![Pentair raychem ngc-30/uit2 Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/pentair/raychem-ngc-30-uit2/raychem-ngc-30-uit2_programming-manual_1524541070.webp)
70 / 84
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H58186 02/16
Fig. A.2 Window to replace the existing NGC UIT2 software with the updated software
step 6
– Wait till the load process is completed.
aPPendiX B. nGC-uit2 BaCkuP ProCess
With a USB drive, you can back up the current configuration of a UIT2. All of the configuration
settings will be saved in an XML format so that it is easily read and edited on a computer. This
includes the following:
– Circuit Database
• The currently configured circuits on the UIT2.
– Events Database
• The last 2000 events that have occurred.
– Network List
• All of the devices that appear in the Network|Device screen.
– Preferences
• The user preferences, which include parameters such as Temperature Units, Language and
Screen Timeout.
step 1
– Insert a USB drive into the UIT2 and wait for the USB Service Panel to appear on the screen.
Fig. B.1 The USB service panel
Содержание raychem ngc-30/uit2
Страница 83: ......