LIST OF FIRST LEVEL VARIABLES (User level) 

Var 

MEANING 

DEF. 

r0 

Temperature  differential  in  relation  to  principal 

SET-POINT    < Range: 0,2 ÷ 10,0°C > 

Expressed in absolute  values and  defines  hysteresis 

(positive  if  mOd=0  or  negative  if  mOd=1)  of 

temperature in relation to SET POINT. 

2,0 

d0 

Defrosting interval 

< Range: 0 ÷ 24 hours > 

If d0=0 defrosting is excluded. 

dd2 

Delayed defrost for the second evaporator  

<Range: 0 ÷ 10 sec > - 0 = contemporary start 

The defrost process of the second evaporator starts 

dd2  seconds  after  the  defrost  process  of  the  first 

evaporator.  This  avoids  overloading  the  electrical 

system  during  the  defrost  process  in  the  event  of 

limited  power.    When  dd2=0,  defrost  processes  1 

and 2 start simultaneously. 

dd2 is forced to 0 if d1 = 1 or 2. (Cycle inversion 

defrosting) 

 

d21 

Defrosting 1 end set point 

< Range:-35 ÷ 45°C > 

Defrosting  1  is  not  performed  if  the  temperature 

read  by  the  defrosting  probe  is  higher  than  value 

d21. (In the event of a defective probe, defrosting 1 

is performed on a time basis.) 

15 

d22 

Defrosting 2 end set point 

< Range:-35 ÷ 45°C > 

Defrosting  2  is  not  performed  if  the  temperature 

read  by  the  defrosting  probe  is  higher  than  value 

d22. (In the event of a defective probe, defrosting 2 

is performed on a time basis.) 

15 

d31 

Maximum defrosting time 

< Range: 1 ÷ 240 min > 

25 

d32 

Maximum defrosting time 

< Range: 1 ÷ 240 min > 

25 

d7 

Dripping duration     < Range:0 ÷ 10 min > 

At completion of defrosting the compressor and fans 

remain inactive for the set period of time d7 and the 

defrosting LED on the front of the board flashes. 

 

F5 

Fan stop after defrosting     < Range: 0 ÷ 10 min > 

Keeps  fans  inactive  for  a  period  of  time  F5  after 

dripping.  This  period  is  timed  from  the  end  of 

dripping. If dripping is not set, the fans pause directly 

after defrosting. 

 

A1 

Minimum temperature alarm 

< Range: - 45 ÷ (A2-1)°C > 

Absolute  temperature  referred  to  by  the  ambient 

probe  below  which,  following  the  ALD  delay,  the 

LOW  temperature alarm  is  triggered,  activating  the 

buzzer  (if  present)  and  showing  the  letters  EL 

alternating with the temperature on  the  display, as 

well as the flashing alarm icon. 

-45 

A2 

Maximum temperature alarm 

< Range: (A1+1) ÷ 99°C  > 

Absolute  temperature  referred  to  by  the  ambient 

probe  above  which,  following  the  ALD  delay,  the 

HIGH temperature alarm is triggered, activating the 

buzzer  (if  present)  and  showing  the  letters  EH 

alternating with the temperature on  the  display, as 

well  as  the  flashing  alarm  icon.  When  the  alarm  is 

reset the alarm icon remains on without flashing to 

indicate that the event occurred, until the UP key is 

pressed. 

99 

tE1 

Evaporator 1 probe temperature display 

< °C  >  (does not display anything if dE1 =1) 

reading 

only 

tE2 

Evaporator 2 probe temperature display 

< °C  > (does not display anything if dE2 =1) 

reading 

only 

dFr 

Evaporators defrost enabling in real time 

With d0=0 and  dFr=1 it  is possible to set  up until  6 

defrosts  in  real  time   in  one  day  through  the 

paramenters dF1…dF6 . 

dF1

..6 

Evaporators defrosts times programming 

It is possible to set up to 6 times for defrosts (from 

00,0 ÷ 23,5 ) 

The time is in the mode HH.M where HH represents 

the hour and M the ten minutes(i.e. 0=0 min.; 1=10 

min.  etc.).  The  winking  point  (.)  shows  that  it  is 

displayed a time and not a temperature. 

tdS  Day start time programming (from 00,0 ÷ 23,5 ) 

6,00 

tdE  Day end time programming (from 00,0 ÷ 23,5 ) 

22,0 

 

LIST OF SECOND LEVEL VARIABLES (Installer level) 

Var 

MEANING 

DEF. 

nrE 

Number of evaporators < Range: 1 ÷ 2 > 

Configuring  nrE=1  disables  evaporator  2  probe  

input. It becomes a second digital input (DI2). 

F3 

Fan status with compressor off    < Range: 0 ÷ 2 > 

0 = Fans in continuous operation 

1 = Fans ON only with compressor ON 

2 = Fans disabled 

F4 

Fan pause during defrosting < Range: 0 ÷ 1 > 

0 = Fans ON during defrosting 

1 = Fans OFF during defrosting 

Fst 

FAN disable TEMPERATURE  < Range: - 45 ÷ 99°C >

 

The fans remain disabled if the temperature value 

read  by  the  evaporator  probe  is  higher  than  the 

value  of  this  parameter.  The  fans  are  re-enabled 

with the evaporator probe deactivated or in error. 

99 

Fd 

Fst. differential 

< Range: 1 ÷ 10°C > 

dE1    

Evaporator 1 probe exclusion < Range: 0 ÷ 1 > 

0 = Evaporator 1 probe present 

1 = Evaporator 1 probe absent 

By  excluding  the  evaporator  probe,  defrosting 

occurs  cyclically  based  on  d0  period  and 

terminates upon the elapse of d31 time. 

 

dE2 

Evaporator 2 probe exclusion < Range: 0 ÷ 1 > 

0 = Evaporator 2 probe present 

1 = Evaporator 2 probe absent 

By  excluding  the  evaporator  probe,  defrosting 

occurs  cyclically  based  on  d0  period  and 

terminates upon the elapse of d32 time. 

d1  

Defrosting type < Range: 0 ÷ 3 > 

0 = Heating element 

1 = Cycle inversion (hot gas) 

2 = Cycle inversion (hot gas) with basin 

3 = Heater with temperature control 

dPo 

Defrost at Power-on           < Range: 0 ÷ 1 > 

0= Disabled 

1= Defrost at Controller power on (if possible) 

dSE 

Smart defrost   < Range: 0 ÷ 1 > 

0 = disabled          1 = enabled 

dSt 

Smart defrost Setpoint (if dSE=1) 

<Range: -30 ÷ 30°C> 

The  counting  of  the  time  between  the  defrost  is 

incremented  only  if  the  compressor  is  ON  and  the 

coldest evaporator temperature is less than dSt. 

C1 

Minimum time between each turning off and on of 

the compressor < Range: 0 ÷ 15 min > 

CE1 

Duration of compressor ON time in the case of faulty 

ambient probe (emergency mode).  

< Range: 0 ÷ 240 min / 0=Disabled > 

If CE1=0  the emergency  mode in the  presence of 

error  EO  remains  disabled,  the  compressor 

remains  off  and  defrosting  is  prevented  in  order 

to conserve the remaining cold. 

CE2 

Duration  of  compressor  OFF  time  in  the  case  of 

faulty ambient probe (emergency mode).  

< Range: 5 ÷ 240 > 

doC 

Compressor timeout due to door switch opened 

< Range: 0 ÷ 5 min > 

When the door switch opens, the evaporator fans 

turn off and the compressor continues to function 

for a period doC, after which it turns off. 

Tdo 

Compressor  re-activation  time  after  door  opened 

(with In1 or In2 = +2 o -2) 

< Range: 0 ÷ 240 min / 0=Disabled >  

When the  door  switch  opens and  after the time tdo, 

normal function of the control is restored, generating 

the door open alarm (Ed). 

Delay time of cold room light alarm signalling and 

visualization (with dO3 or dO4 = +4 or -4) 

< Range: 0 ÷ 240 min / 0=Disabled > 

On switching on of the light with UP key and  passed 

the Tdo time, the E9 alarm starts. If it has silenced and 

the  light  has  not  swiched  off  on  new  Tdo  time  limit, 

the  alarm  starts again. If  dO3/4 is set as alarm relay, 

the E9 alarm will excite the relay.

 

mOd 

Thermostat functioning mode     < Range: 0 ÷ 1 > 

0 =   Cold function 

1 =   Hot function (in this mode defrosting and fan 

disable Fst are excluded) 

In1 

Digital Input DI1 and activation mode setting 

< Range: -8 ÷ 8 > 

8= Night mode digital input (energy saving) (N.O.) 

7= Pump-down pressure switch (N.O., see dO3/4=5 or -5) 

6= Stop defrosting remotely (N.O.) 

(reads leading edge of impulse) 

 5= Start defrosting remotely (N.O.) 

(reads leading edge of impulse) 

 4= Stand-by remotely (N.O.) 

(In order to indicate Stand-By mode, the display shows 

‘Ino’ alternating with the current view) 

 3= Man-in-room alarm (N.O.) 

 2= Door switch  (N.O.) 

 1= Compressor protection (N.O.) 

 0= Disabled 

-1= Compressor protection (N.C.) 

-2= Door switch (N.C.) 

-3= Man-in-room alarm (N.C.) 

-4= Stand-by remotely (N.C.) 

(‘Ino’  alternating  with  the  current  view  is  displayed  to 

indicate stand-by mode) 

-5= Start defrosting remotely (N.C.) 

(reads leading edge of impulse) 

-6= Stop defrosting remotely (N.C.) 

(reads leading edge of impulse) 

-7= Pump-down pressure switch (N.C., see dO3/4=5 or -5) 

-8= Night mode digital input (energy saving)  (N.C.) 

In2 

Digital Input DI2 and activation mode setting (with 

nrE=1)      

< Range: -8 ÷ 8 > 

Such as In1 

dO3 

Digital Output DO3 setting 

(OUTPUT WITH POTENTIAL-FREE CONTACT)  

< Range: -8 ÷ 8 > 

8= Hot relay for neutral zone management (NO) 

7= Energised relay with defrosting 2 (NO) 

6= Energised relay with defrosting 1 (NO) 

5=  Energised  relay  with  activated  cold  function 

(evaporator  solenoid).  The  DO1  output  is 

activated  by  the  digital  input,  set  in  1  as  Pump-

down pressure switch (In 1=7 or –7) 

 4= Light room output (It is automatically activated 

when the door is open and with the man in room 

alarm E8) (NO) 

3= Relay energised in night mode 

2=Energised relay with DO1 energised compressor 

output. Used for motor condenser unit. 

 1= Relay energised in alarm presence 

 0= Relay Deactivated 

-1= Relay de-energised in alarm presence 

-2= Relay de-energised with DO1 energised 

compressor output. Used for carter resistance. 

-3= Relay de-energised in night mode 

-4=Light room output (It is automatically activated 

when the door is open and with the man in room 

alarm E8) (NC) 

-5=  De-energised  relay  with  activated  cold 

function (evaporator solenoid). The DO1 output is 

activated  by  the  digital  input,  set  in  1  as  Pump-

down pressure switch (In 1/2=7 or –7) 

-6= De-energised relay with defrosting 1 (NC) 

-7= De-energised relay with defrosting 2 (NC) 

-8= Hot relay for neutral zone management (NC) 

dO4 

DO4 digital output operation settings 

(OUTPUT  WITH  POTENTIAL-FREE  CONTACT) 

<Range: -8 ÷ 8> 

 Such as dO3 

dnE 

Night mode enable (energy saving) 

0 = disabled   /   1 = enabled 

At night operation decimal point flashes. 

nSC 

Correction factor for the SET button during 

night operation (energy saving) 

< Range: -20,0 to +20,0 ° C > 

During night operation the control set is: 

- If mod = 0 => Set Control = Set + NSC 

- If mod = 1 => Set Control = Set - NSC 

0,0 

LSE 

Minimum value attributable to set point 

< Range: -45 ÷ (HSE-1) °C > 

-45 

HSE 

Maximum value attributable to set point 

< Range: (LSE+1) ÷ +99 °C > 

99 

BEE 

Buzzer state 

0 = buzzer deactivated            1=buzzer activated 

CAL 

Ambient probe value correction  

< Range: -10,0 ÷10,0 °C > 

0,0 

Ald 

Delay time for signalling and display of minimum 

and maximum temperature alarm  

< Range: 0 ÷ 240 > 

120 

Ad 

Network address for connection to TeleNET or 

Modbus supervision system 

< Range: 

 0 ÷ 31    (SEr=0) 

 

 1 ÷ 247  (SEr=1)  

SEr 

Remote control 

0= TeleNET protocol       1= Modbus-RTU protocol 

bdr 

Modbus baudrate 

0=300 baud          

1=600 baud 

2=1200 baud 

   3=2400 baud 

   4=4800 baud 

   5=9600 baud 

6=14400 baud 

7=19200 baud 

8=38400 baud 

Prt 

Modbus parity check Configuration 

0 = none   |   1= even  |   2= odd 

P1 

Password: protection type 

( active when PA is different from 0) 

< Range: 0 ÷ 3 > 

0= Displays only the set point and allows alarm 

stop + keylock echo 

1= Displays the set point, allows alarm stop, + 

d light 

2= Blocks access to levels 1 and 2 during 

programming (all other functions permitted) 

3= Blocks access to level 2 during programming 

(all other functions permitted) 

PA 

Password (see P1 for protection type) 

< Range: 0 ÷ 999 / 0=Disabled > 

Yr  Year set 

0…99

 

Mo  Month set up 

1…12

 

dy  Day set up 

1…31

 

Hr  Time set up 

0…23

 

min  Minutes set up 

0…59

 

dEF  Reserved parameter 

--- 

reL  Release software 

12 read 

only 

 

E   N   G   L   I   S   H  

 

dd2 

forced  0 

 

Содержание Expert nano 200NANO4CK13

Страница 1: ...un BIP di conferma e lo strumento viene portato in stand by MENU HACCP PER LA VISUALIZZAZIONE DELLA REGISTRAZIONE DELL ULTIMO ALLARME DI TEMPERATURA AVVENUTO Stand by Premere contemporaneamente per p...

Страница 2: ...ntato solo se il compressore acceso e la temperatura dell evaporatore pi freddo inferiore a dSt 1 C1 Tempo minimo tra lo spegnimento e la successiva Accensione del compressore Range 0 15 min 0 CE1 Tem...

Страница 3: ...3 secondi forza la fine dello sbrinamento incorso Ilfine sbrinamento manuale salta anche lo sgocciolamento SBRINAMENTO A GAS CALDO Impostare il parametro d1 1 o d1 2 per la gestione dello sbrinamento...

Страница 4: ...it per le possibiliinesattezze contenute nelpresente manuale se dovute aderroridistampa o ditrascrizione e si riservaildirittodiapportareaipropriprodottiquellemodifichecheriterr necessarieoutili senza...

Страница 5: ...enerated to confirm and the system is placed in Stand By mode HACCP MENU FOR VISUALIZATION OF THE LAST TEMPERATURE ALARM RECORDING Stand by Push UP and STAND BY keys simultaneously for over 3 sec To a...

Страница 6: ...imum time between each turning off and on of the compressor Range 0 15 min 0 CE1 Duration of compressor ON time in the case of faulty ambient probe emergency mode Range 0 240min 0 Disabled If CE1 0 th...

Страница 7: ...Counter of the nr of temperature alarm events occurred being memorized data of the latest temperature alarm event the counter is boosted to know if previously other alarms occurred This counter resets...

Страница 8: ...l doesnotacceptresponsibilityforanyinaccuracieswhichmaybepresentinthismanualinthecasethattheseareduetoprintingortranscriptionerrorsandreservestheright tomake modificationstoitsproductswhichitdeemsnec...

Отзывы: