1
2
3
5
6
USE THE (G) 24VAC OUTPUT TO ENERGIZE
THE FAN. PROVIDE PROPERLY SIZED
RELAY/CONTACTORS AS NEEDED.
7
G
19
Pressure
T
1
T
2
T
3
ECONOMIZER (0-10VDC) POSITION FEEDBACK
VARIABLE SPEED FAN (0-10VDC)
ECONOMIZER (0-10VDC) ACTUATOR
COMMONS ARE INTERNALLY
INTERCONNECTED
Y
W
G
W2
Y2
G2
W3
Y3
C
R
D
S1
S2
C
A1
C
A2
C
24VAC
OUTSIDE
AIR
HIGH
LOW
L2
L1 (HOT)
TRANSFORMER
SUPPLY DUCT
STATIC PROBE
AMBIENT AIR
RETURN
AIR
SUPPLY
AIR
4
Fig. 14
Variable Speed Fan and Economizer Wiring Guide
(Conventional)
The following wiring diagram is for a conventional system with a variable speed fan (VFD)
and economizer.
2
3
4
5
1
6
7
Y/W/G/W2/Y2/G2/W3/Y3 OUTPUTS ARE 24VAC @ 1A. ONLY CONNECT THE
OUTPUTS REQUIRED FOR YOUR SYSTEM. PROVIDE PROPERLY SIZED
RELAYS/CONTACTORS AS NEEDED.
POWER SUPPLY. PROVIDE A DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED. POWER TO EQUIPMENT IS 24VAC. SIZE
TRANSFORMERS AS NEEDED.
S2 IS A 0-10VDC INPUT FOR ECONOMIZER ACTUATOR POSITION FEEDBACK FAULT
DETECTION AND DIAGNOSTICS.
A1 IS A 0-10VDC OUTPUT FOR MODULATING THE FAN SPEED. A2 IS A 0-10VDC
OUTPUT FOR MODULATING THE ECONOMIZER ACTUATOR.
INSTALL STATIC PROBE IN SUPPLY/DISCHARGE AIR DUCT. RECOMMEND
INSTALLATION OF AT LEAST SIX (6) FEET AWAY FROM FAN OR ANY BENDS IN
DUCT WORK.
USED FOR AMBIENT AIR PRESSURE SENSING. SOME APPLICATIONS MAY
REQUIRE RUNNING ADDITIONAL TUBING TO THE OUTSIDE OF HVAC UNIT.
T1/T2/T3 ARE 10K TYPE 2 TEMPERATURE PROBE INPUTS.
SUPPLY AND RETURN AIR TEMPERATURE PROBES ARE MANDATORY FOR
PROPER OPERATION.
IF AN EXHAUST FAN IS INSTALLED AND NEEDS
TO BE ENERGIZED DURING ECONOMIZATION,
CONNECT THE (G2) 24VAC OUTPUT TO THE
EXHAUST FAN. PROVIDE PROPERLY SIZED
RELAY/CONTACTORS AS NEEDED.
G2
NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5
COMPRESSOR STAGE 1 RELAY
HEAT STAGE 1 RELAY
FAN ENERGIZE RELAY
HEAT STAGE 2 RELAY
COMPRESSOR STAGE 2 RELAY
EXHAUST FAN RELAY
HEAT STAGE 3 RELAY
COMPRESSOR STAGE 3 RELAY
FOR DUAL DUCT APPLICATIONS, INSTALL ONE Z8
TO MANAGE THE COLD SYSTEM AND A SECOND
Z8 TO MANAGE THE HEAT SYSTEM (AS SHOWN
ON PAGE 8 FIGURE 5). IF THERE IS A SINGLE FAN,
ONLY CONNECT ONE OF THE Z8 CONTROLLERS
TO ENERGIZE THE FAN.
CONTACT PELICAN TECHNICAL SUPPORT FOR
FURTHER ASSISTANCE AT 888.-512-0490 OR