POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
POWER TO Z8 AND WIRELESS MODULE IS 24VAC. SIZE TRANSFORMER AS NEEDED.
WIRE CONNECTING THE WIRELESS MODULE TO THE Z8 CAN BE STANDARD UNSHIELDED COPPER
THERMOSTAT WIRE UP TO 500 FEET.
Pressure
High
(HOT)
TRANSFORMER
24VAC
C
Low
T
1
T
2
T
3
Wiring the Z8 to the Wireless Module (if removed from Z8 base)
3
1
2
2
3
1
WARNING
The following Operation and Application diagrams are to be used as reference to the
most common application where the Z8 will be installed to control specific HVAC
systems. For dual ducted applications, two Z8s will need to be installed. One for the
hot deck and the other for the cold deck (reference Fig 4.3 and 4.4). In the case the
system you are connecting the Z8 to is not defined in this installation guide. Contact
Pelican Technical Support for assistance at 888-512-0490 or email
13
NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5
Fig. 8