72 / 84
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H58186 02/16
aPPendiX C. ProPortionaL ControL
table C.1 Proportional Control temperature Band
Control sensor temperature
duty Cycle
Se 2.22°C
0%
Se 1.11°C
50%
Setpoint
100%
table C.2 approximate time on/off for 50/60 hz Frequencies
temperature
on time/
second
(ms)
off time/
second
(ms)
temperature
on time/
second
(ms)
off time/
second
(ms)
Set Point + 2.22°C
0
1000
Set Point + 1.06°C 525
475
Set Point + 2.17°C
25
975
Set Point + 1.00°C 550
450
Set Point + 2.11°C
50
950
Set Point + 0.94°C 575
425
Set Point + 2.06°C
75
925
Set Point + 0.89°C 600
400
Set Point + 2.00°C
100
900
Set Point + 0.83°C 625
375
Set Point + 1.94°C
125
875
Set Point + 0.78°C 650
350
Set Point + 1.89°C
150
850
Set Point + 0.72°C 675
325
Set Point + 1.83°C
175
825
Set Point + 0.67°C 700
300
Set Point + 1.78°C
200
800
Set Point + 0.61°C 725
275
Set Point + 1.72°C
225
775
Set Point + 0.56°C 750
250
Set Point + 1.67°C
250
750
Set Point + 0.50°C 775
225
Set Point + 1.61°C
275
725
Set Point + 0.44°C 800
200
Set Point + 1.56°C
300
700
Set Point + 0.39°C 825
175
Set Point + 1.50°C
325
675
Set Point + 0.33°C 850
150
Set Point + 1.44°C
350
650
Set Point + 0.28°C 875
125
Set Point + 1.39°C
375
625
Set Point + 0.22°C 900
100
Set Point + 1.33°C
400
600
Set Point + 0.17°C 925
75
Set Point + 1.28°C
425
575
Set Point + 0.11°C 950
50
Set Point + 1.22°C
450
550
Set Point + 0.06°C 975
25
Set Point + 1.17°C
475
525
Set Point + 0.00°C 1000
0
Set Point + 1.11°C
500
500