H D 2 - D M - A / D M - A M
Product Specifications HD2-DM-A
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: G49 621 776-0 • USA +1 330 4253555 • Sin65 67799091 • Internet http://www.pepperl-fuchs.com
12
187630
3.3
Technical Data
3.4
LED Indication
Advanced Diagnostic Module HD2-DM-A
Supply
Rated voltage
19.2 to 35 V
Rated current
110 to 30 mA
Power loss
max. 2 W
Fieldbus interface
Number of segments
4
Rated voltage
9 to 32 V
Ambient conditions
Ambient temperature
-40 to 60 °C (-40 to 140° F)
Storage temperature
-40 to 85 °C (-40 to 185° F)
Shock resistance
15 g 11 ms
Vibration resistance
1 g, 10 to 150 Hz
Humidity
<95 % non-condensing
For complete technical data please refer to the corresponding data
sheets.
•
1 LED status segment 1
2 LED status segment 2
3 LED status segment 3
4 LED status segment 4
5 LED Primary power connection
6 LED Secondary power connection
Seg4
Seg3
Seg2
Seg1
SEC
PWR
PRI
PWR
Fieldbus
Diagnostic
Module
Advanced
Version
HD2-
DM-A
1
2
3
4
5
6