59
TROUBLESHOOTING
Table 10.1: Control Board Blocking Error Codes (automatic reset):
“E”
CODE
Error Display
Internal
No.
Error Description
Corrective Action
E01
SUPPLY SENSOR
NOT CONNECTED
51
Supply sensor not connected.
Check harness and sensor.
E02
RETURN SENSOR
NOT CONNECTED
52
Return sensor not connected.
Check harness and sensor.
E04
DHW SENSOR
NOT CONNECTED
55
DHW sensor not connected.
If DHW Mode is not intended to be set to Mode 1,
DHW Store with Sensor, then change it to the
appropriate Mode.
Check harness and sensor.
E05
STACK SENSOR OPEN
57
Flue gas sensor open.
Check vent temperature, harness, sensor.
E11
SUPPLY SENSOR SHORT
59
Supply sensor shorted.
Check harness and sensor.
E12
RETURN SENSOR SHORT
60
Return sensor shorted.
Check harness and sensor.
E13
STACK SENSOR SHORT
65
Flue gas sensor shorted.
Check harness and sensor.
E14
DHW SENSOR SHORT
63
DHW sensor shorted.
Check harness and sensor.
E19
COMMUNICATION ERROR
E2PROM ERROR
0
Problems reading from or writing
to e2prom.
Contact PB Heat Representative.
E20
FALSE FLAME DETECTED
35
False Flame detected.
Verify no flame in observation port. Check Sensor.
E21
HOT/NEUTRAL REVERSED
44
Phase and neutral of mains
supply are reversed.
Verify polarity of incoming wiring. Check boiler
ground and harness.
E22
POOR GROUND
43
No earth connected or internal
hardware error.
Check boiler ground and harness.
E23
NET FREQUENCY ERROR
45
Mains frequency differs more
than 2% from 60Hz.
Contact electrical provider and/or an electrician.
E24
POOR GROUND
46
Earth connection is not ok.
Check boiler ground and harness.
E25
BLOCKED VENT
38
Blocked Vent Switch is Open
This error applies to PF-200, PF-210, PF-300 and
PF-399 models. Check for blocked vent pipe or blocked
heat exchanger. Check switch and tubing to switch.
E26
BLOCKED CONDENSATE
DRAIN
41
Condensate drain blocked.
Check condensate tanks, hoses, condensate switch,
and harness.
E30
HIGH STACK TEMPERATURE
39
Flue gas sensor above max flue
se diff.
If flue pipe is hot, check flue temperature and
compare to values shown Table 8.5. Check for
proper gas input and combustion readings, check
for dirty heat exchanger.
If flue pipe is not hot, check flue sensor and
harness.
E31
LOW WATER
36
Water level is too low.
Check boiler water level, low water cut-off, harness.
If a LWCO is not used, a jumper should be placed
between terminals #9 and #10, LWCO Contact.
E32
HIGH RETURN TEMP
40
Return temperature is above
194°F (90°C).
Check for reversed supply and return piping or
pump installed backwards.
E42
INTERNAL HDWRE ERROR
47
Internal hardware error.
See Note*
E45
INTERNAL HDWRE ERROR
31
Internal hardware error.
See Note*
E46
INTERNAL HDWRE ERROR
32
Internal hardware error.
See Note*
E47
INTERNAL HDWRE ERROR
33
Internal hardware error.
See Note*
E48
INTERNAL HDWRE ERROR
34
Internal hardware error.
See Note*
E51
RESET BUTTON ERROR
PLEASE WAIT.
66
Reset button pressed more than
7 times within one minute.
Wait five minutes. If error does not clear, replace
control.
* If persistent blocking errors, E42 through E48, occur, systematically disconnect all wires that were not supplied by the factory with the exception
of the power supply (CH T’stat, DHW T’stat, LWCO and Pumps). If the error code goes away, determine if there may be feedback from one of
the circuits. If the Error occurs with all of these disconnected, there is likely a problem with the control board.
Содержание PureFire PF-110
Страница 26: ...24 WATER PIPING AND CONTROLS Figure 4 7 Two Boilers Primary Secondary with Four Zones Zone Circulator ...
Страница 27: ...25 Figure 4 8 Three Boilers Primary Secondary with Five Zones Zone Circulator WATER PIPING AND CONTROLS ...
Страница 28: ...26 WATER PIPING AND CONTROLS Figure 4 9 Three Boilers Primary Secondary with Four Zones Zone Valves ...
Страница 37: ...35 ELECTRICAL CONNECTIONS Figure 7 5 Internal Wiring Schematic for PF 50 PF 80 PF 110 PF 140 boilers ...
Страница 38: ...36 Figure 7 6 Internal Wiring Schematic for PF 200 PF 210 PF 300 PF 399 boilers ELECTRICAL CONNECTIONS ...
Страница 75: ...73 REPAIR PARTS Figure 13 2 Heat Exchanger Burner Assembly Repair Parts PF 50 PF 80 PF 110 PF 140 ...
Страница 77: ...75 REPAIR PARTS Figure 13 3 General Repair Parts PF 200 PF 210 PF 300 PF 399 ...
Страница 79: ...77 Figure 13 4 Heat Exchanger Burner Assembly Repair Parts PF 200 PF 210 PF 300 PF 399 REPAIR PARTS ...
Страница 82: ...80 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS ...
Страница 83: ...81 APPENDIX A STATUS SCREENS ...
Страница 84: ...82 APPENDIX A STATUS SCREENS ...
Страница 85: ...83 APPENDIX A STATUS SCREENS ...
Страница 86: ...84 APPENDIX B USER MENU APPENDIX B USER MENU ...
Страница 87: ...85 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU ...
Страница 88: ...86 APPENDIX C INSTALLER MENU ...
Страница 89: ...87 APPENDIX C INSTALLER MENU ...
Страница 90: ...88 APPENDIX C INSTALLER MENU ...
Страница 91: ...89 APPENDIX C INSTALLER MENU ...