The electrolyser outlet is valid for any type of disinfection. It is a dry contact and does not supply any voltage.
Control Center, connection and configuring a 230-V disinfectant dosing pump
at the “Electrolyser” outlet.
1 - Connect the cables in accordance with the diagram.
2 - Access the secured Install menu of MAESTRO (on the Menu Settings, press Esc and Valid at the same
time for 3 secs).
>
Select Other
to indicate that disinfection will not be carried out by an electrolyser.
In the Disinfect. sub-menu :
>
Modify injection time
(Number of seconds/15 min) if necessary
>
Modify max.
daily volume (number of litres for a 1L/h pump) if necessary.
3 - Via Menu Settings > pH/Disinfect/Temp > Disinfectant:
>
Select Auto
to automatically control the RedOx function.
>
Select Off
to fully cut the pump supply.
>
Select Set point
to modify the RedOx value to be achieved in Auto mode (700 mV factory setting).
> If required, selecting Priming and pressing Valid. manually starts the connected pump.
Disinfectant is injected after filtration, after the heat
pump and after the probes.
Chlorine
Only if connected to a MAESTRO probe unit or 4X extension. The liquid
chlorine tank is empty. > Fill the tank with liquid chlorine.
MAESTRO needs to use more disinfectant than authorised in the max. daily
volume menu (factory setting 0.5 L/day, modifiable, see below). The
message is automatically deleted at midnight.
!!!!!!!!!!!!!!!!!!!!
! Product tank !
!RedOx correct. empty !
!!!!!!!!!!!!!!!!!!!!
!!!!!!!!!!!!!!!!!!!!
! Max daily ! ! RedOx
control !
!!!!!!!!!!!!!!!!!!!!