LIST OF FIRST LEVEL VARIABLES (User level)
Var
MEANING
DEF.
r0
Temperature differential in relation to principal
SET-POINT < Range: 0,2 ÷ 10,0°C >
Expressed in absolute values and defines hysteresis
(positive if mOd=0 or negative if mOd=1) of
temperature in relation to SET POINT.
2,0
d0
Defrosting interval
< Range: 0 ÷ 24 hours >
If d0=0 defrosting is excluded.
4
dd2
Delayed defrost for the second evaporator
<Range: 0 ÷ 10 sec > - 0 = contemporary start
The defrost process of the second evaporator starts
dd2 seconds after the defrost process of the first
evaporator. This avoids overloading the electrical
system during the defrost process in the event of
limited power. When dd2=0, defrost processes 1
and 2 start simultaneously.
dd2 is forced to 0 if d1 = 1 or 2. (Cycle inversion
defrosting)
d21
Defrosting 1 end set point
< Range:-35 ÷ 45°C >
Defrosting 1 is not performed if the temperature
read by the defrosting probe is higher than value
d21. (In the event of a defective probe, defrosting 1
is performed on a time basis.)
15
d22
Defrosting 2 end set point
< Range:-35 ÷ 45°C >
Defrosting 2 is not performed if the temperature
read by the defrosting probe is higher than value
d22. (In the event of a defective probe, defrosting 2
is performed on a time basis.)
15
d31
Maximum defrosting time
< Range: 1 ÷ 240 min >
25
d32
Maximum defrosting time
< Range: 1 ÷ 240 min >
25
d7
Dripping duration < Range:0 ÷ 10 min >
At completion of defrosting the compressor and fans
remain inactive for the set period of time d7 and the
defrosting LED on the front of the board flashes.
0
F5
Fan stop after defrosting < Range: 0 ÷ 10 min >
Keeps fans inactive for a period of time F5 after
dripping. This period is timed from the end of
dripping. If dripping is not set, the fans pause directly
after defrosting.
0
A1
Minimum temperature alarm
< Range: - 45 ÷ (A2-1)°C >
Absolute temperature referred to by the ambient
probe below which, following the ALD delay, the
LOW temperature alarm is triggered, activating the
buzzer (if present) and showing the letters EL
alternating with the temperature on the display, as
well as the flashing alarm icon.
-45
A2
Maximum temperature alarm
< Range: (A1+1) ÷ 99°C >
Absolute temperature referred to by the ambient
probe above which, following the ALD delay, the
HIGH temperature alarm is triggered, activating the
buzzer (if present) and showing the letters EH
alternating with the temperature on the display, as
well as the flashing alarm icon. When the alarm is
reset the alarm icon remains on without flashing to
indicate that the event occurred, until the UP key is
pressed.
99
tE1
Evaporator 1 probe temperature display
< °C > (does not display anything if dE1 =1)
reading
only
tE2
Evaporator 2 probe temperature display
< °C > (does not display anything if dE2 =1)
reading
only
dFr
Evaporators defrost enabling in real time
With d0=0 and dFr=1 it is possible to set up until 6
defrosts in real time in one day through the
paramenters dF1…dF6 .
0
dF1
..6
Evaporators defrosts times programming
It is possible to set up to 6 times for defrosts (from
00,0 ÷ 23,5 )
The time is in the mode HH.M where HH represents
the hour and M the ten minutes(i.e. 0=0 min.; 1=10
min. etc.). The winking point (.) shows that it is
displayed a time and not a temperature.
0
tdS Day start time programming (from 00,0 ÷ 23,5 )
6,00
tdE Day end time programming (from 00,0 ÷ 23,5 )
22,0
LIST OF SECOND LEVEL VARIABLES (Installer level)
Var
MEANING
DEF.
nrE
Number of evaporators < Range: 1 ÷ 2 >
Configuring nrE=1 disables evaporator 2 probe
input. It becomes a second digital input (DI2).
1
F3
Fan status with compressor off < Range: 0 ÷ 2 >
0 = Fans in continuous operation
1 = Fans ON only with compressor ON
2 = Fans disabled
1
F4
Fan pause during defrosting < Range: 0 ÷ 1 >
0 = Fans ON during defrosting
1 = Fans OFF during defrosting
1
Fst
FAN disable TEMPERATURE < Range: - 45 ÷ 99°C >
The fans remain disabled if the temperature value
read by the evaporator probe is higher than the
value of this parameter. The fans are re-enabled
with the evaporator probe deactivated or in error.
99
Fd
Fst. differential
< Range: 1 ÷ 10°C >
2
dE1
Evaporator 1 probe exclusion < Range: 0 ÷ 1 >
0 = Evaporator 1 probe present
1 = Evaporator 1 probe absent
By excluding the evaporator probe, defrosting
occurs cyclically based on d0 period and
terminates upon the elapse of d31 time.
0
dE2
Evaporator 2 probe exclusion < Range: 0 ÷ 1 >
0 = Evaporator 2 probe present
1 = Evaporator 2 probe absent
By excluding the evaporator probe, defrosting
occurs cyclically based on d0 period and
terminates upon the elapse of d32 time.
0
d1
Defrosting type < Range: 0 ÷ 3 >
0 = Heating element
1 = Cycle inversion (hot gas)
2 = Cycle inversion (hot gas) with basin
3 = Heater with temperature control
0
dPo
Defrost at Power-on < Range: 0 ÷ 1 >
0= Disabled
1= Defrost at Controller power on (if possible)
0
dSE
Smart defrost < Range: 0 ÷ 1 >
0 = disabled 1 = enabled
0
dSt
Smart defrost Setpoint (if dSE=1)
<Range: -30 ÷ 30°C>
The counting of the time between the defrost is
incremented only if the compressor is ON and the
coldest evaporator temperature is less than dSt.
1
C1
Minimum time between each turning off and on of
the compressor < Range: 0 ÷ 15 min >
0
CE1
Duration of compressor ON time in the case of faulty
ambient probe (emergency mode).
< Range: 0 ÷ 240 min / 0=Disabled >
If CE1=0 the emergency mode in the presence of
error EO remains disabled, the compressor
remains off and defrosting is prevented in order
to conserve the remaining cold.
0
CE2
Duration of compressor OFF time in the case of
faulty ambient probe (emergency mode).
< Range: 5 ÷ 240 >
5
doC
Compressor timeout due to door switch opened
< Range: 0 ÷ 5 min >
When the door switch opens, the evaporator fans
turn off and the compressor continues to function
for a period doC, after which it turns off.
0
Tdo
Compressor re-activation time after door opened
(with In1 or In2 = +2 o -2)
< Range: 0 ÷ 240 min / 0=Disabled >
When the door switch opens and after the time tdo,
normal function of the control is restored, generating
the door open alarm (Ed).
Delay time of cold room light alarm signalling and
visualization (with dO3 or dO4 = +4 or -4)
< Range: 0 ÷ 240 min / 0=Disabled >
On switching on of the light with UP key and passed
the Tdo time, the E9 alarm starts. If it has silenced and
the light has not swiched off on new Tdo time limit,
the alarm starts again. If dO3/4 is set as alarm relay,
the E9 alarm will excite the relay.
0
mOd
Thermostat functioning mode < Range: 0 ÷ 1 >
0 = Cold function
1 = Hot function (in this mode defrosting and fan
disable Fst are excluded)
0
In1
Digital Input DI1 and activation mode setting
< Range: -8 ÷ 8 >
8= Night mode digital input (energy saving) (N.O.)
7= Pump-down pressure switch (N.O., see dO3/4=5 or -5)
6= Stop defrosting remotely (N.O.)
(reads leading edge of impulse)
5= Start defrosting remotely (N.O.)
(reads leading edge of impulse)
4= Stand-by remotely (N.O.)
(In order to indicate Stand-By mode, the display shows
‘Ino’ alternating with the current view)
3= Man-in-room alarm (N.O.)
2= Door switch (N.O.)
1= Compressor protection (N.O.)
0= Disabled
-1= Compressor protection (N.C.)
-2= Door switch (N.C.)
-3= Man-in-room alarm (N.C.)
-4= Stand-by remotely (N.C.)
(‘Ino’ alternating with the current view is displayed to
indicate stand-by mode)
-5= Start defrosting remotely (N.C.)
(reads leading edge of impulse)
-6= Stop defrosting remotely (N.C.)
(reads leading edge of impulse)
-7= Pump-down pressure switch (N.C., see dO3/4=5 or -5)
-8= Night mode digital input (energy saving) (N.C.)
1
In2
Digital Input DI2 and activation mode setting (with
nrE=1)
< Range: -8 ÷ 8 >
Such as In1
2
dO3
Digital Output DO3 setting
(OUTPUT WITH POTENTIAL-FREE CONTACT)
< Range: -8 ÷ 8 >
8= Hot relay for neutral zone management (NO)
7= Energised relay with defrosting 2 (NO)
6= Energised relay with defrosting 1 (NO)
5= Energised relay with activated cold function
(evaporator solenoid). The DO1 output is
activated by the digital input, set in 1 as Pump-
down pressure switch (In 1=7 or –7)
4= Light room output (It is automatically activated
when the door is open and with the man in room
alarm E8) (NO)
3= Relay energised in night mode
2=Energised relay with DO1 energised compressor
output. Used for motor condenser unit.
1= Relay energised in alarm presence
0= Relay Deactivated
-1= Relay de-energised in alarm presence
-2= Relay de-energised with DO1 energised
compressor output. Used for carter resistance.
-3= Relay de-energised in night mode
-4=Light room output (It is automatically activated
when the door is open and with the man in room
alarm E8) (NC)
-5= De-energised relay with activated cold
function (evaporator solenoid). The DO1 output is
activated by the digital input, set in 1 as Pump-
down pressure switch (In 1/2=7 or –7)
-6= De-energised relay with defrosting 1 (NC)
-7= De-energised relay with defrosting 2 (NC)
-8= Hot relay for neutral zone management (NC)
6
dO4
DO4 digital output operation settings
(OUTPUT WITH POTENTIAL-FREE CONTACT)
<Range: -8 ÷ 8>
Such as dO3
4
dnE
Night mode enable (energy saving)
0 = disabled / 1 = enabled
At night operation decimal point flashes.
0
nSC
Correction factor for the SET button during
night operation (energy saving)
< Range: -20,0 to +20,0 ° C >
During night operation the control set is:
- If mod = 0 => Set Control = Set + NSC
- If mod = 1 => Set Control = Set - NSC
0,0
LSE
Minimum value attributable to set point
< Range: -45 ÷ (HSE-1) °C >
-45
HSE
Maximum value attributable to set point
< Range: (LSE+1) ÷ +99 °C >
99
BEE
Buzzer state
0 = buzzer deactivated 1=buzzer activated
1
CAL
Ambient probe value correction
< Range: -10,0 ÷10,0 °C >
0,0
Ald
Delay time for signalling and display of minimum
and maximum temperature alarm
< Range: 0 ÷ 240 >
120
Ad
Network address for connection to TeleNET or
Modbus supervision system
< Range:
0 ÷ 31 (SEr=0)
1 ÷ 247 (SEr=1)
1
SEr
Remote control
0= TeleNET protocol 1= Modbus-RTU protocol
0
bdr
Modbus baudrate
5
0=300 baud
1=600 baud
2=1200 baud
3=2400 baud
4=4800 baud
5=9600 baud
6=14400 baud
7=19200 baud
8=38400 baud
Prt
Modbus parity check Configuration
0 = none | 1= even | 2= odd
0
P1
Password: protection type
( active when PA is different from 0)
< Range: 0 ÷ 3 >
0= Displays only the set point and allows alarm
stop + keylock echo
1= Displays the set point, allows alarm stop, +
d light
2= Blocks access to levels 1 and 2 during
programming (all other functions permitted)
3= Blocks access to level 2 during programming
(all other functions permitted)
3
PA
Password (see P1 for protection type)
< Range: 0 ÷ 999 / 0=Disabled >
0
Yr Year set
0…99
Mo Month set up
1…12
dy Day set up
1…31
Hr Time set up
0…23
min Minutes set up
0…59
dEF Reserved parameter
---
reL Release software
12 read
only
E N G L I S H
dd2
forced 0