  1. Depress the MENU button and 

hold it until the first setpoint 

appears on the bottom line of 

the display.  This will take 

about 10 seconds.

  2. The display should say LEAD 

ON = XX.X FT.  where XX.X 

is the current value for the lead 

pump on setpoint.

  3. If you wish to change this value 

then use the UP or DOWN 

buttons or you can hold the 

ADJUST button down and 

turn the ADJUST knob until 

the value is correct.  After the 

value is correct then depress 

the MENU/NEXT button to go 

to the next setpoint.

 4. If you have changed the 

value then the displays will 

ask  SAVE? (Y/N).  If you 

wish to save the new value 

then press UP/YES if not 

then press DOWN/NO.  The 

display should change to the 

next setpoint.

  5. The display should say LEAD 

OFF = XX.X FT.  where XX.X 

is the current lead off setpoint.  

Repeat steps 3 and 4 above to 

make any changes you need to 

this setpoint.

  6. This process should be repeated 

until all of the setpoints have 

been examined and changed 

or until no further changes are 

required.  Once all setpoints 

have been done the screen 

will return to normal mode 

or you can, at any time, hit 

the MUTE/RESET button and 

return to normal mode.  

If the system is set up for 2 pumps 

then the setpoints for the lag2 

pump will be skipped in the menu.  

If the system is set up for only 1 

pump then the setpoints for both 

lag pumps will be skipped.
The setpoints are stored in 

electrically erasable programmable 

memory EEPROM which will not 

lose its contents when powered 

down.  This is done every time 

the operator answers YES to the 

SAVE? (Y/N) prompt.

Configuration 

Menu

This menu is used to configure 

the NOVUS 4000 controller for 

its application.  This is normally 

only done once (when the panel 

is built or at startup) and would 

not be required again unless the 

configuration changed.  This menu 

is entered using the following 

procedure:
  1. Depress  the  UP  and  DOWN 

buttons at the same time and 

hold them until the first setting 

is displayed on the bottom line 

of the display.  This will take 

about 10 seconds.

 2. The display should say MAX 

LEVEL XX.X FT where 

XX.X is the current value.  

This parameter is the level 

when the level transmitter is 

at 20 Ma. (full scale). For 

example, if the transducer is a 

10  psig  submersible  pressure 

transducer then 10 psi is 23.1 

feet so adjust this value to 

23.1.  

 3. If no change to this setting is 

required then press the MENU/

NEXT button.  To change 

this value we use the same 

procedure that we used on the 

setpoint menu.  Use the UP or 

DOWN buttons or depress the 

ADJUST button while turning 

the ADJUST knob.  After you 

have the value required depress 

the MENU/NEXT button to go 

to the next parameter. 

 4. If the parameter has changed 

then the display will ask 

 

 

SAVE? (Y/N).  If the value is 

correct then press the UP/YES 

button to save it, or press the 

DOWN/NO button to continue 

without saving the new setting.

  5. The  display  should  say 

OFFSET XX.X  where XX.X 

is the current value.  This 

parameter is the level when 

the level transmitter is at 

4 Ma.  For example, if the 

transmitter is a submersible 

pressure transducer mounted 6 

inches off the floor of the wet 

well then this setting should 

be 00.5 ft.  Use the procedure 

in steps 3 and 4 above to make 

any changes and go to the next 

parameter.

 6. The display should say HOW 

MANY PUMPS X where X 

is the current max number of 

pumps.  If this is a duplex 

station set this to 2.  If it is a 

triplex station then use 3.  Use 

the procedure in steps 3 and 

4 above to make any changes 

and go to the next parameter.

  7. The display should say START 

DELAY XXXS where XXX 

is the current delay between 

pump starts.  This parameter 

is the minimum time between 

starting one pump and then 

starting another.  It is set in 

seconds  from  0  to  255.    Use 

the procedure in steps 3 and 

4 above to make any changes 

and go to the next parameter.

  8. The display should say STOP   

DELAY XXXS where XXX 

is the current delay between 

pump stops.  This parameter 

is the minimum time between 

stopping one pump and then 

stopping another.  It is set in 

seconds  from  0  to  127.    Use 

the procedure in steps 3 and 

4 above to make any changes 

and go to the next parameter.

 9. The display should say TIME 

AT SP XXXS where XXX is 

Содержание Hydromatic Novus 4000

Страница 1: ... provide this manual to the owner of the equip ment or to the responsible party who maintains the system NOVUS 4000 STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL Item H 03 518 Part 5625 518 1 2012 Pentair Pump Group Inc 11 02 12 ...

Страница 2: ...ler so no wires need to be disconnected Unpacking Panel Remove panel from carton When un pack ing unit check for con cealed damage Claims for damage must be made at the receiving end through the delivery carrier Dam age cannot be processed from the factory Pump Features 32 character alpha numeric liquid crystal display for level status and setpoint information Alternation selector switch on front ...

Страница 3: ...tion repair or service with re gard to the control panel refer to the schematic appropriate for that panel The schematic will provide guidance with regard to the terminal block con nec tions CAUTION A nonmetallic enclosure does not provide grounding conduit con nec tions Use grounding bush ing and jumper wires Make the Following Electrical Con nec tions a Connect the pump leads to the control pane...

Страница 4: ...pumps are selected for the maximum number of pumps If the level continues to rise then it will reach the high alarm setpoint and set a high alarm condition The high alarm light and relay will be activated If the horn is enabled then it too will be activated until the alarm condition clears or until the mute button is depressed Single Float Backup A single float backup system is provided in pump do...

Страница 5: ...oggle switch on the front panel When the switch is in the up position the alternator is on and the lead pump will be changed each cycle When the switch handle is in the center position the alternator is off and the lead pump is selected by pushing the handle down The handle has a spring return from the down position Each time the handle is pushed down the lead pump will be incremented to the next ...

Страница 6: ...UTTON This button will reset any current latched up alarms such as temp fail or on floats It will also silence the horn if an alarm is currently active 12 TEST ADJUST BUTTON AND KNOB The function of these two operators depends on the mode of the controller When the controller is in the normal not menus mode these operators are used to test the system When the TEST button is depressed and held the ...

Страница 7: ...ill take about 10 seconds 2 The display should say MAX LEVEL XX X FT where XX X is the current value This parameter is the level when the level transmitter is at 20 Ma full scale For example if the transducer is a 10 psig submersible pressure transducer then 10 psi is 23 1 feet so adjust this value to 23 1 3 If no change to this setting is required then press the MENU NEXT button To change this va...

Страница 8: ...d must be cleared by the MUTE RESET button SEAL INVR AUTO R In this mode the seal fail input is set to cause a failure if the resistance to ground is greater than 2000 ohms and the alarm will auto reset if the alarm condition clears SEAL INVR LATCH In this mode the seal fail input is set to cause a failure if the resistance to ground is greater than 2000 ohms and the alarm will latch up and must b...

Страница 9: ...lack and Red pow er wires are con nect ed to pan el correct ly 3 WARNING Live voltage can kill Check incoming power volt age to make sure that it is correct for panel and pump model 4 Energize control panel Turn on power to panel 5 Check overload relay and verify reset mode if overload is sup plied 6 WARNING Live voltage can kill Check voltage to the panel and at secondary of control trans form er...

Страница 10: ...and secondary If required 2 Contactor 3 Bulbs for any light requiring a bulb 4 Control transformer If required 5 Alternator relay If required Seal Fail Inputs Each pump has an input for the seal fail moisture sensor commonly found in submersible pumps The controller measures the resistance of the sensor In normal operation the seal fail condition is set if the resistance is less than 2000 ohms One...

Страница 11: ...c E Severe humming chat ter ing of contactors and control relays 1 There may be low voltage Check voltage at primary and secondary of control transformer us ing a volt me ter This low voltage condition may cause severe chat ter ing and burnout of contactors and relays 2 Contactor may have dust around magnet of coil struc ture Dry or clean as re quired 3 Check voltage to the control panel Contactor...

Страница 12: ...te to Highest Red Main Start c Capacitor check Make sure the ca pacitor is dis charged Use extreme caution as a spark might occur Disconnect the ca pac i tor leads and connect an analog type volt ohmmeter to the capacitor terminals Set the meter on the RX1 000 scale to check the start ca pacitor Set the meter on the RX10 000 scale to check the run ca pac i tor The meter should in di cate low ohms ...

Страница 13: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 14: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 15: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 16: ...o and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such ser...

Отзывы: