Installing 3900 Mercury 
Switch Controls:

The controls are supported by a 
mounting bracket that is attached
to sump wall or cover or to the
NEMA 4 junction box.

Cord snubbers are used to hold 
the cord in place. Control lever
can be changed at any time by
loosening the snubber and readjusting
cord length.

In either simplex or duplex system
the lower or turn-off control is set
just above the top of volute so 
that the volute will always be 
submerged during the pumping
cycle. The second or turn-on control
is set about 24 inches above the
lower turn-off control. 

More distance between turn-on
and turn-off controls can be used,
but sewage may become septic
and excessive solids may collect
for the pump to handle. A frequent
pumping cycle is recommended
for best operation.

If an alarm system is used, this
control is usually set about 6 inches
above the override control.

Some engineers as described 
previously prefer to have the
alarm control set below the 
override control.

Making Electrical Connections:

ALL ELECTRICAL WIRING
MUST BE IN ACCORDANCE
WITH LOCAL

CODE, 

AND ONLY

COMPETENT

ELECTRICIANS SHOULD
MAKE THE INSTALLATIONS.
Complete wiring diagrams are
glued to the inside cover of the
panel, and an additional set of
prints is included for use in 
making the installation. All wires
should be checked for grounds
with an ohmmeter or Megger after
the connections are made. 

This is

important, as one grounded wire 

Pump
Operations

can cause considerable trouble.

(See Fig. 1.)

IMPORTANT: If equipment is
not properly wired and protected
as recommended, the motor
guarantee is void.

NOTE: For wiring diagram for
wye delta see Addendum
S4LRC-701.

Heat Sensors and Seal Failure
Connections:

Be sure that heat sensor wires are
connected in series with the
starter coil. Connections are 
provided on the terminal strip; see
wiring diagram.

If seal failure unit is used, connect
as shown with seal failure system.
If seal failure unit is not used, the
two seal failure wires are left
open. 

DO NOT CONNECT

POWER TO THESE LINES AT
ANY TIME.

(See Figs. 2 and 3.)

Starting System:

1. Turn the H-O-A switch to 

Off position, then turn on main
circuit breakers.

2. Open all discharge valves 

and allow water to rise in 
sump pump.

3. Turn H-O-A switch to Hand

position on one pump and
notice operation. If pump is
noisy and vibrates, rotation is
wrong. To change rotation 
interchange any two line leads
to motor on 3ø only. DO NOT
INTERCHANGE MAIN 
INCOMING LINES. If duplex 
system, check second pump in
the same manner. 

4. Now set both H-O-A switches

to Auto position and allow
water to rise in sump until one
pump starts. Allow pump to
operate until level drops to
turn-off point.

5. Allow sump level to rise to

start other pump. Notice run

WARNING

BLACK

COIL

ON-OFF

SWITCH

L1

THERMOSTATS

IN SERIES

WHITE

L2

TWO WIRE CONTROL OFFERING AUTOMATIC RESET

THERMOSTATS

IN SERIES

WHITE

L2

BLACK

THREE WIRE CONTROL OFFERING AUTOMATIC RESET

L1

COIL

OL

OL

START

IN CERTAIN APPLICATIONS THE NEC MAY REQUIRE THREE OVERLOAD RELAYS

COLOR

PURPOSE

DARK GREEN

SEAL FAILURE

RED

SEAL FAILURE

BLACK

HEAT SENSOR

WHITE

HEAT SENSOR

WARRANTY IS VOID IF HEAT SENSORS ARE NOT

CONNECTED AS SHOWN (IN SERIES WITH CONTACTOR OIL)

DESIGNATION FOR OPTIONAL

SEAL FAILURE & SENSOR CORD

See Wiring Diagram of seal failure
unit #4673 or 4674 for connecting
dark green and red wires. If seal fail-
ure unit #4673 or 4674 is not used,
leave dark green and red wires open.

Fig. 3

Содержание Hydromatic S4LRC-3450 RPM

Страница 1: ...ease make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system Submersible Sewage Pump Recessed Impeller S4LRC 3450 RPM Pump Installa...

Страница 2: ...r starter coil so that the starter is tripped if heat sensor opens The motor starter is equipped with 3 leg overload heaters so all normal overloads are protected by the starter IMPORTANT If Hydromati...

Страница 3: ...otor guarantee is void Hydromatic electrical equipment is installed in a weatherproof NEMA 3R enclosure WARNING Do not open swing cover until you have first disconnected the power HEAT SENSOR SEAL FAI...

Страница 4: ...p to piping A check valve must be installed on each pump A gate or plug valve in each pump discharge line is also recommended This valve should be installed on the discharge side of the check valve so...

Страница 5: ...iagram for wye delta see Addendum S4LRC 701 Heat Sensors and Seal Failure Connections Be sure that heat sensor wires are connected in series with the starter coil Connections are provided on the termi...

Страница 6: ...considerable lightning occurs it is recommended that a lightning arrestor be installed at the control panel Complete data on lightning arrestors and cost are available from the factory Lightning arres...

Страница 7: ...rough bearings can be reused and it is not necessary to completely dismantle pump to change bearings If bearings are damaged with dirt or heat they must be replaced See additional instructions on repl...

Страница 8: ...sleeve to remove Seal should come off with sleeve If sleeve is not free leave in place and push off when seal plate is removed 7 To remove seal plate take out socket head flat screws and using screws...