Premere per 

sganciare

 

Pannello

 

 
 
 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

DESCRIPTION 

The  Expert  nano  model  200NANO4CK13/14  is  an  electronic 

regulator  operating  with  microprocessor  designed  to  control 

refrigerated  counters,  display  windows  and  static  or  ventilated 

refrigeration units with off-cycle, electrical or  hot gas defrosting 

also in real time clock (RTC). It is fitted with three analogue inputs 

for NTC temperature probes one of which configurable as digital 

input,  another  digital  input,  four  relays  for  the  control  of  the 

compressor,  fans,  light  and  defrosting  evaporator  and  buzzer. 

Two  relays  can  be  set  as:  alarm  relay,  simultaneously  to  the 

compressor  output,    room  light,  cold  function  for  pump  down 

operation,  second defrosting relay, night relay or hot relay. The 

regulator can be also configured for heat applications. 

 

 

PRINCIPAL CHARACTERISTICS 

 

Can be configured for cold, hot or neutral zone applications. 

 

Relay  for  compressor  and  evaporator  fan  management  (2  non 

configurable  relays)  and  defrosting  resistances  1  and  2,  alarm, 

pump  down  start,  room  light  and  compressor  output  (2 

configurable relays). 

 

Clock for programmed defrosts (RTC), up to 6 starts in 24h. 

 

Defrosting can be configured for off-cycle, heating element, cycle 

inversion  and  cycle  inversion  with  basin    and  frequency  and 

duration can be set. End-of- defrosting can be based on time or 

temperature. 

 

Key operated manual START/STOP defrosting. 

 

Key operated ON/OFF. 

 

Night / day management (energy saving). 

 

Smart defrost functionality (energy saving). 

 

Cold  room  light  ON/OFF  switch  with  key  or  by  means  of  door 

switch (if defrost output is configured like cold room light). 

 

Display/adjustment of temperature with decimal point. 

 

Flat front surface for easy cleaning and keys of ample dimensions 

which can be customised with various colours (on request). 

 

3-Digit LED display with sign, decimal point and system status icon.  

Internal buzzer for acoustic signals. 

 

PEGO programming philosophy guaranteeing immediate start-up. 

 

RS485 serial connection with Modbus-RTU  or Telenet protocol. 

 

IP65 front protection. Two-fold fastening option: clips / screws. 

 

Power supply 12Vac. 

 

HACCP  function  for  memorization  and  visualization  of  the  last 

temperature alarm. 

 

200NANO4CK14  Model  with  Connector  for  temperature  repeater 

ECHO. 

 

 

COMBINED ACTIVATION OF KEYS AND THEIR FUNCTIONS 

FUNCTION / KEY COMBINATION 

SETTINGS PROGRAMMING   /

  (Set + 

 o 

 

Press  the  SET  key  to  view  the  current  SETPOINT  value 

(temperature). 
Keeping the SET key down and pressing either the (

) or (

key, the SETPOINT value can be changed. 

Release the SET key to return to view the room temperature; 

the changes made will be automatically saved. 

LEVEL 1 PROGRAMMING /

  (

 + 

 

Press the UP and DOWN keys simultaneously for over 3 sec. to 

access  the  Level  1  programming  menu.  When  the  menu  is 

accessed, a BIP is generated to confirm. The system leaves the 

menu after 30 seconds. 

LEVEL 2 PROGRAMMING

/ (

+

+Stand-by) 

 

Press  the  UP,  DOWN  and  STAND-BY  keys  simultaneously  for 

over 3 sec. to access the Level 1 programming menu. When the 

menu is accessed, a BIP is generated to confirm and the system 

is placed in Stand-By mode. 

HACCP  MENU  FOR  VISUALIZATION  OF  THE  LAST 
TEMPERATURE ALARM RECORDING /

 (

+ Stand-by) 

 
Push UP and STAND-BY keys simultaneously for over 3 sec. To 
access the HACCP menu. 
A BIP is generated to confirm. 

EXIT PROGRAMMING MENUS  /

  (

 + 

 

Pressing  the  UP  and  DOWN  buttons  simultaneously  in  any 

programming menu for over 3 sec. causes the system to save 

the settings entered and leave that menu. A BIP is generated to 

confirm. 
 

 

NANO4CK SERIE MODELS AND ACCESSORIES 

PEGO CODE 

EXPERT NANO DESCRIPTION 

200NANO4CK13 

Power  supply  12Vac,  4  relays  (8A+8A+8A+16A), 

digital  input,  hot/cold  funct.,  RTC,  RS485,  pump  

down,  buzzer, extractable terminals. 

200NANO4CK14 

Power  supply  12Vac,  4  relays  (8A+8A+8A+16A), 

digital  input,  hot/cold  funct.,  RTC,  RS485,  pump  

down,  buzzer, extractable terminals, Connector for 

temperature repeater ECHO

 

KC-TTLB-L2.5 

Connection  cable    for  temperature  repeater  ECHO 

Lenght=2.5m 

200NANOTTL02  Temperature repeater Display (ECHO)

 

 

 

 

 

 
 

E   N   G   L   I   S   H  

 

STATUS ICON 

ICON 

MEANING 

 

COLD FUNCTION ICON (icon activated with mOd=0)   

Led OFF = Cold function OFF 

Led ON =  Cold function ON 

Flashing Led = Cold function ON  waiting for C1 delay 

 

HOT FUNCTION ICON  

Led OFF = Hot function OFF 

Led ON = Hot function ON   

 

FAN ICON   

Led OFF = Fans OFF 

Led ON =  Fans ON   

Flashing  Led  =  Fans  paused  after  defrosting  (see 

parameter F5) 

 

DEFROSTING ICON  (icon activated with mOd=0)   

Led OFF = Defrosting OFF 

Led ON =  Defrosting ON   

Led  Flashing  =  Dripping  in  progress  after  defrosting 

(see parameter d7) 

 

DOOR SWITCH / ROOM LIGHT ICON 

Led OFF = Door switch not activated or not used and 

room light off 

Led  ON  =  Room  light  ON    (function  active  only  if 

variable dO3=1 or dO4=3) 

Flashing Led = Door switch activated or room light ON 

with alarm E8. 

 

ALARM ICON 

Led OFF = No alarm present 

Led  ON  =  Indicates  temperature  alarm  intervention 

with remedy (HACCP alarm). 

Flashing Led =  Alarm present 

 

CLOCK ICON 

Led OFF = Defrosts in real time disabled 

Led ON =  Defrosts in real time enabled 

 

KEY FUNCTIONS 

Key 

FUNCTION 

 

UP KEY 

Increases  values  /  Scrolls  parameters  in  ascending 

order  /  Deactivates  acoustic  alarm  if  present  / 

Acknowledges  an  alarm.  With  variable  dO3=4  or 

dO4=4 if pressed for over 3 sec, activates/deactivates 

room light (DO3 or DO4 output). 

With  manual  activation/  deactivation  of  the  light  a 

BIP is generated to confirm. 

 

DOWN KEY 

Decreases  values  /  Scrolls  parameters  in  descending 

order  /  If  pressed  for  over  3  sec.  activates  manual 

defrosting (if suitable conditions are present). 

Terminates defrosting if pressed for over 3 sec. during 

the  defrosting  process.  With  manual  activation/ 

deactivation  of  defrosting  a  BIP  is  generated  to 

confirm. 

Stand 

by

 

STAND-BY KEY 

If pressed for over 1 sec. alternates the Stand-By with 

normal  mode  and  vice  versa.  When  mode  is 

alternated a BIP is generated to confirm. In Stand-By 

mode  the  system  stops  and  the  display  signals  OFF 

and the temperature alternating. 

 

SET KEY 

Displays the set point. 

Allows  the  set  point  to  be  entered  when  pressed  in 

combination with the DOWN or UP keys. Resets the 

acoustic alarm if present. 

 

DRILL HOLE TEMPLATE (mm)

 

 

THERMOSTAT DIMENSIONS (mm)

 

ECHO Connector only 
for 200NANO4CK12

 

200NANO4CK14

 

KC-TTLB-L2.5

 

200NANOTTL02

 

ECHO DIMENSIONS (mm)

 

ELECTRICAL CONNECTIONS

 

FASTENING TO PANEL BY MEANS OF TWO BACK CLIPS 

FASTENING TO PANEL BY MEANS OF TWO FRONT SCREW 

screw 

2.9x9.5mm

 

Screw2.9x9.5m

m

 

Distance between hole 
centres : 77mm

 

Содержание Expert nano 200NANO4CK13

Страница 1: ...un BIP di conferma e lo strumento viene portato in stand by MENU HACCP PER LA VISUALIZZAZIONE DELLA REGISTRAZIONE DELL ULTIMO ALLARME DI TEMPERATURA AVVENUTO Stand by Premere contemporaneamente per p...

Страница 2: ...ntato solo se il compressore acceso e la temperatura dell evaporatore pi freddo inferiore a dSt 1 C1 Tempo minimo tra lo spegnimento e la successiva Accensione del compressore Range 0 15 min 0 CE1 Tem...

Страница 3: ...3 secondi forza la fine dello sbrinamento incorso Ilfine sbrinamento manuale salta anche lo sgocciolamento SBRINAMENTO A GAS CALDO Impostare il parametro d1 1 o d1 2 per la gestione dello sbrinamento...

Страница 4: ...it per le possibiliinesattezze contenute nelpresente manuale se dovute aderroridistampa o ditrascrizione e si riservaildirittodiapportareaipropriprodottiquellemodifichecheriterr necessarieoutili senza...

Страница 5: ...enerated to confirm and the system is placed in Stand By mode HACCP MENU FOR VISUALIZATION OF THE LAST TEMPERATURE ALARM RECORDING Stand by Push UP and STAND BY keys simultaneously for over 3 sec To a...

Страница 6: ...imum time between each turning off and on of the compressor Range 0 15 min 0 CE1 Duration of compressor ON time in the case of faulty ambient probe emergency mode Range 0 240min 0 Disabled If CE1 0 th...

Страница 7: ...Counter of the nr of temperature alarm events occurred being memorized data of the latest temperature alarm event the counter is boosted to know if previously other alarms occurred This counter resets...

Страница 8: ...l doesnotacceptresponsibilityforanyinaccuracieswhichmaybepresentinthismanualinthecasethattheseareduetoprintingortranscriptionerrorsandreservestheright tomake modificationstoitsproductswhichitdeemsnec...