Automatic Control
thermos 200 / 300 DC
© Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland
Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de
6
4. Switch module 2.1 kW
The switch module is a universal module used to switch on an electric 230 VAC load with a maximum wattage of
2.1 kW.
The switch module is operated by the HCE via the 34-pos. bus connector.
The power pack supplies the module with 230 VAC via its voltage distribution terminals. When connecting the switch
modules to the voltage distribution of the power pack, take care to ensure the individual phases are loaded
symmetrically.
Use a 3-core cable for direct load connection to connector 2 of the power module (inverted 3-pole plug).
To select the function for the module, it is necessary to place two jumpers for the start-up – both jumpers must have the
same position in the male connectors.
Functions
1=Frost protection
2=Back-up heater (electric / hot water) or heating circuit
!!! IMPORTANT: Both jumpers must be in the same position on the module. !!!
The hardware detection and module function assignment will be automatic via the bus line.
One module can be assigned to one function only. Maximum eight different modules can be connected to the internal
bus.
Connections to the power module:
X_1
230 VAC - INPUT
power supply, 3 pos., spring clamps
X_2
230 VAC – switch output (2.1kW)
, 3 pos., inverted socket with plug
Phoenix IC 2,5/3-G-5,08 / 1786417
Содержание thermos 300 DC
Страница 2: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 52: ......
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......