Thank you for purchasing your
Hydromatic

®

pump. To help

ensure years of trouble-free 
operation, please read the 
following manual carefully.

Before Operation: 

Read the following instructions
carefully. Reasonable care and
safe methods should be practiced.
Check local codes and
requirements before installation.

Attention: 

This manual contains important
information for the safe use of
this product.  Read this manual
completely before using this
product and refer to it often for
continued safe product use.
DO NOT THROW AWAY OR
LOSE THIS MANUAL.  Keep it
in a safe place so that you may
refer to it often.

Unpacking Pump:

Remove pump from carton. When
unpacking unit, check for
concealed damage. Claims for
damage must be made at the
receiving end through the delivery
carrier. Damage cannot be
processed from the factory.

WARNING: Before handling
these pumps and controls,
always disconnect the power
first. Do not smoke or use
sparkable electrical devices or
flames in a septic (gaseous) or
possible septic sump.

The S4LRC submersible pumps
are supplied for 3 phase and 
for 460 and 575 volts. Pump is 
supplied with 30 feet of power
cord and/or 30 feet of auxiliary

General
Information

control cord. Longer cable lengths
can be furnished but must be 
specified at time of order. Power
cable is 3 & 4 wire with separate
wire for ground. Be sure green
wire is connected to a good
ground such as water pipe or
ground stake. The auxiliary cable
for seal failure and heat sensors is
also 4 wire color coded.

Heat Sensors:

All motors have heat sensor units
embedded in the motor winding to
detect excessive heat. The heat
sensors are set to trip at 105°C, so
will not operate if dangerous heat
occurs. The sensors automatically
reset when motor cools to safe
temperature.

The sensors are connected in
series with the motor starter coil
so that the starter is tripped if heat
sensor opens. The motor starter is
equipped with 3 leg overload
heaters so all normal overloads
are protected by the starter.

IMPORTANT: If Hydromatic
electrical starting equipment 
is not supplied, the heat sensor
circuit must be connected in
series with the starter coil or
warranty on motor is void.
Connection diagram is included
in this manual.

Sump Level Control:

Sump level is controlled by
Hydromatic 3900 mercury switch
controls. The 3900 control is a
mercury tube switch sealed 
in a solid polyurethane float. 
The float is held in position in the
sump by a weight attached to 
the power cord above the float. 
The cord supports the float and 
is adjusted for height from 
the surface.

Typical duplex systems use three 
controls: one set at turn-off, one

Pump
Information

Pumps Not Operating or
in Storage:

Pumps with carbon ceramic seals
must have impellers manually
rotated (6 revolutions) after setting
non-operational for 3 months or
longer and prior to electrical start-up.

Pumps with tungsten carbide seals
must have impellers manually
rotated (6 revolutions) after setting
non-operational for 3 weeks or
longer and prior to electrical start-up.

Seal Failure:

An electrode probe is installed in the
seal chamber so if any water enters
the chamber through the first seal the
electrode will be energized and a
signal will be transmitted to the
sensing unit at ground surface
causing a red light to flash. The
electrode probe is installed in all
units, but the sensing unit is supplied
at extra cost and must be ordered.

In operation the seal failure unit 
indicates only that there is some
water in the seal chamber. The pump
will continue to operate without
damage, but the seal should be
checked immediately after failure is
indicated.

CAUTION: Failure to correct
leaking seal could result in water
entering motor chamber causing
shorting out of motor.

The sensing unit is recommended 
on all installations as good 
insurance against motor failure.

Содержание Hydromatic S4LRC-3450 RPM

Страница 1: ...ease make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system Submersible Sewage Pump Recessed Impeller S4LRC 3450 RPM Pump Installa...

Страница 2: ...r starter coil so that the starter is tripped if heat sensor opens The motor starter is equipped with 3 leg overload heaters so all normal overloads are protected by the starter IMPORTANT If Hydromati...

Страница 3: ...otor guarantee is void Hydromatic electrical equipment is installed in a weatherproof NEMA 3R enclosure WARNING Do not open swing cover until you have first disconnected the power HEAT SENSOR SEAL FAI...

Страница 4: ...p to piping A check valve must be installed on each pump A gate or plug valve in each pump discharge line is also recommended This valve should be installed on the discharge side of the check valve so...

Страница 5: ...iagram for wye delta see Addendum S4LRC 701 Heat Sensors and Seal Failure Connections Be sure that heat sensor wires are connected in series with the starter coil Connections are provided on the termi...

Страница 6: ...considerable lightning occurs it is recommended that a lightning arrestor be installed at the control panel Complete data on lightning arrestors and cost are available from the factory Lightning arres...

Страница 7: ...rough bearings can be reused and it is not necessary to completely dismantle pump to change bearings If bearings are damaged with dirt or heat they must be replaced See additional instructions on repl...

Страница 8: ...sleeve to remove Seal should come off with sleeve If sleeve is not free leave in place and push off when seal plate is removed 7 To remove seal plate take out socket head flat screws and using screws...

Страница 9: ...e is in the alternating relay Replace with new relay Pump runs but will not shut off 1 Pump may be air locked Turn pump off and let set for several minutes then restart 2 Lower float control may be hu...

Страница 10: ...0 8206 000 1 PLATE INSTRUCTION 1 41 266420210 STATOR 460 3 60 40 60 HP 1 266420211 STATOR 575 3 60 40 60 HP 1 Ref Part Part No No Description Qty 42 14870 011 5 ROTOR SHAFT 40 60 HP 1 43 178 005 1 SCR...

Страница 11: ...11 Wiring Diagrams...

Страница 12: ...isposition Any transportation charges involved in such disposition shall be for the Buyer s account The Buyer s exclusive and sole remedy on account or in respect of the furnishing of material that do...