Functional Safety K-LB-*.*, F*-LB-I, P-LB-*.*.*
Operation
20
21
-0
9
25
Current and Voltage Measurement
Device
Step no.
Rated voltage
Leakage current
Comment
P-LB-1.A.13
1
30 V between Pins 1, 3 < 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-2.A.1346
1
2
30 V between Pins 1, 3
30 V between Pins 4, 6
< 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-1.B.12
1
30 V between Pins 1, 2 < 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-2.B.1245
1
2
30 V between Pins 1, 2
30 V between Pins 4, 5
< 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-1.C.123
1
2
3
30 V between Pins 1, 2
30 V between Pins 2, 3
30 V between Pins 1, 3
< 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-2.D.123456 1
2
3
4
5
6
30 V between Pins 1, 2
30 V between Pins 2, 3
30 V between Pins 1, 3
30 V between Pins 4, 5
30 V between Pins 5, 6
30 V between Pins 4, 6
< 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-1.E.23
1
30 V between Pins 2, 3 < 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-2.C.2356
1
2
30 V between Pins 2, 3
30 V between Pins 5, 6
< 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-1.D.1234
1
2
3
4
5
6
30 V between Pins 1, 2
30 V between Pins 1, 3
30 V between Pins 1, 4
30 V between Pins 2, 3
30 V between Pins 2, 4
30 V between Pins 3, 4
< 50
µ
A
Test passed if leakage
current is below 200
µ
A.
P-LB-1.F.1236
1
2
3
4
5
6
30 V between Pins 1, 2
30 V between Pins 1, 3
30 V between Pins 1, 6
30 V between Pins 2, 3
30 V between Pins 2, 6
30 V between Pins 3, 6
< 50
µ
A
Test passed if leakage
current is below 200
µ
A.
Table 5.5