Serial Menus
Parity
(Default = None)
None
Even
Odd
Data Bits (Default = 8)
5, 6, 7, 8
Stop Bits (Default = 1)
1 or 2
Flow Control (Default =
None)
RTS/CTS
XON/XOFF
Half Duplex
Terminating Resistor
(Only displays on
applicable models)
To ensure the best signal integrity on a long distance high-speed RS-422 or RS-
485 network, sometimes it is required to place a 120
Ω
termination resistor
between each of the transmit differential pair or receive differential pair. Signal
reflection is reduced and a reliable communication is ensured by placing the 120
Ω
termination resistor. Using the software, you can place 120
Ω
termination resistors
between the signals shown below:
•
RS-422 Mode
-
Between TxD+ and TxD- (Pin 5 and 7)
-
Between RxD+ and RxD- (Pin 4 and 2)
•
RS-485 - Between TxD/RxD+ and TxD/RxD- (Pin 5 and 7)
DTR Mode (Default =
Off)
0=Off
1=On
Rx Timeout Between
Packets (ms) (Default =
200)
Receive time-out (0-65535) between packets in msec. This is the maximum
spacing between received bytes allowed before the received Modbus serial
message is expected to be complete.
Discard Rx Packets With
Errors (Default = On)
On or Off: If selected, the ICDM-RX/MOD drops all packets received with parity,
framing, or overrun errors.
Note:
Modbus/RTU messages with invalid CRCs and Modbus/ASCII messages
without correct start and end of transmission characters are always
discarded independent of this setting.
Modbus Settings
Serial Port Protocol
(Default = Modbus/RTU-
to-Slaves)
The Modbus Protocol, setting for this serial port:
•
Modbus/RTU-to-Slaves
– Configures the serial port to communicate to
Modbus/RTU slaves.
•
Modbus/ASCII-to-Slaves
– Configures the serial port to communicate to
Modbus/ASCII slaves.
•
Modbus/RTU-to-Master
– Configures the serial port to communicate to a
Modbus/RTU master.
•
Modbus/ASCII-to-Master
– Configures the serial port to communicate to a
Modbus/ASCII master.
•
Modbus/RTU-to-Master/Slaves
– Configures the serial port to communicate to
a serial bus with a Modbus/RTU master and Modbus/RTU slave(s).
•
Modbus/ASCII-to-Master/Slaves
– Configures the serial port to communicate
to a serial bus with a Modbus/ASCII master and Modbus/ASCII slaves.
Serial Configuration Page (Continued)
Содержание ICDM-RX/MOD
Страница 1: ...MANUAL ICDM RX MOD Modbus Router User FACTORY AUTOMATION...
Страница 12: ...6 3 19 12 ICDM RX MOD User Manual Overview...
Страница 25: ...ICDM RX MOD User Manual Overview 6 3 19 25 Modbus Router Shared Memory Functionality...
Страница 32: ...6 3 19 32 ICDM RX MOD User Manual Overview...