Technical data
Heat recovery device
thermos 200 DC / 300 DC
© Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland
Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de
Equipment design:
MVHR components:
Components
suitable for
Passive
House
Dr. Wolfgang Feist
certificate applies to thermos 200 DC
Heat exchanger box:
Material: HX plastic
Ventilation fans:
EC radial fans with integrated electronics
Filters:
Filter class: G4 (supply/extract air)
Option: pollen filter F8 (supply air)
Housing:
EPP (foam)
Summer mode (bypass):
motorised summer bypass valve, bypass shut-off insert with safety function in winter
operation
Duct connections:
160 mm dia. (socket size)
Elektrical connection:
single-phase 230V, 50Hz
three-phase 3 x 230V, 50 Hz, with frost protection and back-up duct heater options
Central control unit:
LxWxD (mm): 340x300x80, or 340x300x140 with frost protection and back-up duct
heater options
Enclosure:
IP 44 (MVHR unit)
IP 20 (control unit)
Protection Class:
I (acc. to EN 60335)
Weight:
35 kg
Notes:
•
Install the MVHR unit upright in a frost-free place, preferably > 10°C.
•
Never lay control cables for programmers and sensors in parallel to 230/400 VAC
cables (minimum distance of 20 cm) and never lay out cables in loop.
•
Install the control unit in a way to ensure there is no heat build-up and sufficient space
for service access.
•
Simultaneous fireplace operation is possible via an
extra module for negative
pressure monitoring
with a shut-down function for the ventilation unit and/or the
exhauster hood connected to the exhaust air duct.
Note:
The unit should be installed in a raised
position for best condensate discharge.
(100…200 mm depending on drain hose
length) – this increases the height of the
MVHR unit.
Содержание thermos 300 DC
Страница 2: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 52: ......
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......