E. MAIN GAS VALVE - OPERATION
1. Figure 5.2 is an illustration of the gas valve/venturi
assembly for the
P
URE
F
IRE
®
boiler.
a. Adjustments should not be made to the gas valve
without instrumentation to measure carbon
dioxide (CO
2
) and carbon monoxide (CO)
emissions in the vent pipe.
b. Turning the throttle screw clockwise will decrease
the gas flow (decreasing CO
2
) and turning it
counterclockwise will increase the gas flow rate
(increasing CO
2
). Markings adjacent to the throttle
screw show + and – indicating this operation.
c. The recommended CO
2
settings are given in Table
5.4. In no case should the boiler be allowed to
operate with CO emissions above 150 ppm.
2. Refer to Section 3, Venting and Air Intake for
information on obtaining vent samples from this
boiler.
30
FUEL PIPING
Figure 5.2: Gas Valve/Venturi
Natural Gas
Propane (LP)
Low Fire
High Fire
Low Fire
High Fire
Carbon
Monoxide
(CO)
< 75 ppm
< 150 ppm
< 75 ppm
< 150 ppm
Carbon
Dioxide
(CO
2
)
8.8% to
11.5%
8.5% to
9.7%
9.8% to
12.5%
9.5% to
10.5%
Excess
Oxygen
(O
2
)
0.7% to
5.4%
3.9% to
6.0%
1.9% to
6.0%
4.9% to
6.5%
Excess Air
3.2% to
31.2%
20.1% to
35.4%
8.9% to
35.9%
27.6% to
39.8%
Table 5.4: Recommended CO
2
Settings
1 Combustion measurements should be taken during steady state operation.
Values during significant transitions may exceed the numbers shown.
2 Conversions to excess oxygen and excess air are based on natural gas
consisting of 100% methane (CH
4
) or 100% propane (C
3
H
8
)
Instructions (PF8032) for converting from natural gas
to LP gas and from LP gas to natural gas are
included in the boiler folder.
NOTICE
Содержание PureFire PF-110
Страница 26: ...24 WATER PIPING AND CONTROLS Figure 4 7 Two Boilers Primary Secondary with Four Zones Zone Circulator ...
Страница 27: ...25 Figure 4 8 Three Boilers Primary Secondary with Five Zones Zone Circulator WATER PIPING AND CONTROLS ...
Страница 28: ...26 WATER PIPING AND CONTROLS Figure 4 9 Three Boilers Primary Secondary with Four Zones Zone Valves ...
Страница 37: ...35 ELECTRICAL CONNECTIONS Figure 7 5 Internal Wiring Schematic for PF 50 PF 80 PF 110 PF 140 boilers ...
Страница 38: ...36 Figure 7 6 Internal Wiring Schematic for PF 200 PF 210 PF 300 PF 399 boilers ELECTRICAL CONNECTIONS ...
Страница 75: ...73 REPAIR PARTS Figure 13 2 Heat Exchanger Burner Assembly Repair Parts PF 50 PF 80 PF 110 PF 140 ...
Страница 77: ...75 REPAIR PARTS Figure 13 3 General Repair Parts PF 200 PF 210 PF 300 PF 399 ...
Страница 79: ...77 Figure 13 4 Heat Exchanger Burner Assembly Repair Parts PF 200 PF 210 PF 300 PF 399 REPAIR PARTS ...
Страница 82: ...80 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS ...
Страница 83: ...81 APPENDIX A STATUS SCREENS ...
Страница 84: ...82 APPENDIX A STATUS SCREENS ...
Страница 85: ...83 APPENDIX A STATUS SCREENS ...
Страница 86: ...84 APPENDIX B USER MENU APPENDIX B USER MENU ...
Страница 87: ...85 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU ...
Страница 88: ...86 APPENDIX C INSTALLER MENU ...
Страница 89: ...87 APPENDIX C INSTALLER MENU ...
Страница 90: ...88 APPENDIX C INSTALLER MENU ...
Страница 91: ...89 APPENDIX C INSTALLER MENU ...