background image

Switch S1-8:  Respond to Local and Remote Loop from DTE 

Use Switch S1-8 to determine whether the DTE can initiate a local

or remote loopback test.  When Switch S1-8 is in the On position, the
DTE may activate a local or remote loopback test by raising the
appropriate interface signal (see Appendix C to determine the local and
remote loopback signals).

S1-8

Setting

On

Respond to loop request from DTE Interface

Off

Do not respond to loop request from DTE Interface

3.1.3   DIP Switch Set “S2” - Control Port Address and 19.2 kbps

Sync. 

The Model 1092RC may be configured by a menu-driven software

system when used with the Patton 

Model 1000CC 

(for ordering

information, see Appendix B).   In order to configure the Model 1092RC
by software commands, you must set its control port address.   

The control port address is defined by a two digit decimal number.

Switches S2-1 through S2-4 define the least significant digit or the
“ones” digit, and Switches S2-5 through S2-7 define the “tens” digit.
Valid addresses are 0 through 79.  Use the table below and the
instructions that follow the table to set the the control port to the desired
address.

9

S2 SUMMARY TABLE

Switch S2 Settings

1*

2

3

4

5

6

7

8

Address

Digit

0

ON ON

ON

ON

ON

ON

ON

ON

1

OFF ON

ON

ON

OFF ON

ON

ON

2

ON OFF ON

ON

ON

OFF ON

ON

3

OFF OFF ON

ON

OFF OFF ON

ON

4

ON ON

OFF ON

ON

ON

OFF ON

5

OFF ON

OFF ON

OFF ON

OFF ON

6

ON OFF OFF ON

ON

OFF OFF ON

7

OFF OFF OFF ON

OFF OFF OFF ON

8

ON ON

ON

ON

N/A

N/A

N/A

ON

NOTE:

Default Settings Shown in 

Bold Italics

; Default Address is “10” 

5.0  OPERATION

Once the Model 1092RC is properly configured and installed, it

should operate transparently.  This sections describes functions of the
LED status indicators, and the use of the built-in loopback test modes.  

5.1  LED STATUS INDICATORS

The Model 1092RC features twelve front panel LEDs that monitor

power, the DTE signals, network connection and test modes.  Figure 10
(below) shows the front panel location of each LED.  Following Figure
10 is a description of each LEDs function.

TD & RD

glow red to indicate an idle condition of Binary 
“1” data on the respective terminal interface 
signals.  Green indicates Binary “0” data.

CTS

consists of 2 LEDs, 1 red, 1 green.  CTS glows 
green to indicate that the Clear to Send signal from
the modem is active.  Red indicates inactive CTS.

CD

consists of 2 LEDs, 1 red, 1 green.  CD  glows 
red if no carrier signal is being received from the 
remote modem.  Green indicates that the remote 
modem’s carrier is being received.

DTR

glows green to indicate that the Data Terminal 
Ready signal from the terminal is active.

28

Figure 10.

The Model 1092RC Series' front panel LEDs

Model 1092RC

TD

RD

NS

CTS

ER

LLB

511

RDL

511ER

CD

TM

DTR

Содержание 1092RC

Страница 1: ...2 Wire Synchronous and Asynchronous Rack Mount Modem Card SALES OFFICE 301 975 1000 TECHNICAL SUPPORT 301 975 1007 http www patton com Part 07M1092RC E Doc 033021U Rev F Revised 1 22 08 C E R T I F I...

Страница 2: ...ings 3 3 2 Model 1000RCM13492 Strap Settings 4 0 Installation 24 4 1 The Model 1000R16P Rack Chassis 4 1 1 The Rack Power Supply 4 2 Installing the Model 1092RC Series Into Chassis 4 3 1 Connecting to...

Страница 3: ......

Страница 4: ...r This number may be obtained from Patton Electronics Technical Support tel 301 975 1007 email support patton com www http www patton com NOTE Packages received without an RMA number will not be accep...

Страница 5: ......

Страница 6: ...r board strap and two eight position DIP switches on the front card see Figure 1 below Figure 2 shows the orientation of the DIP switches with respect to the ON and OFF positions 5 ON 1 2 3 4 5 6 7 8...

Страница 7: ......

Страница 8: ...te On On 32 Kbps Reserved Off On 56 Kbps Reserved On Off 64 Kbps Reserved Off Off 19 2 or 128 Kbps 0 38 4 kbps NOTE Model 1092RC operates either at a synchronous rate of 19 2 kbps or 128 kbps dependin...

Страница 9: ......

Страница 10: ...see Appendix B In order to configure the Model 1092RC by software commands you must set its control port address The control port address is defined by a two digit decimal number Switches S2 1 throug...

Страница 11: ......

Страница 12: ...n Appendix D Refer to Appendix C to order a pre made cable 2 Power up the terminal and set its RS 232 port as follows 9600 Baud 8 data bits i stop bit no parity Local echo CR CR LF on inbound data ANS...

Страница 13: ......

Страница 14: ...nfiguration Select Option 4 toedit the software configuration of the Model 1092RC To save changes after editing the software configuration select MAIN MENU Option 5 then select Use Software Switches a...

Страница 15: ......

Страница 16: ...odel 1092RC to either respond or ignore the Remote Digital Loop request from the remote 1092RC 6 DTE Controlled Local Line Loop Select Option 6 in the SOFTWARE CONFIGURATION Menu to instruct the Model...

Страница 17: ......

Страница 18: ...ption 7 Test Modes Select Option 7 from the MAIN MENU to select the test mode status of the Model 1092RC below The Model 1092RC Test Mode settings help to verify the integrity of the data link and iso...

Страница 19: ......

Страница 20: ...ious parameters in the remote Model 1092RC 19 REMOTE UNIT CONFIGURATION MAIN MENU 1 Display Remote Unit Configuration 2 Setup Remote Unit Configuration 3 Display Remote Modem Status 4 Select Hardware...

Страница 21: ......

Страница 22: ...function cards Prior to installation you will need to examine the rear card you have selected and make sure it is properly configured for your application Each rear card is configured by setting strap...

Страница 23: ......

Страница 24: ...RCM13492 Strap Settings Figure 7 shows the strap location for the Model 1000RCM13492 M 34 RJ 45 rear card This strap determines whether Signal Ground and Frame Ground will be connected SGND FRGND JB4...

Страница 25: ......

Страница 26: ...the rack chassis and plug into each other by way of mating 50 pin card edge connectors Use the following steps as a guideline for installing each Model 1092RC Series into the rack chassis 1 Slide the...

Страница 27: ......

Страница 28: ...N SIGNAL TIP 4 4 TIP RING 5 5 RING 4 3 5 Connection to the Control Port Interface Please refer to the Model 1000CC Control Card user manual for cable requirements of the Control Port Interface 27 Noti...

Страница 29: ......

Страница 30: ...ese tests can be activated physically from the front panel or via the interface 5 2 1 Using Local Line Loopback LLB The Local Line Loopback LLB test checks the operation of the local Model 1092RC and...

Страница 31: ......

Страница 32: ...sent move the V 52 toggle switch to the right activating the 511 E test with errors present If the test is working properly the local modem s red ER LED will glow A successful 511 E test will confirm...

Страница 33: ......

Страница 34: ...1000RPSM 48A 48V Front Power Supply Module 1000RPEM V 120 240V CE Compliant Rear Power Entry Module 1000RPEM V 120 240V CE Compliant Rear Power Supply Entry Module 1000CC Control Card IM1RC A Interfac...

Страница 35: ......

Страница 36: ...Signal 1 FG Frame Ground 2 TD Transmit Data 3 RD Receive Data 4 RTS Request to Send 5 CTS Clear to Send 6 DSR Data Transfer Rate 7 SGND Signal Ground 15 TC Test Control A 17 RC Receive Timing 18 LLB L...

Страница 37: ......

Страница 38: ...NMENT RJ45 Connector Pin Number Signal 1 N C No Connection 2 N C No Connection 3 N C No Connection 4 Tip 5 Ring 6 N C No Connection 7 N C No Connection 8 N C No Connection Copyright 1997 Patton Electr...

Страница 39: ......

Страница 40: ......

Отзывы: