AXL F SSDO8/3 1F
18
PHOENIX CONTACT
106888_en_01
P
Green
Diagnostics for safe communication protocol
Off
No safe communication.
Green on
Safe communication is running without errors.
Flashing green
Safe communication is running. The SafetyBridge system is requesting an
acknowledgment.
CM
Red
Startup mode
Off
SafetyBridge mode.
Red on
Startup mode.
WARNING:
In startup mode, the device is in
standard
operation.
Startup mode: see Section 7.1.1 “Startup mode” on page 50.
SD
Yellow
Acknowledgment request
Off
No diagnostic message present that needs to be acknowledged.
Yellow on
A diagnostic message is present that needs to be acknowledged for safe
digital output errors, supply voltage errors or general errors.
Acknowledgment: see Section 8.2 “Acknowledging an error” on page 53.
00 - 07
Green
Status of each output from 0 - 7
Off
Output at logic “0”.
Green on
Output at logic “1”.
10 - 17
Red
Diagnostics for each output from 0 - 7
Off
No error present at the output.
Red on
Error at the output (e.g., short circuit).
Des.
Color
State
Description