1.1.3 monitorinG
Both Raychem NGC-20 and Raychem NGC-30 can monitor multiple independent Electrical Heat-
Tracing (EHT) parameters. The Raychem NGC-20 and Raychem NGC-30 monitor continuously
temperature, voltage, current and ground fault current leakage and report the values including alarms
to the UIT. An automated self-check feature is available where the systems periodically checks the
heating cables for faults and report the result to the UIT. This helps to avoid costly downtime. Dry
contact relays are provided for alarm annunciation back to a Distributed Control System (DCS).
1.1.4 Ground-FauLt ProteCtion aCCordinG to north ameriCan eLeCtriCaL
Code (neC) standard
National electrical codes require ground-fault equipment protection on all heat-tracing circuits.
Heat-tracing circuits equipped with Raychem NGC-30 controllers do not require additional
ground-fault detection equipment, simplifying installation and reducing costs. When applying the
IEC standards, additional RCD circuit breaker is required.
1.1.5 instaLLation
The Raychem NGC-30 system is configured with a User Interface Terminal (NGC-UIT2-EX) that has
LCD color touch-screen display technology. The NGC-UIT2-EX provides a user interface for easy
and efficient programming without keyboards or cryptic labels. The NGC-UIT2-EX model used
depends on the location of Raychem NGC-30 panel and the local environment.
Common nGC-uit2 interface and Programming
The term “NGC-UIT2” in this document refers to any of the available NGC-UIT2 models, regardless
of which model is actually installed. All NGC-UIT2s interface to the NGC-30-CRM, NGC-30-CRMS
(Card Rack Relay Control Modules), PLI (Power Line carrier Interface), and the RMM2 module
(Remote Monitoring Module). The three NGC-UIT2 versions described in Table 1.1 on page 5
all use the same wiring, system interface, and programming. The NGC-UIT2s differ only in the
environments in which they can be installed.
nGC-uit2 installed in hazardous and non-hazardous indoor or outdoor Panel Locations
If the panel is located in a hazardous/non-hazardous indoor or outdoor location, the NGC-UIT2-EX
model is required. This NGC-UIT2-EX model is specifically designed for these environments and
meets all applicable standards. The NGC-UIT2-EX model is installed locally on the Raychem NGC-
30 panel door.
nGC-uit2 installed separately from the Panel Locations
If the user interface terminal needs to be mounted separately from the Raychem NGC-30 control
panel, such as when the panel is in a hazardous or difficult to access location, the NGC-UIT2-
ORD-R provides a wall-mount alternative for remote mounting in a nonhazardous (unclassified)
indoor or outdoor location.
table 1.1 nGC-30 user interface terminals (uit2s)
uit2 type
area classification
usage
NGC-UIT2-EX
Nonhazardous (Unclassified) Locations
Hazardous* Locations
Class 1 Div. 2, Groups A, B, C & D
Zone 2
Type 4
• (Indoors or Outdoors)
NGC-UIT2-ORD-R
Nonhazardous (Unclassified) Locations
• The NGC-UIT2-ORD-R must be
installed in a nonhazardous, indoor
or outdoor location.
• The NGC-UIT2-ORD-R connects
to NGC-30 panels using RS-485
communication wiring.
Type 4
• (Indoors or Outdoors)
*Hazardous locations are defined by Article 500 of the National Electrical Code and Section 18 of the
Canadian Electrical Code.