H D 2 - D M - A / D M - A M
Working with the Stand-alone Diagnostic Kit
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: G49 621 776-0 • USA +1 330 4253555 • Sin65 67799091 • Internet http://www.pepperl-fuchs.com
104
187630
13.3
Commisioning with the Diagnostic Manager
Start-up Settings
Before continuing with the start-up settings be certain that PACTware
TM
as well as the Diagnostic
manager is properly installed.
1.
Perform the initial commisioning of the diagnostic project with PACTware
TM
2.
Choose
Connect
in the Diagnostic Manager to get a connection to the Diagnostic Device
3.
Open the
Online parametrization interface
4.
Go to table Motherboard Properties and choose
Stand-alone
from the drop-down list.
5.
Go to table Motherboard Bulk Supply Input Voltages
6.
Deactivate all measurements within the Secondary Voltage row.