51 / 84
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H58186 02/16
3.3.21 status | min / maX WindoW
This window displays an historical record of minimum and maximum values recorded since the
last Reset time. Data in this status window is “read-only” information. Pressing reset releases all
values and starts another period of accumulation for minimum or maximum values.
Fig. 3.31 Status |Min/Max window
The Status|Min/Max window provides the following controls:
•
min Control temp Field
- The lowest measured temperature used for control reported by any
RTD associated with the Circuit since the last Reset time.
•
max Control temp Field
- The highest monitored temperature used for control reported by any
RTD associated with the Circuit since the last Reset time.
•
min monitor temp Field
- The lowest temperature measured used for monitoring purposes
reported by any RTD associated with the Circuit since the last Reset time.
•
max monitor temp Field
- The highest temperature measured used for monitoring purposes
reported by any RTD associated with the Circuit since the last Reset time.
•
max Voltage Field
- The highest voltage recorded for the circuit since last Reset.
•
min Voltage Field
-The lowest voltage recorded for the circuit since last Reset.
•
max GF Current Field
- The highest ground-fault value recorded for the Circuit since the last
Reset time.
•
reset Button
-Immediately resets all Min/Max values and begins updating Min./Max. fields with
new values.
•
max Current Field
- The highest current recorded for the Circuit since the last Reset.