Execute Name Postition Er...

Страница 56: ...reference to be used to move the pointer at the Mode input see Table 3 8 on page 57 Activate the block on a rising edge at the Execute input The execution of the function block is complete when the Do...

Страница 57: ...UINT Input Positioning mode 0 Positioning relative to start of file 1 Positioning relative to current position 2 Positioning relative to end of file Done BOOL Output FALSE The function block was not e...

Страница 58: ...if the monitoring condition set at the Option input is true The name of the modified file can be read as a string at the Name output The size of the file to be modified in bytes can be read at the Si...

Страница 59: ...length Size UDINT Output Size of modified file in bytes This value can be used for example when reading the file later Reason DWORD Output This flag indicates the reason for the modification Possible...

Страница 60: ...information about the current size of this file Because the file is still being written the size indicated does not match the actual size of the file Table 3 10 Options for the option string Option Me...

Страница 61: ...nection monitoring in the application program The Inline controller supports 32 TCP IP connections to another communication partner The function blocks are valid for Order designation As of hardware v...

Страница 62: ...for communication Enter the partner IP address followed by some optional parameters Use the syntax specified below this table VALID BOOL Output This output indicates whether a valid connection has bee...

Страница 63: ...address is specified for a device configured with PASSIVE this device responds to the first connection request that comes in If an IP address is specified the device only responds to the request for...

Страница 64: ...o a communication partner via an IP connection A maximum of 1460 bytes can be sent using the IP_USEND block Before data can be sent a communication connection must be established with the IP_CONNECT b...

Страница 65: ...whether the block has successfully sent the data to be transmitted in full The success of data transmission can only be evaluated during the cycle in which the rising edge occurs at this output ERROR...

Страница 66: ...This input is only used for UDP it is not relevant for TCP IP NDR BOOL Input At this output you can see whether the block has successfully received the data to be transmitted in full The success of d...

Страница 67: ...0031hex The connection was aborted ERR_TIMEOUT 0033hex General timeout receiver is no longer responding or the transmitter has not finished transmitting ERR_STRING_TOO_LONG 0040hex Partner string at t...

Страница 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...

Страница 69: ...stic status register and the diagnostic parameter register These registers are available to the application program as system variables system flags global variables Operating states error states and...

Страница 70: ...ut IN3 ONBOARD_INPUT_BIT3 BOOL State of local input IN4 ONBOARD_INPUT_BIT4 BOOL State of local input IN5 ONBOARD_INPUT_BIT5 BOOL State of local input IN6 ONBOARD_INPUT_BIT6 BOOL State of local input I...

Страница 71: ...e PROFINET device is indicating a diagnostic alarm for an active connection The corresponding device s can be identified using the RALRM diagnostic block or by requesting the PN_DA_NO_DIAG diagnostic...

Страница 72: ...controller attempts to establish a connection cyclically to all devices in the desired configuration under the PROFINET icon For devices that cannot be reached the PROFINET controller cyclically attem...

Страница 73: ...rdware fault MASTER_DIAG_STATUS_REG_DTC BOOL Diagnostic routine is active MASTER_DIAG_STATUS_REG_RUN BOOL Data transmission is active MASTER_DIAG_STATUS_REG_ACT BOOL Selected configuration is ready to...

Страница 74: ...code 15 0 7 8 Example address overlap code 0A50hex 6219B041 A 0 Special case if an interface error cannot be located the value 128 is indicated in the diagnostic parameter register i e bit 7 is set T...

Страница 75: ...e breakpoint has been set in the application program PLCDEBUG_FORCE BOOL Variable s forced at least one variable is being continuously overwritten forced by PROGRAM WORX PLCDEBUG_POWERFLOW BOOL Powerf...

Страница 76: ...d on the control processor COP_DIAG_STATUS_REG_FC_RUN BOOL Runtime system RUN COP_DIAG_STATUS_REG_FC_STOP BOOL Runtime system STOP COP_DIAG_STATUS_REG_FC_HALT BOOL Runtime system HALT COP_DIAG_STATUS_...

Страница 77: ...ate of the external Ethernet port is 100 Mbps ETH_PORT1_FULL_DUPLEX BOOL There is a full duplex connection at the external Ethernet port ETH_PORT2_LINK BOOL The internal Ethernet port is connected ETH...

Страница 78: ...e 4 13 System variables of the system time System variable Type Meaning RTC_HOURS INT System time hours RTC_MINUTES INT System time minutes RTC_SECONDS INT System time seconds RTC_DAY INT System time...

Страница 79: ...must know whether or not a PROFINET device is supplying valid data This is why each device has a PNIO_DATA_VALID process data item PNIO_APPL_RUN The display of this bit is interesting for example if c...

Страница 80: ...ILC 330 350 80 PHOENIX CONTACT 6959_en_07...

Страница 81: ...erance 20 20 Ripple 5 Current consumption at nominal voltage typical 6 mA 7 mA for each input set Current consumption at nominal voltage maximum 8 A Continuation Through potential routing Protective m...

Страница 82: ...event of an error 24 V supply UILC Connection technology Spring cage terminals Nominal value 24 V DC Tolerance 15 20 Ripple 5 Permissible range 20 4 V DC to 30 V DC Current consumption at nominal vol...

Страница 83: ...ive measures Electrical short circuit protection INTERBUS Number of I O points 8192 maximum Number of data words 512 maximum Number of bus segments 254 maximum Transmission speed 500 kbps or 2 Mbps Tr...

Страница 84: ...t consumption from the communications power and analog supply INTERBUS remote bus Interface Inline data jumper Electrical isolation Yes Number of devices See technical data for INTERBUS on page 83 and...

Страница 85: ...nge UIN are limited in application according to the input design Digital outputs Number 4 Output design Protected outputs according to EN 61131 2 Nominal output voltage 24 V DC Nominal output current...

Страница 86: ...mites Resistant Resistance of housing material to fungal decay Resistant This temperature range is only guaranteed if the Inline controller is mounted horizontally Conformance with EMC Directive 2014...

Страница 87: ...Technical data and ordering data 6959_en_07 PHOENIX CONTACT 87 Approvals For the latest approvals please visit phoenixcontact net products...

Страница 88: ...ing fields ILC 350 PN 2876928 1 Description Type Order No Pcs Pkt Parameterization memory CompactFlash card 256 MB CF FLASH 256MB 2988780 1 Parameterization memory CompactFlash card 2 GB CF FLASH 2GB...

Страница 89: ...ning Mode selector switch in STP position Set mode selector switch to RUN PROG position The serial interface is not operating The pin assignment of the programming cable or of the connector adapter us...

Страница 90: ...o your application When wiring proceed as follows Strip 8 mm off the cable Push a screwdriver into the actuation shaft of the appropriate terminal point Figure A 1 A so that you can insert the wire in...

Страница 91: ...Snapping on the Inline controller 28 Figure 2 14 Connectors to be removed if terminals are installed next to the Inline controller 29 Figure 2 15 Removing the Inline controller 30 Figure 2 16 Communi...

Страница 92: ...55 Figure 3 8 FILE_SEEK block 56 Figure 3 9 FILE_NOTIFY block 58 Figure 3 10 IP_Connect block 62 Figure 3 11 IP_USEND block 64 Figure 3 12 IP_URCV block 66 Section 4 Figure 4 1 Error location in the m...

Страница 93: ...f the function blocks 61 Table 3 12 IP_CONNECT function block inputs and outputs 62 Table 3 13 IP_USEND function block inputs and outputs 65 Table 3 14 IP_URCV function block inputs and outputs 66 Tab...

Страница 94: ...t status firmware Version 4 6F 1 11 or later 77 Table 4 12 System variables of the mode selector switch 77 Table 4 13 System variables of the system time 78 Table 4 14 Status information variables of...

Страница 95: ...t 32 Ethernet connection 11 15 Ethernet interface 32 F Fall back characteristic curve 35 FTP functionality 23 H Hardware requirements 9 I Inline local bus 12 13 INTERBUS 34 IP address Setting 43 IP20...

Страница 96: ...ILC 330 350 96 PHOENIX CONTACT 6959_en_07 T Terminal box 27 U Update 9 43 Updating the firmware 89...