background image

 

 

nano LINE

 

200NANO4CK13 / 14  

 

 

PEGO S.r.l. 

Via Piacentina, 6/b - 45030 -  ROVIGO 

Tel : +39(0)425 762906 - Fax: +39(0)425 762905 

www.pego.it   -  e-mail: [email protected] 

 

200NANO4CK13-14_01-19_ITA_ENG  #  Rev.01-19  #  25/03/2019
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 
 

MANUAL DEFROSTING ACTIVATION 

To  activate  defrosting  simply  press  the  DOWN  key  for  more  than  3 

seconds;  this  activates  the  heating  elements  relay.  Defrosting  is  not 

activated  if  the  appropriate  conditions  are  not  present  (end-of-

defrosting temperature (d21 or d22) set lower than the temperature 

read by the evaporator probe). Defrosting terminates when the end-of 

defrosting  temperature  (d21  or  d22)  is  reached  or  for  a  maximum 

defrosting time (d31 or d32) or by manually forced end-of-defrosting 

(end-of-defrosting key or digital input). 

 

MANUALLY FORCED END OF CURRENT DEFROSTING 

Pressing the DOWN key for 3 seconds during defrosting forces the 

end  of  the  current  defrosting.  In  the  case  of  manual  end-of-

defrosting, dripping is also excluded. 

 

HOT GAS DEFROSTING 

Set  the  parameter    d1  =  1  or  2  for  the  management  of  inversion 

defrost cycle. During the entire defrosting process the compressor 

and defrost relays are activated. In this case, you can not set defrost 

in  succession,  dd2  is  forced  to  0.  During  dripping  (d7)  the 

compressor stops and, if d1=2, the defrost relays remain activated  

in  order  to  ensure  the  ignition  of  the  resistances  of  the  basins.  If 

d1=2  it  may  be  necessary  to  add  external  electromechanical 

components for proper control of the solenoid valves. 

For  a  correct  control  of  the  system,  the  installer  must  use  the 

defrost output which must allow the opening of the inversion cycle 

electrovalve  and  closing  of  the  liquid  electrovalve.  For  capillary 

systems  (without  thermostatic  valve)  it  is  sufficient  to  control  the 

inversion cycle electrovalve using the defrost relay command. 

 

HEATER DEFROST BY TIME WITH TEMPERATURE CONTROL 

Set the parameter  d1=3 for the management of heater defrost by 

time with temperature control. During the defrost the outputs are 

activated when the evaporator’s temperatures are lower than d21 

or  d22.  Defrost  stops  after  d31  or  d32  minutes.  It  allows    energy 

saving and a better defrost process. 

 

AMBIENT  TEMPERATURE  DISPLAY  DURING  AND  AFTER 

DEFROSTING  

During defrosting and for a minute following the end of defrosting, 

the display continues to display the last ambient temperature value 

read before start of defrosting.

   

 

RS-485 CONNECTION 

Connection to a RS485 network must be chain type, avoiding star 

connections and observing A and B polarity. It is advisable to use 

BELDEN  8762  cables.  The  configuration  of  the  device  in  the 

TeleNET program is performed by entering the module name such 

as “Expert  Nano4CK  rel.3 or higher” and assigning  to  it  the same 

network  address  entered  in  the  variable  Ad.  For  a  Modbus-RTU 

network  connection  and  for  details  on  the  protocols  of  these 

devices, refer to the manual “MODBUS-RTU_EXP_DIN_NANO4CK” 

which can be downloaded from our internet site: www.pego.it. 

 

HACCP ALARM MANAGEMENT 
With ambient probe temperature ≤ A1 , after the Ald time, the EL 

low temperature alarm is activated.  

With ambient probe temperature ≥ A2 , after the Ald time, the EH 

high temperature alarm is activated.  

During a high or low temperature alarm, the display alternates the 

visualisation of the  temperature  with  the  EH or EL  headings;  the 

alarm  relay  is  activated  (if  set),  the  Buzzer  (silenceable)  and  the 

alarm bell icon (flashing).  

When  the  set  alarm  conditions  are  turned  off,  alarm  signals 

automatically  undo  (the  alarm  relay  is  deactivated,  the  buzzer  is 

silenced and the normal visualisation is reactivated). 

The alarm bell icon remains on (fix) to indicate that EH or EL alarm 

was  triggered  and  the  memorisation  of  the  event  (see  HACCP 

menu for displaying the last temperature alarm activated). To get 

the alarm, push the arrow button up when the fix bell light is on. 

Besides, the starting date of the latest EH or EL event is registered, 

together with its duration and its maximum or minimum reached 

temperature. 
 
 
 

 

A  counter  of  the  nr  of  occurred  alarms  from  the  latest  alarm 

reset (max 99 alarms can be counted) is also present. 

To  display  data related  to  the last  temperature alarm, enter in 

the  HACCP  menu  (push  the  arrow  button  up  +  stand-by  for  3 

seconds). Inside the menu, all the data can be scrolled with the 

up and down arrows or they can  be reset, by pressing the SET 

button  +  arrow  up  button  for  5  seconds.  Once  the  reset 

occurred,  a  BIP  with  the  buzzer  is  provided  to  confirm  the 

occurred cancelation. To exit the menu, wait 10 seconds without 

pressing  anything  or  press  simultaneously  the  up  and  down 

arrows. 

HACCP  variables  are  available  in  read-only  mode  and  are  the 

following: 

 

VARIABLE LIST HACCP LEVEL  

(Values in read-only) 

E## 

Indicates the latest 

activated 

temperature alarm. 

EH = high temperature 

alarm  

EL = low temperature 

alarm 

-- = no alarms have been 

activated from the latest 

reset 

### 

Temperature peak 

value reached during 

the latest EH or EL 

alarm 

-45…+45°C 

--- = no alarms have been 

activated from the latest 

reset 

y## 

Year of the start of 

the latest 

temperature alarm 

y 00 – y99 

y -- = no alarms have been 

activated from the latest 

reset 

M## 

Month of the start of 

the last temperature 

alarm 

M 01 – M12 

M -- = no alarms have been 

activated from the latest 

reset 

d## 

Day of the start of the 

last temperature 

alarm 

d 01 – d31 

d -- = nessun allarme 

intervenuto dall’ultimo 

reset 

h## 

Hour of the start of 

the last temperature 

alarm 

h 00 – h24 

h -- = no alarms have been 

activated from the latest 

reset 

m## 

Minutes of the start 

of the last 

temperature alarm 

m 00 – m59 

m -- = no alarms have been 

activated from the latest 

reset 

t## 

Duration (hours) of 

the last temperature 

alarm 

t 00 – t99 

t -- = no alarms have been 

activated from the latest 

reset 

C## 

Counter of the nr of 

temperature alarm 

events occurred 

(being memorized data of 

the latest  temperature 

alarm event, the counter is 

boosted to know if 

previously other alarms 

occurred. This counter 

resets with the memorized 

alarm reset (silenced 

 SET for 5 sec.) It is 

implemented at every new 

temperature alarm.) 

C 00 – C99 

C -- = no alarms have been 

activated from the latest reset 

 
DIAGNOSTICS 

The  display  shows  ‘orH’  for  temperature  out  of  range 

greater than +99.9°C. It shows  ‘orL’ for temperature out of 

range less than -45.0°C. 

In the case of faults, the “Expert nano” control unit informs the 

operator by means of alarm codes shown on the display and an 

acoustic  signal emitted  by  the  buzzer (if  present).  The  acoustic 

alarm  can  be  stopped  by  pressing  the  UP  key  (the  error  code 

remains) and can be reactivated by pressing the SET key. In the 

event of an alarm, one of the following messages is displayed: 

 
ALARM CODE TABLE 

Var 

MEANING 

E0  Functional fault of ambient probe. 

Eu1 

Functional fault of defrosting probe (in this case, any defrosting 

processes will have a duration equal to time d31). 

Eu2  Functional fault of defrosting probe (in this case, any defrosting 

processes will have a duration equal to time d32). 

E2  EEPROM memory error.  All outputs are deactivated except for 

alarm outputs if present. 

E8  Man-in-room alarm. 

Ec 

Compressor protection alarm (e.g. thermal protection or max. 

pressure  switch).  All  outputs  are  deactivated  except  for  the 

alarm output if present. 

Ed 

Door open  alarm.  When  the  door  switch  opens  and  the  tdo 

time  has  elapsed,  normal  function  of  the  control  is  reset, 

triggering the door open alarm (Ed). 

EL  Minimum  temperature  alarm.  The  letters  EL  flash  alternating 

with the temperature (see parameter A1). 

EH  Maximum temperature alarm. The letters EH flash alternating 

with the temperature (see parameter A2). 

E9 

Room  light  alarm.  The  letters  E9  flash  alternating  with  the 

temperature (see parameter  dO3/4 and Tdo). 

E6  Clock failure alarm 

 
 
 

THERMOSTAT FUNCTION MODES (mOd) 

The variable mOd allows the selection of function mode of the 

thermostat, in particular: 

- COLD MODE (mOd=0) 

The DO1 output is activated when the temperature measured by 

the ambient probe reaches or exceeds the SET POINT+r0 value 

and  remains  active  until  the  temperature  drops  below  the  SET 

POINT.  In  this  mode,  the  DO1  output  is  linked  to  the  cold 

function icon. 

dO3/dO4  can  be  configured  as  hot  relay  for  neutral  zone 

management.  The  output  is  activated  when  the  ambient 

temperature is lower than SET POINT-r0 and remains active until 

the temperature exceeds the SET POINT. 

 

- HOT MODE (mOd=1) 

The DO1 output is activated when the temperature measured by 

the  ambient  probe  reaches  or  exceeds  the  SET  POINT-r0  value 

and remains active until the temperature increases and exceeds 

the SET POINT. In this mode, the DO1 output is linked to the hot 

function icon; defrosting and fan stop FSt are DISABLED. 

 

 

PASSWORD FUNCTION 

The  password  function  is  activated  by  entering  a  value  other 

than  0  for  the  PA  parameter.  See  parameter  P1  for  various 

protection levels. The protection is activated automatically if the 

keyboard remains inactive for about 30 seconds. The figure 000 

appears  on  the  display.  Use  the  up/down  keys  to  change  the 

number  and  the  SET  key  to  confirm.  The  password  entry 

template 000 disappears if the keyboard is not activated within 

30  seconds.  If  you  forget  the  password,  use  the  universal 

number 100. 

 

EMERGENCY MODE IN THE CASE OF ERROR EO 

This safety mode guarantees the functioning of the compressor 

even  in  the case of a  faulty ambient  probe (error  EO). If  probe 

errors E0 and CE1 are different to 0, the compressor functions in 

operation  pause  mode,  with  compressor  ON  for  the  time  CE1 

and  OFF  for  the  time  CE2.  If  CE1>0  in  the  case  of  error  E0, 

defrosting  is  performed  in  normal  functioning  mode.  If  CE1=0 

the  emergency  mode  in  the  presence  of  error  E0  remains 

disabled.  The  compressor  remains  off  and  defrosting  is 

prevented to conserve the remaining cold. Eliminate as soon as 

possible  the  cause  of  error  E0  and  reactivate  the  control’s 

normal function for a correct temperature adjustment. 

 

 

 

 

 

 

 

 

E   N   G   L   I   S   H  

 

TECHNICAL DATA

 

Power Supply 

Power voltage 

12V  +10/-15%  50-60Hz  / 12Vdc +10/-15%  class 2 

Absorbed power  

3 VA  Max 

Environment conditions 

Operating temperature 

-5T55°C  - humidity < 90% Rel. Hum. Not condensing 

Storage temperature 

-20T70°C - humidity < 90% Rel. Hum.  Not condensing 

Unsuitable operating 

environments 

Environments with strong vibrations or impacts; aggressive, polluted or corrosive atmospheres, exposure to direct 

solar radiation, explosive atmospheres or flammable gas. 

General characteristics 
Display 

3-Digit with sign, decimal point and 9 LED status indicators 

Resolution 

0.1 °C 

Probe precision (electronic) 

± 0.5 °C 

Reading range 

-45T99 °C 

200NANO4CK14 

Connector for temperature repeater ECHO 

Clamps

 

Power clamps: extractable, screw for cables with c/section 0.2 to  2.5mm

2

 

Signal clamps: extractable, screw for cables with c/section  0.2 to  1.5mm

2

 

Software class: A  /  Parameters saved on non-volatile memory (EEPROM) 
Input characteristics 
Analogue inputs 

3 Inputs for NTC probes (10K Ώ 1%  at 25°C)   

Digital inputs 

1 Input (clean contact) 

Output characteristics (free voltage contact) 
Compressor relay (DO1) 

N.O.  16(6)A  / 250V  

Fan relay  (DO2) 

N.O.  8(3)A    /  250V  

Heating elements relay (DO3) 

N.O.  8(3)A   /  250V  

Relay (DO4) 

N.O.  8(3)A   /  250V  

Buzzer 

Present 

Dimensional, insulation and mechanical characteristics 
Dimensions 

93x37x65mm  Depth 59mm   (Depth 69mm with removable clamps) 

Drill hole template 

71x29mm (+0.2/-0.1mm) 

Front protection rating 

IP65 with front board installation 

Installation 

In front of board by means of rear fastening clips or or two front screws 

Casing 

Plastic PC+ABS UL94 V-0 body, PC transparent front, Key panel PC or PC+ABS 

Insulation type 

Class II 

Conformity with EU low voltage directives, electromagnetic compatibility and EC mark 
Conforms to following EU Directives : Directives 2014/30/EU, 2014/35/EU. 

Conforms to following harmonised standards: EN60730-1:2016, EN60730-2-9:2010, EN61000-6-1:2007,  EN61000-6-3:2007 

 

Содержание Expert nano 200NANO4CK13

Страница 1: ...un BIP di conferma e lo strumento viene portato in stand by MENU HACCP PER LA VISUALIZZAZIONE DELLA REGISTRAZIONE DELL ULTIMO ALLARME DI TEMPERATURA AVVENUTO Stand by Premere contemporaneamente per p...

Страница 2: ...ntato solo se il compressore acceso e la temperatura dell evaporatore pi freddo inferiore a dSt 1 C1 Tempo minimo tra lo spegnimento e la successiva Accensione del compressore Range 0 15 min 0 CE1 Tem...

Страница 3: ...3 secondi forza la fine dello sbrinamento incorso Ilfine sbrinamento manuale salta anche lo sgocciolamento SBRINAMENTO A GAS CALDO Impostare il parametro d1 1 o d1 2 per la gestione dello sbrinamento...

Страница 4: ...it per le possibiliinesattezze contenute nelpresente manuale se dovute aderroridistampa o ditrascrizione e si riservaildirittodiapportareaipropriprodottiquellemodifichecheriterr necessarieoutili senza...

Страница 5: ...enerated to confirm and the system is placed in Stand By mode HACCP MENU FOR VISUALIZATION OF THE LAST TEMPERATURE ALARM RECORDING Stand by Push UP and STAND BY keys simultaneously for over 3 sec To a...

Страница 6: ...imum time between each turning off and on of the compressor Range 0 15 min 0 CE1 Duration of compressor ON time in the case of faulty ambient probe emergency mode Range 0 240min 0 Disabled If CE1 0 th...

Страница 7: ...Counter of the nr of temperature alarm events occurred being memorized data of the latest temperature alarm event the counter is boosted to know if previously other alarms occurred This counter resets...

Страница 8: ...l doesnotacceptresponsibilityforanyinaccuracieswhichmaybepresentinthismanualinthecasethattheseareduetoprintingortranscriptionerrorsandreservestheright tomake modificationstoitsproductswhichitdeemsnec...

Отзывы: