Setting up an IntelliFlo VF pump with IntelliComm II

The IntelliFlo VF pump can operate with all of its stand alone features if desired. For example the pump can run filter cycles, egg timer 

features 1 and 2 and time of day scheduling of features 3-9. If IntelliComm II sends the pump a command when the pump is running 

the filter cycle or features 3-9, the IntelliComm II command takes priority regardless of flow rate. 

IntelliComm II will not interrupt 

nor take priority over Features 1 or 2.

For the IntelliFlo VF to accept a command from the IntelliComm II the pump must be in the “Running” mode. To place the IntelliFlo 

VF in “Running” mode, press the 

Filter mode button

, then press the 

Start/Stop button

. The led above the Start/Stop button must be 

lit for the IntelliFlo VF to accept commands from the IntelliComm II.
The default “Filter” cycle time in the IntelliFlo VF is from 9 AM to 9 PM. Since the IntelliFlo VF must be in the “Filter” mode, running 

Schedules, (LED above Start/Stop button lit) to accept commands from IntelliComm II, it will run its default filtration schedule first. 

If you want the pump to only run when it receives commands from IntelliComm II, program its “Filter” mode with the same start and 

stop times. For example program Cycle 1 in the “Filter” menu to “Start” cycle one at 9 AM and “Stop” cycle one at 9 AM. This will 

cause the pump to not run its filter cycle. This is done on the IntelliFlo keypad under Menu, Filter. Address 1, is the default address 

for the IntelliFlo VF. The IntelliComm II will only communicate with address 1. The pump’s “Address” setting is the first menu item 

under “Pool Data”.

Programming Flow into the IntelliFlo VF

1.  Press the Menu button.
2.  Press the down arrow until Ext. Ctrl. (External Control is displayed).
3.  Press the Select button to go Ext. Ctrl. (Program 1 is displayed).
4.  Press the Select Button (Enabled, Activation is displayed).
5.  Press the down arrow. (Program 1, 7 m³/h GPM, Set Flow, is displayed. The Program 1 flow rate will run when PRGM 1 is activated 

on the IntelliComm II control board.

6.  To change this flow rate press the “Select” button. The flow rate can be adjusted from 3.4 to 29.5 m³/h.
7.  The cursor will highlight the one’s digit column. Press the left and right arrows to move the cursor and the up and down arrows 

to change the number.

8.  Press the Enter Button to save.
9.  Press the down arrow until “Time Delay Stop” is displayed. Time Delay Stop is used to control the pump to run the Program speed 

for an additional amount of time after the IntelliComm II turns off its run command. This is often used for a heater cool down.

10.  Press Select to highlight the cursor, use the left and right arrows to move the cursor and the up and down arrows to change the 

number.

11.  Press Enter to save.
12.  Press Escape to Exit. The display shows Program 1. Press the down arrow to get to Program 2 and follow the same instructions 

to program. For more information about programming the pump, refer to the IntelliFlo VF Installation and Quick Start Guide.

Setting up an IntelliFlo VSD

The IntelliFlo VSD pump Speeds 1, 2, 3 and 4 correspond to Prgm (Program) 1, 2, 3 and 4 on the IntelliComm II circuit board. To 

program speed one on the IntelliFlo VSD. Press the “Speed 1” button. Press the Start button. To increase the speed of “Speed 1” press 

the up arrow button. Each press of the up arrow will increase the RPM by 10 RPM increments. Pressing the down arrow will decrease 

the RPM by 10 RPM. When the desired speed is found, press and hold down the “Speed 1” button and the new speed will be locked in. 

This new speed will be the speed that the pump will run when “Prgm 1” is activated on the IntelliComm II. The speed can be adjusted 

from 400 RPM to 3450 RPM. 

Note

: If the IntelliFlo VSD pump is turned on manually by pressing a Speed button and the Start button, it will run the speed that was 

pressed and the LED above this button will be illuminated. If it then gets a command to run a speed from the IntelliComm II, it will run 

the new commanded speed and the LED above the new speed will be illuminated. When the command from the IntelliComm II has 

stopped, the pump will go back to running the manually pressed speed.

Note

: If the IntelliComm II has switched on the IntelliFlo VSD and it is running a speed and you manually adjust the pump speed 

using the speed buttons on the pump, you must then manually switch the pump OFF, this turns off the manually manipulated speed 

and allows the IntelliComm II to take command and switch the pump back on to run at the commanded speed. If, after manipulating 

the keypad, the pump is not manually turned off by pressing the Stop button the pump will continue to run after the IntelliComm II 

command is stopped. 
Unlike the VF, the IntelliFlo VSD does not have to be in the “Running” mode to accept commands from an IntelliComm II. The power 

must be on (Green LED lit) on the IntelliComm II to accept commands.

Содержание INTELLICOMM II

Страница 1: ... INSTALLATIEHANDLEIDING BEDIENUNGSANTLEITUNG GUIDE D INSTALLATION GUIA DE INSTALACION GUIDE ALL INSTALLAZIONE Français INTERFACE ADAPTOR INTELLICOMM II IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS AQUATIC SYSTEMS G INSB ICOMM2 Rev 01 2018 ...

Страница 2: ...ty warnings and instructions can result in severe injury death or property damage Visit www pentairpooleurope com for additional free copies of these instructions Risk of electrical shock or electrocution The IntelliComm II Interface adapter must be installed by a qualified electrician according to the current National Electrical Code and local codes and ordinances The electrician should also cons...

Страница 3: ...ting Flow Rates m h for IntelliFlo VF Pump The IntelliFlo VF pump can be selected to run at a specific m h for each external control input IntelliFlo VF 3 4 to 29 5 m h Selecting Pump Speeds RPM for IntelliFlo VSD Pump The IntelliFlo VSD pump can be selected to run at a specific speed RPM for each external control input IntelliFlo VSD 400 3450 RPM English Disclaimer of liability There are a multit...

Страница 4: ...l The input terminal cable wires are not polarized Plugs wires can be connected in any order Connecting IntelliComm II to a Valve Actuator A Valve Actuator can be connected from the automation control system circuit board to any one of the IntelliComm II input terminals 1 4 by splicing into the valve actuator cable using the provided two wire input terminal cable Connecting Power 9 24 VDC to Intel...

Страница 5: ...M 1 connects to Filter Pump If more than one terminal input is active the highest input number m h RPM 4 will take priority regardless of the pump setting RS 485 COMMUNICATION CABLE 22 AWG PWR BLK YLW GRN RED M H RPM 1 9 24V DC AC GND M H RPM 2 M H RPM 3 M H RPM 4 PROGRAM 1 PROGRAM 2 PROGRAM 3 PROGRAM 4 9 24 VDC 1 A1 A2 3 5 7 2 4 6 8 RED BLK ControlPro connection RS 485 COMMUNICATION CABLE 22 AWG ...

Страница 6: ...9 Press the down arrow until Time Delay Stop is displayed Time Delay Stop is used to control the pump to run the Program speed for an additional amount of time after the IntelliComm II turns off its run command This is often used for a heater cool down 10 Press Select to highlight the cursor use the left and right arrows to move the cursor and the up and down arrows to change the number 11 Press E...

Страница 7: ...REEN LED sequence Number of time the LED will blink Alarm Description Action 2 Drive Temperature Warning Excessive drive tem perature 1 Ensure the motor fan has adequate area for ventilation 2 Stop motor and allow to cool 3 Run motor at a higher speed to improve cool ing air flow 5 Unknown alarm Electronic failure 1 Cycle power to reset pump 2 Replace drive 6 Drive Temperature Alarm Excessive driv...

Страница 8: ... not to touch the circuit board components Hold the circuit board by the edges Place the circuit board aside Drill two mounting screws holes for the back cover 3 Cut out the template on the following page 4 Position the template on a flat surface Mark the two screw locations for the mounting holes Remove the template 5 Using a in drill bit drill the two mounting holes 6 Position the back cover ove...

Страница 9: ...English IntelliComm II Back Cover Template Cut Out Cut Out 9 ...

Страница 10: ...ser Anweisungen erhalten Sie unter www pentairpooleurope com Gefahr eines Stromschlags oder Elektroschocks Der IntelliComm II Schnittstellenadapter muss durch einen qualifizierten Elektriker gemäß dem geltenden National Electric Code sowie lokalen Bestimmungen und Auflagen installiert werden Der Elektriker muss sich bezüglich lokaler Bestimmungen ferner an die lokale Bauabteilung wenden Eine nicht...

Страница 11: ... 1 Auswahl des Durchflusses m h für die IntelliFlo VF Pumpe Auf der IntelliFlo VF Pumpe kann für jeden der externen Steuereingänge der Betrieb mit einem bestimmten m h Durchfluss ausgewählt werden IntelliFlo VF 3 4 bis 29 5 m h Auswahl der Pumpendrehzahl U min für die IntelliFlo VSD Pumpe Auf der IntelliFlo VSD Pumpe kann für jeden der externen Steuereingänge der Betrieb mit einer bestimmten Drehz...

Страница 12: ...sind nicht polarisiert Stecker bzw Drähte können in beliebiger Reihenfolge angeschlossen werden Verbindung des IntelliComm II mit einem Ventilstellglied Ein Ventilstellglied kann aus der Leiterplatte des Automatisierungssteuerungssystems an einen beliebigen der IntelliComm II Eingangsanschlüssen 1 4 angeschlossen werden indem es mithilfe des mitgelieferten zweidrahtigen Eingangsanschlusskabels in ...

Страница 13: ...R BLK YLW GRN RED M H RPM 1 9 24V DC AC GND M H RPM 2 M H RPM 3 M H RPM 4 PROGRAM 1 PROGRAM 2 PROGRAM 3 PROGRAM 4 9 24 VDC 1 A1 A2 3 5 7 2 4 6 8 RED BLK Verbindung zu ControlPro RS 485 COMMUNICATION CABLE 22 AWG PWR BLK YLW GRN RED M H RPM 1 9 24V DC AC GND M H RPM 2 M H RPM 3 M H RPM 4 PROGRAM 1 PROGRAM 2 PROGRAM 3 PROGRAM 4 9 24 VDC BLK RED Verbindung zu ControlPro IntelliFlo Pumpe 230 VAC Pumpe...

Страница 14: ...tverzögerungsstopp wird verwendet um die Pumpe so zu steuern dass sie die programmierte Drehzahl für eine zusätzliche Zeitspanne aufrecht erhält nachdem der Betriebsbefehl von IntelliComm II deaktiviert wurde Dies wird häufig zum Abkühlen einer Heizung verwendet 10 Drücken Sie die Auswahltaste um den Cursor zu markieren verwenden Sie die Links und Rechts Pfeiltasten um den Cursor zu bewegen und di...

Страница 15: ...r Motorventilator über entsprechenden Ventilationsraum verfügt 2 Stoppen Sie den Motor und lassen Sie ihn abkühlen 3 Lassen Sie den Motor mit höherer Drehzahl laufen um die Strömung der Kühlluft zu ver bessern 5 Unbekannter Alarm Elektronische Stö rung 1 Schalten Sie die Stromversorgung aus und wieder ein um die Pumpe zurückzusetzen 2 Ersetzen Sie den Antrieb 6 Antriebstempera turalarm Zu hohe Ant...

Страница 16: ...e zur Seite Bohren Sie zwei Löcher für Befestigungsschrauben für die hintere Abdeckhaube 3 Schneiden Sie die Vorlage auf der folgenden Seite aus 4 Positionieren Sie die Vorlage auf einer flachen Oberfläche Markieren Sie die Position der beiden Schrauben für die Montagelöcher Entfernen Sie die Vorlage 5 Bohren Sie mit einem 6 mm Bohreinsatz die beiden Montagelöcher 6 Positionieren Sie die hintere A...

Страница 17: ...IntelliComm II hintere Abdeckhaube Cut Out Cut Out Ausnehmung Ausnehmung Deutsch 17 ...

Страница 18: ...pooleurope com voor gratis bijkomende exemplaren van deze instructies Gevaar voor elektrische schok of elektrocutie De IntelliComm II interfaceadapter moet door een gekwalificeerd elektricien geïnstalleerd worden in overeenstemming met de nati onale en lokale voorschriften en verordeningen voor elektrische installaties De elektricien moet ook de lokale bouwdienst raadplegen over de lokale voorschr...

Страница 19: ... VF pomp kan ingesteld worden om bij elke externe regelinput met een bepaald debiet m u te draaien IntelliFlo VF van 3 4 tot 29 5 m u Pompsnelheden t min voor de IntelliFlo VSD pomp selecteren De IntelliFlo VSD pomp kan ingesteld worden om bij elke externe regelinput met een bepaalde snelheid t min te draaien IntelliFlo VSD 400 3450 t min Disclaimer van aansprakelijkheid Tal van factoren spelen ee...

Страница 20: ...rd Plugs draden kunnen in gelijk welke volgorde aangesloten worden IntelliComm II op een klepregelaar aansluiten Een klepregelaar kan vanop de elektrische kaart van het automatische regelsysteem aangesloten worden op gelijk welke inputterminal van IntelliComm II 1 4 Dit door de kabel van de klepregelaar met de kabel 2 draden voor de inputterminal te verbinden Stroomvoeding 9 24 VDC op IntelliComm ...

Страница 21: ... 9 24V DC AC GND M H RPM 2 M H RPM 3 M H RPM 4 PROGRAM 1 PROGRAM 2 PROGRAM 3 PROGRAM 4 9 24 VDC 1 A1 A2 3 5 7 2 4 6 8 RED BLK Aansluiting op ControlPro RS 485 COMMUNICATION CABLE 22 AWG PWR BLK YLW GRN RED M H RPM 1 9 24V DC AC GND M H RPM 2 M H RPM 3 M H RPM 4 PROGRAM 1 PROGRAM 2 PROGRAM 3 PROGRAM 4 9 24 VDC BLK RED Aansluiting op ControlPro IntelliFlo pomp 230 VAC stroom naar pomp RS 485 COMMUNI...

Страница 22: ...om de pomp gedurende een bijkomende tijd nadat de IntelliComm II zijn bedrijfsinstructie uitgeschakeld heeft nog met de programmasnelheid te laten draaien Dat gebeurt vaak om een verwarmingselement af te koelen 10 Druk op Select om de cursor te markeren gebruik de pijlen links of rechts om de cursor te verplaatsen en de pijlen omhoog of omlaag om het cijfer te veranderen 11 Druk op Enter om op te ...

Страница 23: ...mperatuur aandrijving 1 Controleer of de motorventilator genoeg ruimte heeft voor de verluchting 2 Stop de motor en laat hem afkoelen 3 Laat de motor met een hogere snelheid draaien om de stroming van de koellucht te verbeteren 5 Onbekend alarm Elektronische storing 1 Voeding uit en inschakelen om de pomp terug te stellen 2 Vervang de aandrijving 6 Alarm tempera tuur aandrijving Te hoge temperatuu...

Страница 24: ...n de elektrische kaart niet aanraakt Hou de elektrische kaart vast bij de randen Leg de elektrische kaart opzij Boor twee gaten voor de bevestigingsschroeven van de achterzijde 3 Snij het model op de volgende pagina uit 4 Plaats het model op een vlak oppervlak Markeer de plaats voor de montagegaten Neem het model weg 5 Boor de twee montagegaten met een inch boor 6 Plaats de achterzijde op het vlak...

Страница 25: ...IntelliComm II achterzijde model Cut Out Cut Out Uitsnijding Uitsnijding Nederlands 25 ...

Отзывы: