Parkwood Maxi Скачать руководство пользователя страница 14

Installation, Operating and Service Manual 

 
 

For safe installation and operation of your pellet Fire, read and follow the safety instructions on pages 5 & 6 and 

throughout the manual.

 

© 20.3.2011 Firemakers Limited                                                                                                                           Page 14   

clearance (75mm from the inner flue) is met by installing a Parkwood supplied Wall / Ceiling Ring. Fit a non 
combustible shield (12mm from the combustible surface) if safe clearances for flue components cannot be achieved.  
9. Finally, extend the Flue to go through the roof and flash the roof penetration. 
10. Do not sit the Cowl on the outer flue; ensure that there is a minimum of 20mm gap to allow natural upward draft. A 
Spacer (Spider) or three (3) screws can be used to centralize the inner flue to the outer flue beneath the Cowl. 
     
 

NOTE

: The 150mm distance between the rear of the Fire and the rear of the Clean Out Tee illustrated on the Diagram 

above is only to indicate the approximate distance that Installers should allow for Flue at the rear of the Fire. 

 

FREE STANDING EXTERNAL VERTICAL INSTALLATION 

 

An external installation is often used when the customer does not want the Flue to be visible or if the Pellet Fire will sit 
too far forward in the room for an internal installation to be practical. 

Free Standing External Vertical Installation Instructions 

Refer to the Diagram and Installers Flue Instructions 
 
1. Choose a Fire location that is suitable. See the section “Positioning the Pellet Fire” on page 12. 
 
2. Place a non-combustible Hearth Pad where / if necessary. 
 
3. Determine the centre point of where the flues is to exit the wall of the dwelling and use a divider set at a radius of 
85mm to scribe a 170mm circle on the wall. Drill a hole through the wall to establish the centre point on the exterior of 
the wall and scribe a 170 mm circle on the exterior of the house, cut the hole in the dwelling wall.  
 
4. Connect a 75mm and 100mm Flue to the fire and pass them through the dwelling wall ensuring that the Wall / 
Ceiling Rings are sealed vermin and waterproof with silicone. Connect a Clean Out Tee in a position so that when the 
Flue is installed vertically, it will be 25mm away from a combustible wall. 
 
5. Use a Plumb Bob to establish the center of the flue on the soffit and use a divider set at a radius of 85mm to scribe a 
170mm circle on the soffit and cut the hole in the soffit.  
 
6. Use a Plumb Bob to establish the center of the flue on the roof, cut the hole in the roof.    
 
7. Install the Flue upward from there. When you reach the soffit, make sure that the Inner & Outer Flue goes through a 
Wall / Ceiling Ring to provide adequate safe clearance.   
 
8. When using double skin flue components a 25mm clearance is required from all combustibles. Single skin flue 
components must have a 75mm safe clearance from combustibles. For wall and ceiling penetrations; additional safe 
clearance (75mm from the inner flue) is met by installing a Parkwood supplied Wall / Ceiling Ring. Fit a non 
combustible shield if safe clearances for flue components cannot be achieved.  
 
9. Finally, extend the Flue to go through the roof and flash the roof penetration. 
 
10. Do not sit the Cowl on the outer flue; ensure that there is a minimum of 20mm gap to allow natural upward draft. A 
Spacer (Spider) or three (3) screws can be used to centralize the inner flue to the outer flue beneath the Cowl. 
  

Содержание Maxi

Страница 1: ...NOT INSTALL OR OPERATE THIS FIRE UNTIL THE INSTALLER AND OPERATORS HAVE ENTIRELY READ THIS MANUAL FAILURE TO FOLLOW THESE INSTRUCTIONS COULD VOID THE WARRANTY OR RESULT IN DAMAGE TO THE FIRE Private B...

Страница 2: ...FIGURATIONS 13 FREE STANDING INTERNAL VERTICAL INSTALLATION 13 Free Standing Internal Vertical Installation Diagram 13 Free Standing Internal Vertical Installation Instructions 13 FREE STANDING EXTERN...

Страница 3: ...ate of Compliance issued by the Installer Council in a safe place for future reference or any future warranty claims Parkwood reserves the rights to any carbon credits associated with this product Pel...

Страница 4: ...on NOTE The ash content of the fuel and operation of your Fire will directly determine the frequency of cleaning The use of high ash content fuels may result in the fire needing to be frequently clean...

Страница 5: ...ous and will void the warranty of the Fire 6 This Fire must be connected to an earthed standard 240 volt 50 Hz electrical outlet Parkwood Pellet Fires recommends that a power surge protector be fitted...

Страница 6: ...Never attempt to operate this Fire without the Burn Pot Liner in place 27 CARBON AND FLY ASH The products of combustion will contain small particles of fly ash The fly ash will collect in the Firebox...

Страница 7: ...hot exhaust gases are drawn through Heat Exchangers which extract heat from the gases as they are discharged to the exhaust flue 3 The room air Convection Blower circulates room air through the Heat E...

Страница 8: ...rious quality wood pellet fuel differs this will considerably affect the performance and heat output of Fire Parkwood Pellet Fires recommend that you burn only premium quality wood pellet fuel Poor qu...

Страница 9: ...ce Technicians to disconnect the Fire from the power before servicing Also the warning labels inform the Operator and Service Technicians that the Fire should not be operated with the panels removed P...

Страница 10: ...the firebox door 4 Run a thin bead of high temp silicone on the inside of the Door Cover about 20mm from the inside corner edge 5 Orientate the Door facedown above the Plated Door Cover so that the Do...

Страница 11: ...ill not operate properly in a non compliant improperly earthed electrical outlet Contact a local electrician to ensure proper electrical power is provided to the Fire To avoid any shock hazard the Fir...

Страница 12: ...lue the Fire internally check for structural beams and trusses where the proposed flue passes through the ceiling externally behind the Fire or flue an existing masonry chimney with a 75mm stainless s...

Страница 13: ...table See the section Positioning the Pellet Fire on page 12 2 Place a non combustible Hearth Pad where if necessary 3 Install the Clean Out Tee and Elbow place the Wall Ceiling Ring over the Elbow Pl...

Страница 14: ...it the wall of the dwelling and use a divider set at a radius of 85mm to scribe a 170mm circle on the wall Drill a hole through the wall to establish the centre point on the exterior of the wall and s...

Страница 15: ...COMBUSTIBLE FLOOR PROTECTION EXISTING FLOOR 600mm Free Standing Safe Clearances 200mm 75mm 75mm FLOOR PROTEC TOR 150mm Note The 75mm clearance at the rear of this fire is recommended for ease of main...

Страница 16: ...anels of the Fire remain accessible This provides for ease of service and maintenance to the Fire Fire Place Insert Installation Instructions Refer to the Diagram and Installers Flue Instructions 1 En...

Страница 17: ...Requires 290mm to allow hopper lid to fully open C Top Rear of Unit 0mm D Side Rear of Unit 25mm E Rear of Unit 200mm F Floor Protector 150mm G Depth 450mm H Height 605mm Notes 1 Other dimensions illu...

Страница 18: ...her wood burning appliances in that they do not rely on natural draft produced by a chimney Instead the flows of combustion air and exhaust gasses are forced with a fan A Pellet Fire Flue operates und...

Страница 19: ...To centre the Inner flue from the Outer Flue a spacer Spider may be used or tabs may be cut on the small end of the Outer Flue and folded into the Inner Flue to centralise the Inner Flue Where practic...

Страница 20: ...e Exhaust Fan The On Off switch on the Control Panel controls the Igniter The Igniter turns off when the Exhaust Temperature Sensor detects a significant sustained temperature rise or after 20 minutes...

Страница 21: ...his is achieved by increasing or decreasing the electric pulses sent to the Auger Motor These switches also control the 4 speed Convection Blower These switches are also used to set the clock and time...

Страница 22: ...20 minutes later the Exhaust Fan and the Convection blowers are turned off During STOPPING MODE as the Fire cools down the Convection Blower will move down through the Heat Settings until it the Fire...

Страница 23: ...dinarily cleaning the Burn Pot Liner once a day is adequate however if very poor quality fuel is used this procedure may need to be carried out up to every two hours or so Ordering a second Burn Pot L...

Страница 24: ...ation of the fire requires is to inspect the Burn Pot Liner for Build up of pellets or clinkering The frequency of these inspections is dependant on fuel quality refer to Pellet Fuel Quality on page 3...

Страница 25: ...a manual Air Damper Rod that adjusts the combustion air to the Fire Sufficient combustion air is required to enable efficient combustion of the fuel and maintain maximum heat output of the Fire Exces...

Страница 26: ...ill prevent optimum combustion and cause carbon to form in the Firebox on the Glass and cause automatic ignition failures Always keep the hopper at least full TOO MUCH AIR If the Pellet Fire has too m...

Страница 27: ...g may be changed during a period of one minute immediately after the ON TIME has been set SETTING THE TIME 1 The clock uses 24 hour notation The time will be displayed at all times unless there is no...

Страница 28: ...cold Carefully check that the Fire and all ashes are cooled completely before commencing any cleaning DO NOT Vacuum the Fire if any hot partially burnt pellet fuel or embers are present DO NOT put an...

Страница 29: ...re is insufficient combustion air or if the Burn Pot Liner requires cleaning Warning Do not use chemicals or abrasive cleaning compounds on the glass or any other part of the Fire 6 Empty the Ash Pan...

Страница 30: ...from the track Apply a generous bead of or hi temperature silicone into the track Position NEW 14mm round fiberglass rope seal into the track and gently press into the door Trim off any excess fiberg...

Страница 31: ...Pot Liner Adjust the Air Damper Rod and heat switches accordingly until you have the desired flame and heat output The holes in the Burn Pot Liner must be kept clean Parkwood Pellet Fires recommends...

Страница 32: ...ll because vacuum can be lost through the Pellet Hopper 3 Ensure the Ash Pan Burn Pot Ash Slide and Firebox Door are firmly closed 4 Carry out Daily Weekly and Annual Maintenance to remove excessive a...

Страница 33: ...LER When the display is powered up PARKWOOD then the firmware revision number displays ie 1 12 If the display fails on initial starting ensure that the fire was plugged in to the mains supply at least...

Страница 34: ...foreign objects obstructing the Auger Clear the obstruction by removing the bolts retaining the Auger cover inside the Hopper with an 8mm socket Ensure the top of the Auger Cover is resealed with bla...

Страница 35: ...uncil in a safe place as you may be required to produce this for any future warranty claims 1 Parkwood warrants the Fire to the original retail purchaser only 2 Parkwood makes the following warranties...

Страница 36: ...ate Bag 9038 Wanaka New Zealand 9034 of any defect by providing the following information i Serial Number of the Model Pellet Fire ii The original purchasers name and date of purchase iii The date of...

Страница 37: ...f your pellet Fire read and follow the safety instructions on pages 5 6 and throughout the manual 20 3 2011 Firemakers Limited Page 37 Parkwood Pellet Fires Firemakers Limited Private Bag 9038 Wanaka...

Страница 38: ...PPER LID ASSEMB LY YF2_P01 17 SIDE PANEL LHS YF2_P01 18 SIDE PANEL RHS YF3 FPI_A19 HOPPER LID ASSEMB LY YF3 FS_P01 17 SIDE PANEL LHS YF3 FPI_P01 17 SIDE PANEL LHS YF3 FS_P01 18 SIDE PANEL RHS YF3 FPI_...

Страница 39: ...ation Operating and Service Manual For safe installation and operation of your pellet Fire read and follow the safety instructions on pages 5 6 and throughout the manual 20 3 2011 Firemakers Limited P...

Страница 40: ...ation Operating and Service Manual For safe installation and operation of your pellet Fire read and follow the safety instructions on pages 5 6 and throughout the manual 20 3 2011 Firemakers Limited P...

Отзывы: