Commands
20
13
-0
4
29
7.2.1
Command examples
Example: Define tag type
Command: Change tag type on channel 1 to IPC03
Confirmation
Response: Type IPH-... read/write head on channel 1
Alternative response: No read/write head on channel 1
Example: Read tag
Prerequisites:
■
The tag type IPC03 is set.
■
One type IPH-
…
read/write head is connected to channel 1.
Command: Read two double words starting from address 0 on channel 1
04:02:30:33 (hexadecimal format)
04
Command code
CT
(change tag)
02
Reserved/Channel (1), toggle bit 0b
30:33
tag type (IPC03)
04:02:FF:01
04
Repeat command code
CT
(change tag)
02
Reserved/Channel (1), toggle bit 0b
FF
Status FFh (processing command)
01
Reply counter
04:02:00:02
04
Repeat command code
CT
(change tag)
02
Reserved/Channel (1), toggle bit 0b
00
Status 0 (command executed without error)
02
Reply counter
04:02:06:02
04
Repeat command code
CT
(change tag)
02
Reserved/Channel (1), toggle bit 0b
06
Status 6 (hardware error)
02
Reply counter
10:22:00:00
10
Command code
SR
(single read words)
22
Number of double words (2) / channel (1), toggle bit
00:00
Address of double words (0000)