12
a. Label the leads and the
ter mi nals 1, 2, and 3
respectively.
b. Record the amperage for
each lead.
c. Move each lead to the next
terminal (1 to 2, 2 to 3,
3 to 1).
d. Again read the amperage
of each lead.
e. Move each lead to the
next terminal (1 to 3, 2 to
1, 3 to 2).
f. Again read the amperage
of each lead.
g.
If the unbalance
moves with the motor
leads, the un balance is
caused by the mo tor. If
the unbalance remains
with the terminals, the
un bal ance is in the pow er
supply.
h. If the current unbalance
exceeds five percent, nui-
sance tripping or ex ces-
sive heating will result.
i. Connect leads for the
lowest percent of current
un bal ance.
6.
Connections and start
components. Single phase
only.
a.
Disconnect all power from
the panel before making
these checks.
b. Motor winding re sis tance
read ings.
• Disconnect all three
motor leads from panel
terminal blocks.
• Using a volt-ohmmeter,
with the scale set on
RX1, measure the
resistance be tween the
leads with the chart.
Typical
Motor Resistance
Winding Leads Reading
Main
Black to
Lowest
White
Start
Black to
Next
Red Lowest
(Middle)
Both
White to
Highest
Red
(Main & Start)
c. Capacitor check.
• Make sure the ca pacitor
is dis
charged. Use
extreme caution as a
spark might occur.
• Disconnect the ca pac i tor
leads and connect
an analog-type volt-
ohmmeter to the
capacitor terminals.
• Set the meter on the
RX1,000 scale to check
the start ca
pacitor.
Set the meter on the
RX10,000 scale to
check the run ca pac i tor.
• The meter should
in di cate low ohms when
it is first connected,
but as the ca
pacitor
becomes charged
(by the meter), it will
return to a read ing of
infinity (open circuit).
d. Start relay check.
• Check coil re sistance.
It should be 3,000 to
15,000 ohms.
• Install a clamp on amp
meter around the start
wind ing lead.
• Set the amp meter scale
to at least 2 times the
pump motor full load
current.
• Place the H-O-A switch
in the Hand position to
start the pump.
• The meter should read
ap prox i mate ly 2 times
full load current during
starting.
• After the motor
has started (within
one sec
ond) the
cur rent should drop to
a value much less than
full load cur rent.
e. Motor voltage check:
Typical
Motor Voltage
Component Lead Mode Reading
Main Winding
Black to
Start
Line Voltage
White
Main Winding
Black to
Run
Line Voltage
White
Start Winding
Black to
Start
Line Voltage
Red
Start Winding
Black to
Run
120%
Red
Line Voltage
Содержание Hydromatic Novus 4000