KENR6933
63
Troubleshooting Section
4.
Inspect the battery wires from the ECM to the
battery compartment. Refer to the Schematic
Diagram. Inspect the wires and the power relay.
Check the power and ground connections to the
ECM. Refer to the schematic diagram for more
information.
5.
Select the “Wiggle Test” from the diagnostic tests
on the electronic service tool.
6.
Choose the appropriate group of parameters to
monitor.
7.
Press the “Start” button. Wiggle the wiring harness
in order to reproduce intermittent faults.
Note:
If an intermittent fault exists, the status will be
highlighted and an audible beep will be heard.
8.
Repair any faults and ensure that the symptom
has been cleared. If the symptom is still present,
refer to “Fuel Supply”.
Fuel Supply
NOTICE
Do not crank the engine continuously for more than
30 seconds. Allow the starting motor to cool for two
minutes before cranking the engine again.
1.
Visually check the fuel tank for fuel. The fuel
gauge may be faulty.
2.
Ensure that the fuel supply valve (if equipped) is
in the full OPEN position.
3.
If the temperature is below 0 °C (32 °F), check
for solidi
fi
ed fuel (wax).
4.
Check the primary
fi
lter/water separator for water
in the fuel.
5.
Check for fuel supply lines that are restricted.
6.
Check that the low pressure fuel lines are tight
and secured properly.
7.
Check the fuel
fi
lters.
8.
Check the diesel fuel for contamination. Refer to
Testing and Adjusting, “Fuel Quality - Test”.
9.
Check for air in the fuel system. Refer to Testing
and Adjusting, “Air in Fuel - Test”.
10.
Ensure that the fuel system has been primed.
Refer to Testing and Adjusting, “Fuel System -
Prime”.
11.
Check the fuel pressure. Refer to Testing and
Adjusting, “Fuel System Pressure - Test”.
i02535522
Intermittent Low Power or
Power Cutout
Note:
Use this procedure only if the engine does not
shut down completely.
Probable Causes
•
Diagnostic codes
•
Electrical connectors
•
ECM connection
•
Fuel supply
•
Intake manifold pressure
Recommended Actions
NOTICE
Do not crank the engine continuously for more than
30 seconds. Allow the starting motor to cool for two
minutes before cranking the engine again.
Diagnostic Codes
Check for active diagnostic codes and event codes
on the electronic service tool. Troubleshoot any
active codes before continuing with this procedure.
Electrical Connectors
1.
Refer to Troubleshooting, “Electrical Connectors
- Inspect”.
2.
Repair the electrical connectors or replace the
electrical connectors.
3.
Ensure that all the connector seals are in place
and that the connectors have been correctly
installed.
4.
Ensure that the repairs have eliminated the fault.
If the fault has not been eliminated proceed to
“ECM Connection”.
ECM Connection
1.
Check that the P2/J2 connector is correctly
connected.
2.
Check that the P1/J1 connector is correctly
connected.
Содержание 1106C Genset
Страница 1: ...May 2007 Troubleshooting 1106C Genset PK Engine KENR6933 00 ...
Страница 19: ...KENR6933 19 Troubleshooting Section g01178875 Illustration 6 ...
Страница 119: ...KENR6933 119 Troubleshooting Section g01244183 Illustration 31 Schematic of the bypass harness connector ...
Страница 186: ...186 KENR6933 Index Section ...
Страница 187: ...KENR6933 187 Index Section ...
Страница 188: ...Copyright 2007 Perkins Engines Company Limited All Rights Reserved Printed in U K ...