1
2
24
Pressure
T
1
T
2
T
3
VARIABLE SPEED FAN (0-10VDC)
COMMONS ARE INTERNALLY
INTERCONNECTED
Y
W
G
W2
Y2
G2
W3
Y3
C
R
D
S1
S2
C
A1
C
A2
C
24VAC
OUTSIDE
AIR
HIGH
LOW
L2
L1 (HOT)
TRANSFORMER
SUPPLY DUCT
STATIC PROBE
AMBIENT AIR
RETURN
AIR
SUPPLY
AIR
3
4
5
6
COMPRESSOR STAGE 1 RELAY
REVERSING VALVE (O/B) RELAY
FAN ENERGIZE RELAY
AUXILIARY HEAT RELAY
COMPRESSOR STAGE 2 RELAY
COMPRESSOR STAGE 3 RELAY
Fig. 19
Variable Speed Fan Wiring Guide
(Heat Pump)
The following wiring diagram is for a heat pump with a variable speed fan (VFD).
2
3
4
5
Y/W/G/W2/Y2/G2/W3/Y3 OUTPUTS ARE 24VAC @ 1A. ONLY CONNECT THE
OUTPUTS REQUIRED FOR YOUR SYSTEM. PROVIDE PROPERLY SIZED
RELAYS/CONTACTORS AS NEEDED.
POWER SUPPLY. PROVIDE A DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED. POWER TO EQUIPMENT IS 24VAC. SIZE
TRANSFORMERS AS NEEDED.
A1 IS A 0-10VDC OUTPUT FOR MODULATING THE FAN SPEED.
INSTALL STATIC PROBE IN SUPPLY/DISCHARGE AIR DUCT. RECOMMEND
INSTALLATION OF AT LEAST SIX (6) FEET AWAY FROM FAN OR ANY BENDS IN
DUCT WORK.
USED FOR AMBIENT AIR PRESSURE SENSING. SOME APPLICATIONS MAY
REQUIRE RUNNING ADDITIONAL TUBING TO THE OUTSIDE OF HVAC UNIT.
T1/T2/T3 ARE 10K TYPE 2 TEMPERATURE PROBE INPUTS.
SUPPLY AND RETURN AIR TEMPERATURE PROBES ARE MANDATORY FOR
PROPER OPERATION.
1
6
NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5
USE THE (G) 24VAC OUTPUT TO ENERGIZE
THE FAN. PROVIDE PROPERLY SIZED
RELAY/CONTACTORS AS NEEDED.
G