Bulletin 100-50-9.1 –
Page 133
4. Remove valve module either by pressing down and
releasing the DIN rail latch or removing the four
mounting screws.
5. Install new module by snapping on to DIN rail or using
mounting screws.
6. Install terminal plugs (with wires).
7. Ensure the position of the four switches are the same as
the old module.
8. Retighten all wiring on the terminal plugs.
9. Apply power to the S3C Valve Module.
Note:
Ud
followed by dashes may appear on the display
while the module is updating.
19.20.3 DISPLAY MODULE
1. Remove the power and communications terminal plug
from the back of the display.
2. Press the slide locks and remove from the sides of the
display.
3. Slip out display from the panel/bulkhead.
4. Slide new display into bulkhead.
5. Install slide locks onto the display and compress against
bulkhead to ensure proper sealing.
6. Connect power and communications terminal plug.
Note:
Ud
followed by dashes may appear on
the display while the Display Module (DM) is
updating.
19.21 VIEWING CASE CONTROL FIRMWARE
REVISION
To view the controller firmware revision:
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the
administrator
password and press
SET.
3. The display will show
(will skip to Process Values if
system is self-contained).
4. Press the
SET
button and
(Process Values) will be
displayed.
5. Press the
SET
button and
will be displayed.
6. Press the
▼
button until
(Version) is showing.
7. Press the
SET
button to display the Case Control
firmware revision.
8. Press the
ESC
button four times to exit the menu and
return to the
default
display.
19.22 FIRMWARE UPDATES
To update firmware, contact Sporlan Technical Support.
E-mail: [email protected]
Phone: 636-392-3906