Bulletin 100-50-9.1 –
Page 1
S3C Case Control
Installation and Operation Instructions
March 2020 / Bulletin 100-50-9.1
VALVE MODULE
DISPLAY MODULE
S3C CASE CONTROL
Страница 1: ...Bulletin 100 50 9 1 Page 1 S3C Case Control Installation and Operation Instructions March 2020 Bulletin 100 50 9 1 VALVE MODULE DISPLAY MODULE S3C CASE CONTROL...
Страница 2: ...roperty damage This document and other information from Parker Hannifin Corporation its subsidiaries and authorized distributors provide product or system options for further investigation by users ha...
Страница 3: ...4 Remote Multiple Evaporator with 2 EEVs and Circuit EEPR Configuration N 63 Wiring Diagram Configuration N 65 6 15 Remote Multiple Evaporator with 3 EEVs and Circuit EEPR Configuration O 66 Wiring Di...
Страница 4: ...16 Hide Conditions For Defrost Configuration Menu Items 110 12 2 Defrost Schedule 111 12 3 Defrost CT Sensor 111 13 Lighting Configuration 112 13 1 Lights Constant On 112 13 2 One Day Lighting Schedu...
Страница 5: ...et 130 19 18 Fan Current Base Line Reset 130 19 19 Fuse Replacement 130 19 20 Controller Replacement 132 19 21 Viewing Case Control Firmware Revision 133 19 22 Firmware Updates 133 20 Troubleshooting...
Страница 6: ...frigerated case line up remote display fixtures on a parallel compressor refrigeration rack circuit loop Coordination of defrost lighting control temperature con trol and controller configuration is m...
Страница 7: ...r Defrost Termination and One Auxiliary 10 One Pressure Transducer input with 5V excitation voltage 11 One Clogged Drain Sensor input 12 One Occupancy Sensor input 13 One Ambient Temperature Humidity...
Страница 8: ...n lit and flashing there is a device id or IP address conflict on the network TABLE 3 QUICK VIEW COLOR DESIGNATIONS Color Description BLINK TEV Assist Case temperature out of range alarm threshold BLI...
Страница 9: ...liquid line solenoid valve if used are either open or closed during refrigeration mode The Quick View indicators are illuminated BLUE for low temperature operation or GREEN for medium temperature ope...
Страница 10: ...inimum Digital Inputs 4 Dry contact or Open Collector connection only Negative reference to be supplied by the Case Control only Note Occupancy Sensor 5V excitation voltage 75mA maximum Analog Inputs...
Страница 11: ...ength between power supply and Valve Module is 400 ft 22AWG minimum Analog Inputs 7 Temperature Inputs 6 10K Thermistor Software selectable 2K 3K Pressure Transducer 1 5 4 5 VDC Ratiometric output Pre...
Страница 12: ...onal feature 4 5 LIQUID LINE SOLENOID VALVE CONTROL The case refrigeration system includes a solenoid valve placed in the liquid refrigerant supply line A normally closed solenoid is typically used to...
Страница 13: ...ller to add additional hard ware support for 1 Pulse valve and 2 stepper valves 2 EEVs or 1 EEV and 1 EEPR pressure transducer and six temper ature sensors The temperature sensors measure coil out let...
Страница 14: ...s system diagnostics in two areas 1 Detect and report problems with sensor inputs and stepper motor valves 2 Detect and report problems with case components such as fans and defrost heaters 4 17 FAIL...
Страница 15: ...e the power and communication wiring from the Display Module to the Case Controller Use 22 2 shielded twisted pair Belden 8723 or equivalent Attach one end of the shield to earth ground Wire designati...
Страница 16: ...2 shielded twisted pair Belden 8723 or equivalent Attach one end of the shield to earth ground Wire designations are located on the top of the Valve Module Maximum torque on the screw terminals is 3 5...
Страница 17: ...lue coil outlet sensor leads to the controller Take caution to route the leads away from sharp edges fans and defrost heaters Ensure the terminal screws on the controller are backed all the way out In...
Страница 18: ...eads away from sharp edges fans and defrost heaters Ensure the terminal screws on the controller are backed all the way out Insert the leads of the sensor wire into Dsch Air location on the controller...
Страница 19: ...y from sharp edges Ensure the terminal screws on the controller are backed all the way out Insert the leads of the sensor wire into Humidity location on the controller see chart below for sequence Tig...
Страница 20: ...es Follow case OEM instructions for exact mounting location Note Use caution when fastening to the door frame to ensure internal case wiring is not damaged 5 4 7 2 WIRING With controller unpowered car...
Страница 21: ...figured on which sensor is used See Section Defrost Configuration Section for configuration of this input 5 5 DUAL TEMPERATURE SWITCH 5 5 1 MOUNTING A dry contact switch may be used to initiate dual t...
Страница 22: ...wires from the power supply to the controller Take caution to route the cable away from sharp edges Ensure the terminal screws on the controller are backed all the way out Insert the leads of the sens...
Страница 23: ...EEV location sizing along with distributor nozzle sizing is important to proper system performance 5 9 1 2 WIRING The EEV may be wired to the S3C Case Control or the S3C Valve Module depending on fin...
Страница 24: ...ms should beusedasreferencetodeterminevalveandsensorlocations Thewiringdiagramsshouldbeusedasreferencetodetermine controller valve and sensor requirements along with correct wiring locations on the co...
Страница 25: ...of refrigerants can be seen in Table on page 99 15 Press the SET button when Discharge Air Temperature Setpoint is shown Use the buttons to choose the setpoint in F press SET 16 Press the SET button...
Страница 26: ...ND 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS CONTROL S3C CASE SPORLAN S3C D...
Страница 27: ...SET button when Application Type is displayed Use button and scroll to Single Temperature Case press SET 6 Press the SET button when Local Stepper Valve Configuration is displayed Use button to scroll...
Страница 28: ...buttons to choose the Refrigerant Type press SET The list of refrigerants can be seen in Table on page 99 15 Press the SET button when Discharge Air Temperature Setpoint is shown Use the buttons to c...
Страница 29: ...OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS CONTROL S3C CASE SPORLAN S3C DM POWER SUPPLY INPUT 100 2...
Страница 30: ...on for numeric for alpha characters When satisfied with each digit press the SET button to go to the next digit Pressing SET multiple times will move to the next parameter 3 Press the SET button when...
Страница 31: ...ress the SET button when Refrigerant Type is shown Use the buttons to choose the Refrigerant Type press SET The list of refrigerants can be seen in Table on page 99 15 Press the SET button when Discha...
Страница 32: ...R ANTI SWEAT DIGITAL INPUTS OUT COIL AIR DSCH AIR RTN DET TERM 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS 5V S GND 5V S GND CL GND 5V HUMIDITY POWER ALARM COOLING FANS DEFRO...
Страница 33: ...button to go to the next digit Pressing SET multiple times will move to the next parameter 4 Press the SET button when Application Type is displayed Use button and scroll to Single Temperature Case pr...
Страница 34: ...setting the time will accelerate the scrolling 13 Press the SET button when Refrigerant Type is shown Use the buttons to choose the Refrigerant Type press SET The list of refrigerants can be seen in T...
Страница 35: ...DSCH AIR RTN DET TERM 5V S GND 5V S GND 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND HUMIDITY 5V POWER ALARM COOLING FANS DEFROST RDM VM Rx Tx BAS Rx Tx LIGHTS VALVE SOL...
Страница 36: ...ttons to scroll to press SET This will configure the controller to support a remote case 2 Press the SET button when Rack Identifier is displayed Use the buttons to configure the 4 character Rack Iden...
Страница 37: ...pected in Line up is shown Use the buttons to choose the number of cases expected in the Line up press SET 15 Press the SET button when EPR Type is shown Use the button to choose for no EPR press SET...
Страница 38: ...ND 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS CONTROL S3C CASE SPORLAN S3C D...
Страница 39: ...for numeric for alpha characters When satisfied with each digit press the SET button to go to the next digit Pressing SET multiple times will move to the next parameter 3 Press the SET button when Li...
Страница 40: ...en in Table 9 on page 99 15 Press the SET button when Number of Cases Expected in Line up is shown Use the buttons to choose the number of cases expected in the Line up press SET 16 Press the SET butt...
Страница 41: ...OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS CONTROL S3C CASE SPORLAN S3C DM POWER SUPPLY INPUT 100 2...
Страница 42: ...figure the 4 character Rack Identifier Note Push button for numeric for alpha characters When satisfied with each digit press the SET button to go to the next digit Pressing SET multiple times will mo...
Страница 43: ...e buttons to choose from either or depending on the valve press SET Please consult the literature supplied with the valve to determine the correct step count For custom valve selection see valve confi...
Страница 44: ...D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS S3C CASE CONTROL SPORLAN S3C DM POWER SUPPLY INPUT 100 240VAC 1 2A...
Страница 45: ...ameter 3 Press the SET button when Line up Identifier is displayed Use the buttons to configure the 4 character Line up Identifier Note Push button for numeric for alpha characters When satisfied with...
Страница 46: ...s to choose from either or depending on the valve press SET Please consult the literature supplied with the valve to determine the correct step count For custom valve selection see valve configuration...
Страница 47: ...D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS S3C CASE CONTROL SPORLAN S3C DM POWER SUPPLY INPUT 100 240VAC 1 2A...
Страница 48: ...ontained case 1 Press the SET button then use buttons to scroll to press SET This will configure the controller to support a remote case 2 Press the SET button when Rack Identifier is displayed Use th...
Страница 49: ...SET 16 Press the SET button when Evaporator Pressure Regulating Valve Type is shown Use the buttons to choose from either or depending on the valve press SET Please consult the literature supplied wit...
Страница 50: ...DIGITAL INPUTS OUT COIL AIR DSCH AIR RTN DET TERM 5V S GND 5V S GND 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx...
Страница 51: ...hen Rack Identifier is displayed Use the buttons to configure the 4 character Rack Identifier Note Push button for numeric for alpha characters When satisfied with each digit press the SET button to g...
Страница 52: ...in the Line up press SET 16 Press the SET button when Evaporator Pressure Regulating Valve Type is shown Use the buttons to choose from either or depending on the valve press SET Please consult the l...
Страница 53: ...DIGITAL INPUTS OUT COIL AIR DSCH AIR RTN DET TERM 5V S GND 5V S GND 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx...
Страница 54: ...to press SET This will configure the controller to support a remote case 2 Press the SET button when Rack Identifier is displayed Use the buttons to configure the 4 character Rack Identifier Note Push...
Страница 55: ...Press the SET button when Number of Cases Expected in Line up is shown Use the buttons to choose the number of cases expected in the Line up press SET 16 Press the SET button when Evaporator Pressure...
Страница 56: ...R ANTI SWEAT DIGITAL INPUTS OUT COIL AIR DSCH AIR RTN DET TERM 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS 5V S GND 5V S GND CL GND 5V HUMIDITY POWER ALARM COOLING FANS DEFRO...
Страница 57: ...eevaporatorsanditshouldbewiredinto the case controller This configuration only supports Discharge Air control To configure the S3C control package for configuration L shown above follow these directio...
Страница 58: ...Use the button to choose the current time in 24 hour format press SET Note Holding the or down while setting the time will accelerate the scrolling 14 Press the SET button when Refrigerant Type is sho...
Страница 59: ...DSCH AIR RTN DET TERM 5V S GND 5V S GND 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND HUMIDITY 5V POWER ALARM COOLING FANS DEFROST RDM VM Rx Tx BAS Rx Tx LIGHTS VALVE SOL...
Страница 60: ...SET button then use buttons to scroll to press SET This will configure the controller to support a remote case 2 Press the SET button when Rack Identifier is displayed Use the buttons to configure th...
Страница 61: ...es expected in the Line up press SET 15 Press the SET button when Evaporator Pressure Regulating Valve Type is shown Use the buttons to choose from either or depending on the valve press SET Please co...
Страница 62: ...D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS S3C CASE CONTROL SPORLAN S3C DM POWER SUPPLY INPUT 100 240VAC 1 2A...
Страница 63: ...own above follow these directions If the controller has not been factory set then upon initial start up the controller will be in set up mode and the screen will display for self contained case 1 Pres...
Страница 64: ...s Expected in Line up is shown Use the buttons to choose the number of cases expected in the Line up press SET 16 Press the SET button when Evaporator Pressure Regulating Valve Type is shown Use the b...
Страница 65: ...DIGITAL INPUTS OUT COIL DSCH AIR AIR RTN DET TERM PRESSURE DRAIN OCCUPANCY D RS 485 D GND TEMPERATURE SENSORS CL GND HUMIDITY 5V POWER ALARM COOLING FANS DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS...
Страница 66: ...single circuit EEPR while allowing the EEVs to control superheat The optional liquid line solenoid LLS may be installed as one per case or one per line up In addition only one case in the line up lea...
Страница 67: ...year Year is shown Use the button to choose the current day press SET 13 Press the SET button when Time is shown Use the button to choose the current time in 24 hour format press SET Note Holding the...
Страница 68: ...MIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS CONTROL S3C CASE SPORLAN S3C DM POWER SUPPLY INPUT 100 240VAC 1 2A 50 60Hz OUTPUT 24VDC 2 5A ACN BLUE ACL BROWN V...
Страница 69: ...e controller will be in set up mode and the screen will display for self contained case 1 Press the SET button then use buttons to scroll to press SET This will configure the controller to support a r...
Страница 70: ...ess SET 16 Press the SET button when Evaporator Pressure Regulating Valve Type is shown Use the buttons to choose from either or depending on the valve press SET Please consult the literature supplied...
Страница 71: ...IGITAL INPUTS OUT COIL DSCH AIR AIR RTN DET TERM PRESSURE DRAIN OCCUPANCY D RS 485 D GND TEMPERATURE SENSORS CL GND HUMIDITY 5V POWER ALARM COOLING FANS DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS...
Страница 72: ...2 3 4 n that have two or three evaporators will require their own S3C case controller and valve module as well All case functions will be synchronized across the line up in this configuration with the...
Страница 73: ...14 Press the SET button when Refrigerant Type is shown Use the buttons to choose the Refrigerant Type press SET The list of refrigerants can be seen in Table on page 99 15 Press the SET button when N...
Страница 74: ...MIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS CONTROL S3C CASE SPORLAN S3C DM POWER SUPPLY INPUT 100 240VAC 1 2A 50 60Hz OUTPUT 24VDC 2 5A ACN BLUE ACL BROWN V...
Страница 75: ...button then use buttons to scroll to press SET This will configure the controller to support a remote case 2 Press the SET button when Rack Identifier is displayed Use the buttons to configure the 4...
Страница 76: ...Please consult the literature supplied with the valve to determine the correct step count For custom valve selection see valve configuration menu in Section 11 16 Press the SET button when EPR Locati...
Страница 77: ...GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS S3C CASE CONTROL SPORLAN S3C DM POWER SUPPLY INPUT 100 240VAC 1 2A 50 6...
Страница 78: ...above follow these directions If the controller has not been factory set then upon ini tial start up the controller will be in set up mode and the screen will display for self contained case 1 Press t...
Страница 79: ...ype is shown Use the buttons to choose from either or depending on the valve press SET Please consult the literature supplied with the valve to determine the correct step count For custom valve select...
Страница 80: ...TAL INPUTS OUT COIL AIR DSCH AIR RTN DET TERM 5V S GND 5V S GND 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BA...
Страница 81: ...upport a remote case 2 Press the SET button when Rack Identifier is displayed Use the buttons to configure the 4 character Rack Identifier Note Push button for numeric for alpha characters When satisf...
Страница 82: ...or Pressure Regulating Valve Type is shown Use the buttons to choose from either or depending on the valve press SET Please consult the literature supplied with the valve to determine the correct step...
Страница 83: ...DIGITAL INPUTS OUT COIL AIR DSCH AIR RTN DET TERM 5V S GND 5V S GND 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx...
Страница 84: ...essing SET multiple times will move to the next parameter 3 Press the SET button when Line up Identifier is displayed Use the buttons to configure the 4 character Line up Identifier Note Push button f...
Страница 85: ...be seen in Table on page 99 15 Press the SET button when Number of Cases Expected in Line up is shown Use the buttons to choose the number of cases expected in the Line up press SET 16 Press the SET...
Страница 86: ...D D GND RS 485 TEMPERATURE SENSORS CL GND 5V HUMIDITY POWER FANS ALARM COOLING DEFROST RDM VM Rx Tx BAS Rx Tx VALVE SOLENOIDS LIGHTS CONTROL S3C CASE SPORLAN S3C DM POWER SUPPLY INPUT 100 240VAC 1 2A...
Страница 87: ...dentifier is displayed Use the buttons to configure the 4 character Line up Identifier Note Push button for numeric for alpha characters When satisfied with each digit press the SET button to go to th...
Страница 88: ...se the buttons to choose from either or depending on the valve press SET Please consult the literature supplied with the valve to determine the correct step count For custom valve selection see valve...
Страница 89: ...DIGITAL INPUTS OUT COIL AIR DSCH AIR RTN DET TERM 5V S GND PRESSURE DRAIN OCCUPANCY D D GND RS 485 TEMPERATURE SENSORS 5V S GND 5V S GND CL GND HUMIDITY 5V POWER FANS ALARM COOLING DEFROST RDM VM Rx...
Страница 90: ...per case unless otherwise noted Configuration Case Controller Display Module Valve Module A 1 1 B 1 1 C 1 1 1 D 1 1 1 E 1 1 F 1 1 G 1 1 H 1 1 I 1 1 1 per line up J 1 1 1 K 1 1 1 L 1 1 1 M 1 1 N 1 1 1...
Страница 91: ...Used Not Used L Case Controller Stepper Valve Valve Module Stepper Valve 1 Valve Module Stepper Valve 2 Not Used M Not Used Not Used Not Used Case Controller Stepper Valve N Case Controller Stepper Va...
Страница 92: ...uttons to enter the administrator password and press SET 3 The display will show will skip to Process Values if system is self contained 4 Press the SET button and will be displayed 5 Press the button...
Страница 93: ...e options value for that parameter Use the buttons to navigate through the options or increment decrement the parameter value TABLE 4 SET UP MENU PARAMETERS Display Description Factory Default Hide Co...
Страница 94: ...lighting control are controlled In the event a control in the line up is replaced or a new one added it will receive its line up level operating parameters from its peer controllers as soon as it is r...
Страница 95: ...et 1 Number of controllers detected in the COM loop Number of controllers detected on the rack Number of controllers detected in the line up EEPR Controller Detected Number of Evaporators Detected Use...
Страница 96: ...or Evaporator view shows process values for valves and sensors connected to a particular evaporator These views are available on multi coil cases For single coil cases the evaporator parameters may b...
Страница 97: ...temporary All settings will resort back to previous setting after exiting this level It is used to View all service parameters Change service parameters to help diagnose system 11 2 CONFIGURING THE S3...
Страница 98: ...Line up Configuration Allows viewing of line up level process values 1 EvP3 Evaporator 3 Configuration Allows configuration of evaporator level sensors offsets for evaporator 3 2 EvP2 Evaporator 2 Con...
Страница 99: ...nt 30 to 19 F 30 19 5 6 raMt Return Air Medium Temperature Set Point 20 to 50 F 20 50 5 6 ratd Return Air Temperature Differential 1 to 10 F 1 10 4 5 SHSP Superheat Set Point 5 to 45 F 5 45 7 EPrC EEP...
Страница 100: ...oc Fireware Version Lock Yes NO yes no TABLE 10 HIDE CONDITIONS FOR BASIC CONFIGURATION MENU ITEMS Number Hide Condition 1 Application type is dual temperature 2 Control temperature input selection is...
Страница 101: ...hen press SET 7 Press the ESC button three times to return to default display 11 5 2 3 CUSTOM PRESSURE TRANSDUCER A custom transducer range may be configured in the S3C The transducer must be a 0 5 to...
Страница 102: ...ed 11 8 DISPLAY CONFIGURATION The brightness of the side Quick View indicators on the Display Module DM may be adjusted to suit individual requirements The indicators may also be turned off 11 8 1 ADJ...
Страница 103: ...r Fan Fault Current Baseline If this parameter is not set the controller will automatically establish a baseline current using system run time information within the first 24 hours of operation An ala...
Страница 104: ...MODBUS over IP BACnet over IP BACnet over RS 485 MODBUS over RS 485 BAS Communications Time out 1 to 100 minutes IP Address Selection DHCP with AutoIP DHCP with static Address Static IP Address IP Ad...
Страница 105: ...lve type is configured as SFV 3 Expansion valve type not configured as custom 4 Expansion valve type not configured as pulse valve 5 EPR type NOT configured as custom TABLE 11 VALVE CONFIGURATION MENU...
Страница 106: ...SET to change to either bipolar or unipolar press SET 8 Display will show press the button to scroll to number of steps press SET to change the max stroke in steps press SET 9 Display will show press...
Страница 107: ...ion Two Valve Modules are needed when discharge air and return air sensors are required for three coil cases 11 15 VALVE MODULE CONFIGURATION FOR EEV AND EEPR The S3C Valve Module may be configured to...
Страница 108: ...1 17 1 FIXED DUTY CYCLE CONTROL 1 From the default display press the button The display will show 2 Use the buttons to enter the administrator password and press SET 3 The display will show press SET...
Страница 109: ...ol type Set the type of control used for anti sweat control Fdty fixed duty cycle control dptC dew point control ASPP Anti sweat pulse period Sets the pulse period total time of pulse cycle includes o...
Страница 110: ...h evaporator fans energize after defrost 32 32 2 Fdte Fan delay time Maximum elapsed time before fans resume operation 0 60 minutes 2 LLsd Liquid line solenoid defrost operation Liquid line solenoid e...
Страница 111: ...o start time in 24 hour time press SET 7 Press the button to scroll to the defrost per day press SET 8 Use the buttons to scroll to the amount of defrosts per day press SET 9 Press the ESC button 3 ti...
Страница 112: ...o scroll to the time the lights turn off in 24 hour time press SET 11 Press the ESC button 3 times to revert to the default display 13 3 SEVEN DAY LIGHTING SCHEDULE 1 From the default display press th...
Страница 113: ...NCY SENSOR The S3C supports the Sporlan OCC occupancy sensor This sensor is mounted on the top of the case and senses when there is movement near the front of the case This sensor is used in conjuncti...
Страница 114: ...is at 0 and it has been 24 hours The S3C Case Control or Valve Module has been power cycled Valve configurations are changed thru the menu During start up the S3C Case Control scans all sensor inputs...
Страница 115: ...ly The EEVs close during defrost for electricdefrostsystemsandopento100 whenhotgasisused and will resume controlling superheat when all evaporators in the case have reached termination temperature or...
Страница 116: ...2 7 AIR DEFROST Air defrost is accomplished by stopping the flow of refrigerant to the evaporator while leaving the evaporator fans on The S3C Case Controller will stop the flow of refrigerant via a c...
Страница 117: ...t Open during drain parameter to bleed excess pressure to the suction header In accordance with its configuration when resuming refrigeration the Solenoid and EEV opens while leaving the fans ON OFF I...
Страница 118: ...Values 5 Press the button repeatedly until is displayed 6 Press SET to enter the Alarm Configuration sub menu TABLE 17 ALARM CONFIGURATION MENU ITEMS Display Meaning Hide Condition Door Alarm Delay 1...
Страница 119: ...on type is dual temperature case or control temperature input selection is not return air temperature 4 Skipped if application type is not dual temperature case 5 Skipped if application type is dual t...
Страница 120: ...tput reverts to 100 on Yes No Coil Outlet Temperature sensor detected Note Can be Coil Outlet sensor on Valve Module in multiple evaporator applications EEV superheat control selected Sensor not conne...
Страница 121: ...when EEPR selected or when 2 evaporators selected Yes Case Network communication fault S3C Case Control configured for presence of 2 or more controls in line up Case Network settings incorrect Communi...
Страница 122: ...perheat Control selected 1 EEV closes to prevent possible flood back Yes 3 No Coil Outlet Temperature sensor detected on Right Evaporator S3C Valve Module CO1 input 2 or 3 Evaporators installed in cas...
Страница 123: ...d on initial power up to enable alarm Discharge Air Temperature sensor not connected miswired or faulty EEPR Temperature control selected 1 Single case in line up One DA sensor connected to S3C Valve...
Страница 124: ...low limit for a period greater than selected low alarm time delay Yes Suction pressure high Measured suction pressure is above user selected high limit for a period greater than selected high alarm ti...
Страница 125: ...isplay discharge air For Coil 3 1 From the default display press the button to then press SET 2 Press the button and scroll to 3 Press SET button to show current superheat value 4 Press ESC button thr...
Страница 126: ...ET 5 Use the buttons and scroll to press SET 6 Press the button to scroll to basic menu press SET 7 Press the button to scroll to superheat setpoint press SET 8 Use the buttons to increase or decrease...
Страница 127: ...o be used for safety critical servicing Use proper lockout tag out producers as defined by local requirements and codes on the case if electrical repair or other safety critical servicing is required...
Страница 128: ...Action LED Driver lighting ALL Press then SET to dim 0 100 of 10V Fan Speed Output ALL Press then SET to change speed 0 100 of 10V Anti Sweat Duty Cycle ALL Press then SET to change duty cycle 0 100 o...
Страница 129: ...and scroll to press SET 2 Use the button and scroll to press SET The system will resume operation 3 Press the ESC button 2 times to revert to the default display 19 15 LED SERVICE INDICATORS The S3C...
Страница 130: ...frost Heater Reset press SET 5 Use the buttons and scroll to press SET 19 18 FAN CURRENT BASE LINE RESET The S3C Case Control has an integrated detection circuit for fan current This feature allows cu...
Страница 131: ...or to handling the controller For replacement use the following fuse specification or equivalent Liquid Line Solenoid Pulse Valve 1A 250VAC 2AG Littelfuse Part Number 0225001 MXP 1 Remove power from v...
Страница 132: ...roller by snapping on to DIN rail or using mounting screws 6 Install terminal plugs with wires 7 Ensure the position of the termination resistor switch is the same as the old controller 8 Retighten al...
Страница 133: ...e locks onto the display and compress against bulkhead to ensure proper sealing 6 Connect power and communications terminal plug Note followed by dashes may appear on the display while the Display Mod...
Страница 134: ...nufacturer s installation instructions The following chart can be used as a guide for trouble shooting Problem Check Solution Display not powering up Voltage at Display Module Gnd and 24VDC Ensure wir...
Страница 135: ...on D for communication 24VDC Positive side of supply voltage and Gnd Negative side of 24VDC Note This is only for the dedicated private network between modules not refrigerated case to refrigerated ca...
Страница 136: ...logs Time Time of Day 24 hour Time and Date stamping of alarms and data logs Defrost and Lighting Schedule control Superheat Target Evaporator superheat set point Control set point for EEV Pulse or St...
Страница 137: ...er not equipped with a local pressure transducer 2 Allows for continued superheat control from a common suction pressure if one or more pressure transducer faults occur within a line up Minimum Coolin...
Страница 138: ...ature Suction Pressure Low Alarm Threshold Low Pressure alarm threshold for Low Temperature operation Dual Temp Medium Temperature Suction Pressure High Alarm Threshold High Pressure alarm threshold f...
Страница 139: ...Drain Time Time period between deactivation of defrost mechanism an re initiating refrigeration Allows for elimination of defrost water Fan Delay Temperature Temperature at which evaporator fans ener...
Страница 140: ...rain wire and foil shield from the cable at the S3C controller side The shield must be tied to earth ground on the BAS side A subnet is a set of cases that are networked together that connect thru a s...
Страница 141: ...and scroll to building automation time out press SET 11 Use the buttons to scroll to the desired time out in minutes press SET Note This is the amount of time the S3C Control waits before a communicat...
Страница 142: ...A1 and B1 are the routers that route data from the line up via ethernet to the BAS via RS 485 These are the cases that communicate into the BAS All other cases communicate via ethernet Unique address...
Страница 143: ...nd a DHCP server on the network then the AutoIP protocol will assign unique IP addresses to the controllers The AutoIP protocol IP range is 169 254 0 1 thru169 254 255 254 TheDHCPservershouldalsoassig...
Страница 144: ...uttons to change IP Address Octet 1 16 Use the button and the SET button to navigate through and Subnet Mask 17 Press the ESC button 3 times to revert to the default display 21 5 VIEWING CONTROLLER IP...
Страница 145: ...documents Seller deems necessary to perfect its security interest 11 Improper Use and Indemnity Buyer shall indemnify defend and hold Seller harmless from any losses claims liabilities damages lawsuit...
Страница 146: ...Bulletin 100 50 9 1 32020 2020 Parker Hannifin Corporation Parker Hannifin Corporation Sporlan Division 206 Lange Drive Washington MO 63090 USA phone 636 239 1111 fax 636 239 9130 www sporlan com...