![background image](http://html1.mh-extra.com/html/penguin-computing/arctica-1600cs/arctica-1600cs_installation-manual_1523849028.webp)
Rev. 1.0
Penguin Computing
28
Figure 20: Sliding the Switch into the Rack
Step 7.
When fully inserted, fix the switch by closing the remaining 2 screws in the middle and
tightening the 8 screws inserted in Step 2 with a torque of 4.5±0.5 Nm.
Removing the System from the Rack
Follow these steps to remove a unit from the rack:
Step 1.
Turn off the system and disconnect it from peripherals and from the electrical outlet.
Step 2.
Unscrew the two M6 screws securing the front of the inner rails’ ears to the outer rails and to
the rack.
Step 3.
Pull the unit out until braking is felt. For safety purposes, the locking mechanism will not allow
a complete removal of the unit at this stage.