VB24
60
5.3
ID-NET™ INTERFACE
25-pin
Name
Function
23
ID+
ID-NET™ n
24
ID-
ID-NET™ network -
7
GND
Ground
5.3.1
ID-NET™ Cables
The following instructions are referred to Figure 52, Figure 53 and Figure 54.
•
The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted
pair, shielded cable AWG 24 (or AWG 22) stranded flexible.
We recommend using DeviceNet cables (drop or trunk type) to the following reference
standards:
AN50325 – IEC 62026
UL STYLE 2502 80°C 30V
•
Cable Shield MUST be connected to earth ground ONLY at the Master.
•
NEVER use ID-NET™ cable shield as common reference.
•
The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table
below).
•
For Common Power Connections use only 2 wires (23 and 24).
-
DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do not
put it together with AC cable):
-
Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8
Volts.
-
Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide loops
between them).
•
Scanner's chassis may be connected to earth.
•
Network inside the same building.
Baudrate Table
Baud Rate
125 kbps
250 kbps
500 kbps
1Mbps
Cable Length
1200 m
900 m
700 m
*
* Application dependent, contact your Fuchs GmbH representative for details.
NOTE
The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates
allow longer cable lengths. The baudrate is software configurable by
authorized Fuchs GmbH personnel only.
Содержание FUQ-B8
Страница 1: ...VB24 BARCODE SCANNER FABRIKAUTOMATION MANUAL ...
Страница 22: ...VB24 12 b Operating mode selection and definition c Digital Outputs configuration ...
Страница 42: ...VB24 32 Figure 16 Positioning with U Shape Mounting Bracket Pitch Skew 0 15 45 45 15 alignment marks ...
Страница 54: ...VB24 44 Figure 28 ID NET Network Connections with isolated power blocks Power Supply Power Supply Power Supply ...
Страница 55: ...VB24 45 Figure 29 ID NET Network Connections with Common Power Branch Network ...
Страница 56: ...VB24 46 Figure 30 ID NET Network Connections with Common Power Star Network ...
Страница 72: ...VB24 62 Figure 52 ID NET Network Connections with isolated power blocks Power Supply Power Supply Power Supply ...
Страница 73: ...VB24 63 Figure 53 ID NET Network Connections with Common Power Branch Network ...
Страница 74: ...VB24 64 Figure 54 ID NET Network Connections with Common Power Star Network ...
Страница 112: ...VB24 102 T Technical Features 108 Troubleshooting 105 Typical Layouts 77 ...