The set-up is simplified by presenting the user with only the parameter selections required based on previous parameter
value selections. Parameters that can be hidden in the table above are shaded and assigned a number in
parenthesis. The explanations below correspond to those numbers.
TABLE 13 - ANTI-SWEAT CONFIGURATION MENU ITEMS
Display
Meaning
Range
Selection
Hide Condition
Anti-sweat control type
Set the type of control used for anti-sweat control
d
= fixed
duty cycle
control
d
= dew
point control
Anti-sweat pulse period
Sets the pulse period (total time of pulse cycle, includes on/off)
1 to 120
seconds
(1)
fd
Anti-sweat fixed duty cycle
Sets the amount of time the heaters are on for the period
0 to 100%
(1)
o
Anti-sweat control offset
Sets when the heaters turn off (degrees above dew point)
0 to 100°F
(2)
TABLE 14 - HIDE CONDITIONS FOR ANTI-SWEAT CONFIGURATION MENU ITEMS
Number
Hide Condition
1
Skipped if anti-sweat control type is dew point control
2
Skipped if anti-sweat control type is fixed duty cycle