With your installation partner supporting the weight of the system, perform steps 3, 4 and 5:
Step 3.
On the rear side of the cabinet, install the two blades (B) in the selected rack unit, using four
M6 screws (C). Do not tighten the screws yet. See Figure 29.
Step 4.
Slide the two blades into the left and right rails, and adjust them to fit your rack's depth. Use
four M6 screws (D) to fix the blades into the rack. Do not tighten the screws yet. See Figure 30.
Figure 27: Sliding the Blades in the Rails
Step 5.
Secure the system in the rack by tightening the 8 screws inserted in Step 3 and Step 4 with a
torque of 4.5±0.5 Nm.
Side by Side Mounting for Arctica 1600cs Rail Kit
A designated rail kit for the Arctica 1600cs systems can be purchased
separately.
This section is relevant to short-depth systems that permit this type of
installation.
For safety, it is necessary that at least two people mount the system in the
rack.