Diagnostics Menu
6.3. Serial Interface Logs Page
This page displays the serial messages transmitted and received during normal operation. Click
Diagnostics |
Communication | Serial Logs
to access this page.
The format is as follows:
Pkt(N): ddd:hh:mm:ss.mss Rx/Tx>(data packet)
Where
:
ddd
– days since last system restart
hh
– hours since last system restart
mm
– minutes since last system restart
ss
– seconds since last system restart
mss
– milliseconds since last system restart
(
data
) – Modbus/RTU or Modbus/ASCII message data.
•
Private messages between the master and slaves on the Master/Slaves ports are indicated with “(
Private
)”.
•
All other messages are those routed through the Modbus gateway to the Modbus network or Shared
Memory.
6.4. Known Modbus Slave Device List Page
The
Known Modbus Slave Device
List
page provides device specific status and statistics for each device
connected locally to one or more of the serial ports or remotely through a remote Modbus/TCP device
configuration.
Access the
Known Modbus Slave Device List
page by clicking
Diagnostics | Modbus Diagnostics | Modbus
Devices
.
The following table provides detailed information about this page.
Known Modbus Slave Device List Page - Public Devices
Device ID
Displays the device ID associated with this device.
Note:
If
Device ID Offset Mode
is enabled, the actual device ID transmitted out the
serial port displays as (SP=xxx).
Active?
Displays the status of device:
•
Yes
means that the last request received a valid response and did not time out.
•
No
means that the last request timed out or the device has not yet received a
message.
IP Address
Displays the IP address associated with the local device under
Configured Remote
Modbus Devices
.
IP Port
Displays the TCP/IP port associated with the remote device under
Configured Remote
Modbus Devices
.
Tx Req
Displays the number of Modbus messages transmitted to this device.
Rx Rsp
Displays the number of Modbus responses received from this device.
Timeouts
Displays the number of response timeouts associated with this device.
Last Rsp Time
Displays the last response time from the Modbus device.
Avg Rsp Time
Displays the average response time from the Modbus device.