2.4
Menu System setup – Duct heater
------------------------
|Duct heater 9.5.0 |
| <-| TA1
|Duct t.max: -> x5°C |
|Hys. DCTH: H5 |
|Hys. Room: H0 | TA2
| |
| -> - + |
------------------------
TA5 TA4 TA3
Press TA5 to select a value, and TA3 and TA4 to adjust it.
x5
absolute maximum for duct temperature, causing the duct heater (DCTH) to stop.
!!! Limited duct temperature !!! SAFETY REQUIREMENT !!!
When the duct heater is enabled, the summer/winter bypass is automatically closed.
Hysteresis Room (H0) defines the ON and OFF switching points related to T0 (room sensor in the
programmer).
DCTH ON:
Room temperature below setpoint, and
Maximum duct temperature not reached
DCTH Off:
Room temperature exceeds setpoint, or
Maximum
duct
temperature
reached
Example:
x0= 21.0°C
Duct heater ON:
T5 < 20.5°C
H0= 0.5 K
Duct heater OFF:
T5 > 21.5°C
X5= 50.0°C
Duct heater ON:
T5 < 49.0°C
H5= 1.0 K
Duct heater OFF:
T5 > 51.0°C
Side conditions DCTH ON:
Thermal cut-out ok (only for electric duct heater with ohmic heating element)
Flow sensor Fz4 ok (only for electric duct heater with ohmic heating element)
Power input Fz4 ok (only for electric duct heater with ohmic heating element)
T0 / T5 plausible
Heating enabled
Ventilation other than 0
Side conditions DCTH OFF:
Thermal cut-out fault (only for electric duct heater with ohmic heating element)
Flow sensor Fz4 fault (only for electric duct heater with ohmic heating element)
Power input Fz4 fault (only for electric duct heater with ohmic heating element)
T0 / T5 not plausible
Air heating disabled
2.5
Menu System setup – Ventilation steps
-----------------------
|Fan 9.7.0 |
|->+constant flow<- | TA1
| +SUP +EXT |
| 030 030 min |
| 050 050 normal |
| 085 085 max ST->| TA2
| 100: 100 correction|
Содержание thermos 300 DC
Страница 2: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 52: ......
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......