46
Operators Manual Model PT2000/H Series Gas Monitor Rev 2. January 2014
3.
To change the address, hold the magnetic wand
position. The sensor address will be increment by 1 at a time. Hold the magnet
until the desired sensor address is displayed and then remove the magnet. The
address number rolls over to 0 after reaching the maximum address limit (typical
address limit is 32)
4.
After changing the sensor address the LCD will display the Zone ID. The user may
now change the Zone ID. The default zone ID is 0. In order for all the sensor and
controller to communicate this zone ID must he identical.
5.
To change the Zone ID hold the magnet until desired zone id is displayed on the
LCD and then remove the magnet.
6.
Few seconds after the magnet is removed, the unit will return to normal operation.
The sensor may re-boot if the zone id is modified. The new zone ID will be
retained in the non-volatile memory and will be recalled upon next power up.
Caution
The default Zone ID is 0 set at the factory for all the detectors and the controller. In
order for the controller and the all the detectors on the Network to communication
properly the Zone ID of all the detectors and the controller must be identical.
However, the sensor Address must be distinct. It is recommended that the sensor
addresses should all be in numerical order and any address should not be skipped.
Zone ID should be modified or changed only if more than 1 system is being used in a
close proximity or within the communication range.