![Parker Sporlan S3C Скачать руководство пользователя страница 125](http://html2.mh-extra.com/html/parker/sporlan-s3c/sporlan-s3c_installation-and-operation-instructions-manual_3744235125.webp)
Bulletin 100-50-9.1 –
Page 125
For Coil 1:
1. From the default display, press the
▲
button to
then press
SET.
2. Press the
▲
button and scroll to
d1
.
3. Press
SET
button to show current discharge air value.
4. Press
ESC
button three times to return to
default
display.
For Coil 2:
1. From the default display, press the
▲
button to
2
then press
SET.
2. Press the
▲
button and scroll to
d
.
3. Press
SET
button to show current discharge air value.
4. Press
ESC
button three times to return to
default
display.
For Coil 3:
1. From the
default
display, press the
▲
button to
3
then press
SET.
2. Press the
▲
button and scroll to
d
.
3. Press the
SET
button to show current superheat value.
4. Press the
ESC
button three times to return to
default
display.
19.4 VIEW SUPERHEAT
19.4.1 SINGLE COIL CASE
1. From the
default
display, press the
▲
button to
then press
SET.
2. Press the
▲
button and scroll to
h
.
3. Press
SET
button to show current superheat value.
4. Press
ESC
button three times to return to
default
display (discharge air).
19.4.2 MULTI-COIL CASE
For Coil 1:
1. From the
default
display, press the
▲
button to
then press
SET.
2. Press the
▲
button and scroll to
h1
.
3. Press
SET
button to show current superheat value.
4. Press
ESC
button three times to return to
default
display (discharge air).
For Coil 2:
1. From the
default
display, press the
▲
button to
2
then press
SET.
2. Press the
▲
button and scroll to
h
.
3. Press
SET
button to show current superheat value.
4. Press
ESC
button three times to return to
default
display (discharge air).
For Coil 3:
1. From the
default
display, press the
▲
button to
3
then press
SET.
2. Press the
▲
button and scroll to
h
.
3. Press
SET
button to show current superheat value.
4. Press
ESC
button three times to return to
default
display (discharge air).
19.5 VIEW SUCTION PRESSURE
1. From the
default
display, press the
▲
button to
then press
SET.
2. Press the
▲
button and scroll to
U
.
3. Press
SET
button to show suction pressure value.
4. Press
ESC
button three times to return to
default
display (discharge air).
19.6 VIEW COIL OUTLET TEMPERATURE
19.6.1 SINGLE COIL CASE
1. From the
default
display, press the
▲
button to
e
then press
SET.
2. Press the
▲
button and scroll to
oU
.
3. Press
SET
button to show evaporator coil outlet
temperature.
4. Press
ESC
button three times to return to
default
display.
19.6.2 MULTI-COIL CASE
For Coil 1:
1. From the
default
display, press the
▲
button to
then press
SET.
2. Press the
▲
button and scroll to
o1
.
3. Press
SET
button to show evaporator coil outlet
temperature.
4. Press
ESC
button three times to return to
default
display.
For Coil 2:
1. From the
default
display, press the
▲
button to
2
then press
SET.
2. Press the
▲
button and scroll to
oU
.
3. Press
SET
button to show evaporator coil outlet
temperature.
4. Press
ESC
button three times to return to
default
display.
For Coil 3:
1. From the
default
display, press the
▲
button to
3
then press
SET.
2. Press the
▲
button and scroll to
oU
.
3. Press
SET
button to show evaporator coil outlet
temperature.
4. Press
ESC
button three times to return to
default
display.
19.7 VIEW EEV POSITION
19.7.1 SINGLE COIL CASE
1. From the
default
display, press the
▲
button to
then press
SET.
2. Press the
▲
button and scroll to
.