29
involved. With keys (16) or (17)
set the number of minimum pressure units (in BARs) assigned
to the first pump (in the case of this example it is for 5.0 Bars - normally from 0.5 to 1.0 lower than maximum
pressure). Press key (18)
and set the pressure decimal value always confirming with key (18) (in
the the case of this example its for 5.0 BARs - normally from 0.5 to 1.0 lower than the maximum pressure). The following
message will be displayed:
+
-
ENTER
ENTER
PRES. Bar PO:2
MAX05.2 MIN04.7
- Line n. 1 PRESS. BAR PO: 2
Indicates the number of pumps to which the pressure levels of the following line refer to
- Line n. 2 MAX0X.XS
With keys (16)
or (17) set the number in tens of minimum pressure values for the second pump
(normally 0). Confirm by pressing key (18) . The cursor will change position depending on the number of
units involved. With keys (16)
or (17) set the number of minimumpressure units (in BARs)
assigned to the second pump. Press key (18)
and set the pressure decimal value always
confirming with key (18) . In the case of this example it is for 5.2 bars (normally 0.3-1.0 bars lower than the
value assigned to pump 1).
- Line n. 2 MIN0X.XS
With keys (16) or (17) set the number in tens of minimum pressure values for the second pump
(normally 0). Confirm by pressing key (18) . The cursor will change position depending on the number of
units involved. With keys (16) or (17) set the number of minimum pressure units (in BARs)
assigned to the second pump (in the case of this example it is for 4.7 Bars - normally from 0.5 to 1.0 lower than maximum
pressure). Press key (18) and set the pressure decimal value always confirming with key (18) (in
the case of this example it is for 4.7 BARs - normally from 0.5 to 1.0 lower than the maximum pressure). The following
message will be displayed:
+
-
ENTER
+
-
ENTER
ENTER
+
-
ENTER
+
-
ENTER
ENTER
PRES. Bar PO:3
MAX04.9 MIN04.4
- Line n. 1 PRESS. BAR PO: 3
Indicates the number of pumps to which the pressure levels of the following line refer to
- Line n. 2 MAX0X.XS
With keys (16)
or (17)
set the number in tens of maximum pressure value of the third pump
(normally 0). Confirm by pressing key (18)
. The cursor will change position depending on the number of
units involved. With keys (16)
or (17)
set the number of minimum pressure units (in BARs)
assigned to the pump which will be started third.
Press key (18)
and set the pressure decimal value always confirming with key (18)
in the
case of this example its for 4.9 BARs (normally 0.3 to 1.0 lower than the value assigned to pump 2).
+ -
+
-
ENTER
+
-
ENTER
ENTER
GB
Содержание Nocchi Pressomat
Страница 19: ...129 Fig 2 a...
Страница 20: ...130 I Fig 2 b...
Страница 21: ...131 Fig 3...
Страница 22: ...132 Fig 5...
Страница 23: ...133 Fig 4 Fig 6 Fig 7 Fig 8 Fig 9...
Страница 24: ...134 Fig 10...
Страница 27: ...253P8800 PENTAIR INTERNATIONAL S a r l Avenue de Sevelin 18 1004 LAUSANNE Switzerland...