![PEMTECH PT2000/H Series Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/pemtech/pt2000-h-series/pt2000-h-series_operators-manual_1523673005.webp)
5
Operators Manual Model PT2000/H Series Gas Monitor Rev 2. January 2014
1.0 Quick Setup Guide / Check List
Follow step by step instruction below for quick setup of the system. Details are
outlined in the section number referred in the right column.
Step #
Description
Refer
Section #
1
If the unit is to use Alarm Text messaging function then an active SIM
Card must be installed in order for onboard Cell Module to activate.
See Section on
SIM Card Installation
for details.
3.1
2
Install PT2000 Series Wireless Controller in safe and indoor.
3
Inside the Controller move the AC Circuit Breaker (Next to AC/DC Power
supply) in OFF position (downward). Connect AC Power to the Unit as
per local Electrical codes.
3.5
4
For proper wireless communication antenna must be installed at an
elevated level connected to the controller with the coax cable. Use the
antenna and the coax cable supplied with the controller. Using
antenna and or cable other than the one supplied by Pem-Tech could
result in inefficient data communication between the detectors and the
controller.
3.3
5
If Hardwired Audio/Visual Alarm Station is to be used then follow the
wiring diagram for the Alarm station referred later in the manual.
If Wireless Remote Alarm Relay Module is used then refer to Wiring
Diagram Drawing # B2013138 in Appendix A
3.4
6
Verify AC Power Connection and then apply AC power to the unit.
Move the Circuit Breaker to UPWARD position to turn the unit ON.
3.5
7
Unit is shipped with default setting for H2S and LEL alarm levels and 12
wireless detectors as Active (for a 24 Channel Unit). The Controller is
ready to receive the data from wireless detectors if installed. However, if
the detectors are not installed then after 2-5 minutes each detector
data block on the display screen will indicate
Comm Fail
. Once
detectors are on-line this message will clear and the sensor reading will
appear in the data block of the main display screen.