7.
Stick the three Test Plugs together (general pin allo,-,S).
•
6.3
DM-AM Connection Details
The Mobile Advanced Diagnostic Module is powered via the USB port
of your PC.
By using the delivered AC/DC adapter or supply via Bulk Power supply
the DM-AM works as a Data-Logger only. In this case no communicaton
between the DM-AM and Diagnostic Manager takes place.
#
DM-AM Connection and Commissioning
1.
Connect the fieldbus cable to the fieldbus segment
2.
Plug the connection clamp of the fieldbus cable into the DM-AM
3.
Connect the DM-AM via the USB-cable to your Notebook
The DM-AM starts right away and the LED
POWER
lights solid red
For communication purposes the current supply via USB is necessary,
the supply current from the Notebook USB-interface to the DM-AM must
be at least 150 mA. Check your Notebook manual to find out the maxi-
mum power your Notebook can supply via its USB por. If your Notebook
does not allow such a supply value use an externally-supplied USB-Hub.
The DM-AM is a Plug-and-Play device. After connecting it to a Notebook
Windows
TM
automatically installs the DM-AM driver. The FieldConnex
R
FDT/DTM Diagnostic Manager contains and installs all necessary driver
software by itself.