Pump
Information

The electrical equipment includes
a main circuit breaker for each
pump, a magnetic starter with
overload protection for each
pump, an H-O-A switch and run
light for each pump, an electric
alternator and a transformer to
provide 115 volts for control 
circuit and alarms.

Overload Heaters:

If the Hydromatic electrical panel
is not used, starters with 3 leg
overload protection must be
supplied. On 3 phase pumps the
heaters must be sized in 
accordance with the nameplate
amps on the motor housing. The
amp draw on these submersible
motors is slightly higher than a
corresponding horsepower surface
motor, so heaters must be sized by
the nameplate rating.

IMPORTANT: If other than
Hydromatic starters are used be
sure the heat sensor wires are
connected in series with the
starter coil circuit. Typical
wiring diagrams are included.

HYDR-O-RAIL:

If the pump or pumps are to be
used with the HYDR-O-RAIL
system, the pumps will be
equipped with guide brackets and
hydraulic sealing flange.

manually. Impeller may be slightly
stuck due to factory test water 
so it must be broken loose with 
small bar or screwdriver in edge
of vanes. The impeller should 
turn freely.

Clean all trash and sticks from
sump and connect pump to piping.

A check valve must be installed
on each pump. A gate or plug
valve in each pump discharge line
is also recommended. This valve
should be installed on the 
discharge side of the check valve
so if necessary to service the
check valve, the line pressure can
be cut off. Single pump systems
are sometimes installed without a
check valve where it is desirable
to self-drain the discharge line to
prevent freezing. This can be done
only with short discharge lines,
otherwise water will return to the
sump and cause short cycling of
the pump.

NEMA

4 Junction Box

(Optional):

If electrical control panel is to be
set remote from the sump pump, 
a NEMA 4 junction box should be
used to make power and control
connections. The Hydromatic
NEMA 4 junction box is provided
with compression connectors for
sealing all wires. No sealing 
compound is needed to make 
connections waterproof.

Wiring diagrams are provided
with panel for making connections.
An extra set of diagrams is included
so that one set can be used in the
sump when making connections.
The size wire to use from panel to
sump depends on motor size and
distance in feet. 

The table on page 3 can be used as
a guide for wire size.

Be sure each wire is checked out
so that wrong connections will not
be made.

Pump
Installation

        

     

460 VOLTS

GREEN

L3

L2

L1

3

2

1

9

8

7

6

5

4

       

     

 

    

 

 

    

    

 

 

Fig. 1

Fig. 2

Installing Pump in Sump:

Before installing pump in sump,
lay it on its side and turn impeller

Содержание Hydromatic S4LRC-3450 RPM

Страница 1: ...ease make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system Submersible Sewage Pump Recessed Impeller S4LRC 3450 RPM Pump Installa...

Страница 2: ...r starter coil so that the starter is tripped if heat sensor opens The motor starter is equipped with 3 leg overload heaters so all normal overloads are protected by the starter IMPORTANT If Hydromati...

Страница 3: ...otor guarantee is void Hydromatic electrical equipment is installed in a weatherproof NEMA 3R enclosure WARNING Do not open swing cover until you have first disconnected the power HEAT SENSOR SEAL FAI...

Страница 4: ...p to piping A check valve must be installed on each pump A gate or plug valve in each pump discharge line is also recommended This valve should be installed on the discharge side of the check valve so...

Страница 5: ...iagram for wye delta see Addendum S4LRC 701 Heat Sensors and Seal Failure Connections Be sure that heat sensor wires are connected in series with the starter coil Connections are provided on the termi...

Страница 6: ...considerable lightning occurs it is recommended that a lightning arrestor be installed at the control panel Complete data on lightning arrestors and cost are available from the factory Lightning arres...

Страница 7: ...rough bearings can be reused and it is not necessary to completely dismantle pump to change bearings If bearings are damaged with dirt or heat they must be replaced See additional instructions on repl...

Страница 8: ...sleeve to remove Seal should come off with sleeve If sleeve is not free leave in place and push off when seal plate is removed 7 To remove seal plate take out socket head flat screws and using screws...

Страница 9: ...e is in the alternating relay Replace with new relay Pump runs but will not shut off 1 Pump may be air locked Turn pump off and let set for several minutes then restart 2 Lower float control may be hu...

Страница 10: ...0 8206 000 1 PLATE INSTRUCTION 1 41 266420210 STATOR 460 3 60 40 60 HP 1 266420211 STATOR 575 3 60 40 60 HP 1 Ref Part Part No No Description Qty 42 14870 011 5 ROTOR SHAFT 40 60 HP 1 43 178 005 1 SCR...

Страница 11: ...11 Wiring Diagrams...

Страница 12: ...isposition Any transportation charges involved in such disposition shall be for the Buyer s account The Buyer s exclusive and sole remedy on account or in respect of the furnishing of material that do...

Отзывы: