6.6
REMOTE SINGLE EVAPORATOR WITH EEV – CONFIGURATION F
The S3C case controller is capable of controlling and monitoring single temperature, single evaporator refrigerated fixtures
installed as a line-up. The case shown in the diagram below is the lead case of the line-up. In this scenario, one S3C case
controller is required. The S3C case controller will control all case functions as well as take all the desired sensor inputs and
drive the EEV. The typical control method:
Without mechanical EPR: EEV will control case temperature with a minimum superheat setpoint.
With mechanical EPR: EEV will control superheat and the EPR will control case temperature.
The optional liquid line solenoid (LLS) may be installed as one-per-case or one-per-line-up if no EPR is used or if an EPR
per line-up is used. Case numbers 2, 3, 4,…n will require their own S3C case controller as well.
To configure the S3C control package for configuration F shown
above, follow these directions:
If the controller has not been factory set, then upon initial start-
up, the controller will be in set-up mode and the screen will
display
(for self-contained case).
1. Press the
SET
button, then use
▲▼
buttons to scroll to
o
; press
SET.
This will configure the controller to support
a remote case.
2. Press the
SET
button when
(Rack Identifier)
is displayed. Use the
▲▼
buttons to configure the 4
character Rack Identifier.
Note: Push
▲
button for
numeric,
▼
for alpha characters.
When satisfied
with each digit, press the
SET
button to go to the next
digit. Pressing
SET
multiple times will move to the next
parameter.
3. Press the
SET
button when
ud
(Line-up Identifier)
is displayed. Use the
▲▼
buttons to configure the 4
character Line-up Identifier.
Note: Push
▲
button for
numeric,
▼
for alpha characters.
When satisfied
with each digit, press the
SET
button to go to the next
digit. Pressing
SET
multiple times will move to the next
parameter.
4. Press the
SET
button when
d
(Case Identifier)
is displayed. Use the
▲▼
buttons to configure the 4
character Case Identifier.
Note: Push
▲
button for
numeric,
▼
for alpha characters.
When satisfied
with each digit, press the
SET
button to go to the next
digit. Pressing
SET
multiple times will move to the next
parameter.
5. Press the
SET
button when
(Application Type) is
displayed. Use the
▲
button and scroll to
(Single
Temperature Case); press
SET.
6. Press the
SET
button when
(Local Stepper Valve
Configuration) is displayed. Use the
▲
button to scroll to
(Electronic Expansion Valve); press
SET.
This is the
valve that is attached to the main S3C Case Controller.
7. Press the
SET
button when
(Expansion Valve Type)
is displayed. Use
▲▼
buttons to choose the Expansion
Valve Type based on the below chart; press
SET.
EEV 1
Compressor Suction
CASE
From CASE #n
Liquid
Liquid Line
Solenoid
FIGURE 3 - REMOTE SINGLE EVAPORATOR WITH EEV – CONFIGURATION F
Display
Meaning
u
Pulse Width Modulation Valve
5
500 Step Valve
1596
1596 Step Valve
25
2500 Step Valve
3193
3193 Step Valve
6386
6386 Step Valve
u
Custom Stepper Valve (See Section 11)