Below is a list of common problems
and the probable causes:

WARNING: Before handling
pumps and controls, always 
disconnect power first. Do 
not smoke or use sparkable 
electrical devices or flame in a
septic (gaseous) or possible 
septic sump.

Pump will not start.

1. No power to the motor. Check

for blown fuse or open 
circuit breaker.

2. Selector switch may be in the

Off position.

3. Control circuit transformer

fuse may be blown.

4. Overload heater on starter may

be tripped. Push to reset.

Pump will not start and 
overload heaters trip.

1. Turn off power and check

motor leads with Megger or
ohmmeter for possible ground.

2. Check resistance of motor

windings. All 3 phases should
show the same reading.

3. If no grounds exist and the

motor windings check OK,
remove pump from sump 
and check for clogged or
blocked impeller.

Pump operates with selector
switch in Hand position but will
not operate in Auto position.

1. This indicates trouble in the

float level control or the 
alternator relay.

2. To check for defective 3900

control, put selector switch in

Auto position and turn off
main power. Put a jump wire
between 2 and 3 on terminal
strip. Turn on power and 
if pump starts, trouble is in 
the lower 3900 control.
Replace control.

If pump does not start, turn 
off power, remove jumper
from 2 and 3 and put jumper
wire between 1 and 2
terminals.

Turn on power and if pump
starts, trouble is in upper control.
Replace control.

If pump does not start, turn off
power and put jumper between
2 and 3 and 1 and 2 and turn on
power. If pump starts, both
lower and upper controls are
defective. If pump still does not
start, trouble is in the alternating
relay. Replace with new relay.

Pump runs but will not shut off.

1. Pump may be air locked. Turn

pump off and let set for several
minutes, then restart.

2. Lower float control may be

hung up in the closed position.
Check in sump to be sure control
is free.

3. Selector switch may be in the 

Hand position.

Pump does not deliver proper
capacity.

1. Discharge gate valve may be 

partially closed or partially clogged.

2. Check valve may be partially

clogged. Raise level up and
down to clear.

3. Pump may be running in

wrong direction. Low speed
pumps can operate in reverse
direction without much noise
or vibration.

4. Discharge head may be too

high. Check total head with
gauge when pump is operating.

Total head is discharge gauge
pressure converted to feet 
plus vertical height from 
water level in sump to center
line of pressure gauge in 
discharge line. Gauge should 
be installed on pump side of 
all valves. Multiply gauge
presure in  pounds by 2.31 to
get head in feet.

5. If pump has been in service for

some time and capacity falls
off, remove pump and check
for wear or clogged impeller.

Motor stops and then restarts
after short period but overload
heaters in starter do not trip.

1. This indicates heat sensors in

the motor are tripping due to
excessive heat. Impeller may
be partially clogged, giving a
sustained overload but not 
high enough to trip overload 
heater switch.

2. Motor may be operating out 

of liquid due to a failed 
level control. All Hydromatic
S4LRC submersible motors
can operate for extended periods
out of water without burning
up the winding, but the heat
sensors give motor prolonged
life by controlling winding
temperature.

3. Pump may be operating on a

short cycle due to sump being
too small or from water returning
to sump due to a leaking 
check valve.

Pump
Troubleshooting

Содержание Hydromatic S4LRC-3450 RPM

Страница 1: ...ease make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system Submersible Sewage Pump Recessed Impeller S4LRC 3450 RPM Pump Installa...

Страница 2: ...r starter coil so that the starter is tripped if heat sensor opens The motor starter is equipped with 3 leg overload heaters so all normal overloads are protected by the starter IMPORTANT If Hydromati...

Страница 3: ...otor guarantee is void Hydromatic electrical equipment is installed in a weatherproof NEMA 3R enclosure WARNING Do not open swing cover until you have first disconnected the power HEAT SENSOR SEAL FAI...

Страница 4: ...p to piping A check valve must be installed on each pump A gate or plug valve in each pump discharge line is also recommended This valve should be installed on the discharge side of the check valve so...

Страница 5: ...iagram for wye delta see Addendum S4LRC 701 Heat Sensors and Seal Failure Connections Be sure that heat sensor wires are connected in series with the starter coil Connections are provided on the termi...

Страница 6: ...considerable lightning occurs it is recommended that a lightning arrestor be installed at the control panel Complete data on lightning arrestors and cost are available from the factory Lightning arres...

Страница 7: ...rough bearings can be reused and it is not necessary to completely dismantle pump to change bearings If bearings are damaged with dirt or heat they must be replaced See additional instructions on repl...

Страница 8: ...sleeve to remove Seal should come off with sleeve If sleeve is not free leave in place and push off when seal plate is removed 7 To remove seal plate take out socket head flat screws and using screws...

Страница 9: ...e is in the alternating relay Replace with new relay Pump runs but will not shut off 1 Pump may be air locked Turn pump off and let set for several minutes then restart 2 Lower float control may be hu...

Страница 10: ...0 8206 000 1 PLATE INSTRUCTION 1 41 266420210 STATOR 460 3 60 40 60 HP 1 266420211 STATOR 575 3 60 40 60 HP 1 Ref Part Part No No Description Qty 42 14870 011 5 ROTOR SHAFT 40 60 HP 1 43 178 005 1 SCR...

Страница 11: ...11 Wiring Diagrams...

Страница 12: ...isposition Any transportation charges involved in such disposition shall be for the Buyer s account The Buyer s exclusive and sole remedy on account or in respect of the furnishing of material that do...

Отзывы: