Parameterization of the module
106888_en_01
PHOENIX CONTACT
35
5
Parameterization of the module
5.1
Parameterization in a SafetyBridge system
Parameterization includes the following:
–
Assigning the SafetyBridge address
–
Parameterizing outputs
SafetyBridge address
The SafetyBridge address is a unique ID for the safety module in the SafetyBridge structure.
It is assigned in the configuration software for the assigned logic module.
The address of the connected satellites (here: AXL F SSDO8/3 1F) is based on the island
number of the logic module and the position in the hardware editor of the SAFECONF
configuration software.
•
Set this address of the safety module via the DIP switches (see see “Setting the DIP
switch” on page 30).
Parameterization of
outputs
The parameterization of the safe outputs determines the behavior of the module and
influences the safety integrity that can be achieved.
The controller automatically writes the parameterization created in the configuration
software to the module on every power up, reset or deactivation/activation of the “Operate”
function block.
The following conditions must be met:
–
Supply voltage is present
–
Local bus is in the RUN state
–
Communication connection has been established between the controller and the
module
The module cannot be operated if it is not parameterized. The FS LED flashes.
The module is ready to operate if the parameters for all outputs are valid and transmitted
without errors. Valid output data is only written in this state. In any other state, every output
is set to the safe state.
If errors are detected during parameterization, the parameterization data is not applied. The
FS LED flashes to indicate that the parameterization is invalid.
In addition, the error is indicated at the controller.
•
In this case, check and correct the settings.
Information on error messages and troubleshooting: see Section 8 “Errors: messages and
removal” on page 53.
The communication address configured in the controller project must match the address
set on the device.
The settings on the device take effect after a power up.
For more detailed information on the SafetyBridge address, please refer to the
documentation for the logic module used.
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from