To implement this Device ID Mapping example, the following web page configuration entries are required on the
Modbus Alias Device ID Configuration
page, which is accessed by clicking
Modbus | Alias Configuration
.
Where:
Parameter
Type
Description
Rx Device
Configuration
(1-255)
The original, or pre-alias, device ID received from Modbus
master(s). Required.
Alias Device ID
Configuration
(1-255)
The corresponding slave device ID. Required.
Modbus/TCP Master
Configuration (yes/
no)
Enables the Alias conversion from Modbus/TCP masters.
M
ust be enabled if Modbus/TCP master(s) are present
.
Modbus Serial Master
Configuration (yes/
no)
Enables the Alias conversion from serial Modbus masters.
Must be enabled if serial Modbus master(s) are present.
Modbus over TCP Master Configuration (yes/
no)
Enables the Alias conversion from Modbus over Ethernet
TCP/IP masters.
Must be enabled if Modbus over Ethernet
TCP/IP master(s) are present.