2 Introduction

These water coolers are monoblock units for the production of cooled 
water in a closed circuit.
The fan, pump and compressor motors are equipped with a thermal 
protector that protects them against possible overheating.

2.1 Transport

The packed unit must remain:

a)  Upright;
b)  Protected against atmospheric agents;
c)  Protected against impacts.

2.2 Handling

Use a fork-lift truck suitable for the weight to be lifted, avoiding any 
type of impact (see paragraph 7.2).

2.3 Inspection

a)  All the units are assembled, wired, charged with refrigerant and oil 

and tested in the factory;

b)  On receiving the machine check its condition: immediately notify 

the transport company in case of any damage; 

c)  Unpack the unit as close as possible to the place of installation.

2.4 Storage

a)  Keep the unit packed in a clean place protected from damp and 

bad weather.

b)  Do not stack the units;
c)  Follow the instructions given on the package.

3 Installation

Y

For correct installation, follow the instructions given in par.7.2, 7.3, 

7.4 and 7.8.

!

 The product installed must be suitably protected against fi re risk 

(ref. EN378-3).

For the correct application of the warranty terms, follow the in-

structions given in the start-up report, fi ll it in and send it back to Seller

!

 

Liquids to be chilled

The liquids to be chilled must be compatible with the materials used.
Examples of liquids used are water or mixtures of 

water and ethylene 

or propylene glycols.

The liquids to be chilled must not be fl ammable. 
If the liquids to be chilled contain hazardous substances (e.g. ethylene/
propylene glycol), any liquid discharged from a leakage area must be 
collected, because it is harmful to the environment.  When draining 
the hydraulic circuit, comply with the current regulations and do not 
disperse the contents in the environment.

3.1 Operating space

To allow an unrestricted air fl ow around the chiller and easy access for 
servicing, ensure the area around the unit is kept free of obstacles (see 
paragraph 7.3). 
Leave a space of at least 80 inch (2 metres) above the refrigerator in 
models with vertical emission of condensation air.

3.2 Versions

Air-cooled version
Axial fans (A)

Do not create cooling air recirculation situations. 
Do not obstruct the ventilation grilles.
The ducting of extracted air is not recommended for versions with axial 
fans.

Centrifugal version (C)

Always ensure a minimum counterpressure on the delivery of
fans, ducting the individual hot air outlets.

Water- cooled version (W)

If the water to the condenser is in open circuit, install a mesh fi lter on 
the condensation water inlet.
Please note that for special cooling water types such as demineral-
ized, deionized or distilled it is necessary to contact the manufacturer 
to verify which kind of condenser should be used since the standard 
material may not be suitable.

3.3 Water circuit

3.3.1 

Checks and connection

Before connecting the chiller and fi lling the water circuit, check 

that all the pipes are clean. If not, wash them out thoroughly. 

If the plumbing circuit is of the closed type, under pressure it is 

advisable to install a safety valve set to  87 PSIg (6 bar). 

Always install mesh fi lters on the water inlet and outlet pipelines.

If the hydraulic circuit is intercepted by automatic valves, protect 

the pump with an anti-hammering system.

If the hydraulic circuit is emptied for shut-down periods we 

recommend that you add lubricating fl uid to the pump’s impeller to 
avoid the risk of blockage when it is re-started.    In case the impeller is 
blocked then you should unblock it manually.
Remove the rear cover of the pump and carefully turn the plastic fan.   
If the impeller is stuck then remove the fan and turn the impeller shaft 
directly. After un-blocking the impeller re-assemble the fan and cover.

Preliminary checks

1)  Check that any shut-off valves in the water circuit are open.
2)  In the case of a closed water circuit, check that an expansion tank 

of suitable capacity has been installed. See paragraph 3.3.3.

Connection

1)  Connect the water cooler to the inlet and outlet piping, using the 

special connections located on the back of the unit.
We recommend the use of fl exible unions to reduce system rigidity.

2)  Fill the water circuit using the fi tting provided on the rear of the 

chiller (

).

3)  The tank is equipped with a breather valve that should be operated 

manually when fi lling the tank. Also, if the hydraulic circuit has high 
points, install a vent valve at the highest points.

4)  We recommend that taps are installed on the inlet and outlet pipes, 

so that the unit can be excluded for maintenance when necessary.

5)  If the chiller works with an open tank, the pump must be installed 

on intake to the tank and on delivery to the chiller.

Subsequent checks

1)  Check that the tank and the circuit are completely full of water and 

that all the air has been expelled from the system.

2)  The water circuit must always be kept full. For this reason, carry 

out periodic checks and top the circuit up if necessary, or install an 
automatic fi lling kit.

3.3.2 

Water and ethylene glycol

If installed outdoors or in an unheated indoor area, it is possible that 
the water in the circuit may freeze if the system is not in operation dur-
ing the coldest times of the year.
To avoid this hazard:

a)  Equip the chiller with suitable antifreeze protection devices, avail-

able from the manufacturer as optional accessories;

b)  Drain the system via the drain valve if the chiller is to remain idle for 

a prolonged period;

c)  Add an appropriate quantity of antifreeze to the water in circulation 

(see table).

Sometimes the temperature of the outlet water is so low as to require 
the addition of ethylene glycol in the following percentages.

Outlet water

temperature  [°C]

Ethylene glycol

(% vol.)

Ambient

temperature

4

5

-2

2

10

-5

0

15

-7

-2

20

-10

-4

25

-12

-6

30

-15

3.3.3 Expansion 

tank

To avoid the possibility of an increase or decrease in the volume of the 
fl uid due to a signifi cant change in its temperature causing damage to 
the machine or the water circuit, we recommend installing an expansion 
tank of suitable capacity.
The expansion tank must be installed on intake to the pump on the rear 
connection of the tank.
The minimum volume of an expansion tank to be installed on a closed 
circuit can be calculated using the following formula:
V=2 x Vtot x (Pt min - P t max)
where
Vtot= vol. circuit total (in litres)
P t min/max= specifi c weight at the minimum/maximum temperature 
reached by the water [kg/dm3].

Содержание Hyperchill PCW420

Страница 1: ...PCW420 PCW510 PCW650 Hyperchill 60Hz DATE 14 02 2022 Rev 17 CODE 398H272297 EN User Manual ES Manual de uso FR Manuel d utilisation PT Manual do utilizador...

Страница 2: ......

Страница 3: ...right to modify this manual at any time For the most comprehensive and updated information the user is advised to consult the manual supplied with the unit CAUTION Moving parts hot parts and risk of...

Страница 4: ...7 PSIg 6 bar Y Always install mesh filters on the water inlet and outlet pipelines Y If the hydraulic circuit is intercepted by automatic valves protect the pump with an anti hammering system Y If the...

Страница 5: ...at the machine and the auxiliary equipment are earthed and protected against short circuit and or overload Once the unit has been connected and the upstream main switch closed thereby connecting the p...

Страница 6: ...ure limit values Pmax and Pmin indicated on the pump data plate P1 pressure with pump ON P0 pressure with pump OFF Pmin P1 P0 Pmax Example n 1 Conditions closed circuit pressure P0 29 PSIg 2 bar pump...

Страница 7: ...5 U 0 0 4 4 7 B7 sensor parameters PARAMETER CODE TYPE DEFAULT High temperature configuration cHA7 U 0 High temperature alarm HA7 U 60 0 140 0 Low temperature alarm LA7 U 3 0 37 4 Sensor calibration C...

Страница 8: ...w pressure alarm 1 from pres sure switch M ID3 tP L7 Pump thermal cutout alarm M ID4 LL L8 Water tank low water level alarm No water flow A ID6 PII L9 Protection alarm compressor 1 Phases monitor M ID...

Страница 9: ...imum chiller efficiency and reliability carry out a Z every 6 months clean the condenser fins and make sure compressor electrical absorption is within the dataplate values b Z kit for maintenance par...

Страница 10: ...FILTER CLOGGED RENEW THE FILTER CONDENSER FINS DIRTY CLEAN THE FINS OF THE CONDENSER CONDENSER SURFACES CLOGGED CLEAR THE FRONT SURFACE OF THE CON DENSER INSUFFICIENT WATER FLOW INCREASE THE FLOW RATE...

Страница 11: ...a el derecho de modi car sin previo aviso la informaci n de este manual Para que la infor maci n resulte completa se recomienda al usuario consultar el manual a pie de m quina PRECAUCI N Partes m vile...

Страница 12: ...Se recomienda instalar filtros de red en los tubos de entrada y salida del agua Y Si el circuito hidr ulico posee v lvulas autom ticas de corte proteger la bomba con sistemas contra golpe de ariete Y...

Страница 13: ...el equipo cuando se cierra el interruptor ge neral de alimentaci n para energizarlo la tensi n en el circuito el ctrico alcanza valores peligrosos Se recomienda la m xima precauci n 3 4 2 Alarma gene...

Страница 14: ...o leer P1 y P0 y los valores l mite de presi n Pm x y Pm n indicados en la placa de datos de la bomba P1 presi n con bomba ON P0 presi n con bomba OFF Pm n P1 P0 Pm x Ejemplo n 1 Condiciones circuito...

Страница 15: ...baja temperatura LA5 U 20 0 4 0 Calibraci n de la sonda CA5 U 0 0 4 4 7 Par metros de la sonda B7 PARAMETER CODE TYPE DEFAULT Configuraci n alta temperatura cHA7 U 0 Alarma de alta temperatura HA7 U 6...

Страница 16: ...larma alta presi n 1 desde presostato M ID2 LPI L6 Alarma baja presi n 1 desde presostato M ID3 tP L7 Alarma t rmico de la bomba M ID4 LL L8 Alarma bajo nivel de agua en el dep sito Falta flujo de agu...

Страница 17: ...cia y fiabilidad del refrigerador hay que a Z ocada 6 meses climpiar las aletas del condensador y contro lar que la absorci n de corriente del compresor est dentro de los valores nominales b Z kit de...

Страница 18: ...TASCADO SUSTITUIR EL FILTRO ALETAS DEL CONDENSADOR SUCIAS LIMPIAR LAS ALETAS DEL CONDENSADOR SUPERFICIE DEL CONDENSADOR OBSTRUIDA LIBERAR LA SUPERFICIE FRONTAL DEL CONDENSADOR CAUDAL DE AGUA INSUFICIE...

Страница 19: ...parfaitement conformes pour une utilisation correcte de cette m me unit ou de ses composants ATTENTION Le fabricant se r serve le droit de modi er sans aucun pr avis les informations contenues dans c...

Страница 20: ...nseill de toujours installer des filtres grillag s sur les tuyauteries d entr e et de sortie de l eau Y Si le circuit hydraulique est intercept par des soupapes auto matiques prot ger la pompe avec de...

Страница 21: ...iaires sont bien mis la terre et qu ils sont prot g s contre les courts circuits et ou les surcharges Apr s avoir branch l unit et ferm l interrupteur g n ral en amont mettant ainsi la machine sous te...

Страница 22: ...paragraphe 4 5 b V rifier le fonctionnement de la pompe avec le manom tre lire P1 et P0 et les valeurs limites de pression Pmax et Pmin inscrites sur la plaquette signal tique de la pompe P1 pression...

Страница 23: ...DE TYPE DEFAULT Alarme haute temp rature HA3 U 60 0 140 0 Alarme basse temp rature LA3 U 20 0 4 0 Calibrage sonde CA3 U 0 0 4 4 6 Param tres sonde B5 PARAMETER CODE TYPE DEFAULT Alarme haute temp ratu...

Страница 24: ...S lectionner le param tre b01 ou b02 avec les touches P3 et P4 puis appuyer sur la touche P2 SEL pour afficher la temp rature 4 Appuyer sur la touche P1 PRG pour sortir 4 6 Gestion alarmes 4 6 1 Alarm...

Страница 25: ...ience maximum et la fiabilit de l ap pareil proc der comme suit a Z tous les 6 mois nettoyage des ailettes du condenseur et v rifier que l absorption lectrique du compresseur se situe dans les valeurs...

Страница 26: ...TES DU CONDENSATEUR SALES NETTOYER LES AILETTES DU CONDENSATEUR SURFACE DU CONDENSEUR BOUCH E LIB RER LA SURFACE FRONTALE DU CONDENSATEUR D BIT D EAU INSUFFISANT AUMENTARE LA PORTATA DEL FLUI DO DA RA...

Страница 27: ...serva se o direito de modi car as infor ma es contidas no presente manual sem incorrer na obriga o de avis las previamente Para obter informa es completas e actualizadas recomenda se ao utilizador de...

Страница 28: ...e entrada e sa da de gua Y Se o circuito hidr ulico for interceptado por v lvulas autom ticas proteja a bomba com sistemas anti golpe de ariete Y Se o circuito for esvaziado para paragens prolongadas...

Страница 29: ...arelhos auxiliares foram ligados terra e protegidos contra curto circuitos e ou sobrecargas Uma vez ligada a unidade e uma vez fechado o interruptor geral situado a montante conferindo assim tens o m...

Страница 30: ...o funcionamento correcto da bomba utilizar um ma n metro consultar P1 e P0 e os valores limites de press o Pmax e Pmin indicados na chapa de caracter sticas da bomba P1 press o com bomba ON P0 press...

Страница 31: ...U 20 0 4 0 Calibragem da sonda CA3 U 0 0 4 4 6 Par metros da sonda B5 PARAMETER CODE TYPE DEFAULT Alarme de temperatura elevada HA5 U 60 0 140 0 Alarme de baixa temperatura LA5 U 20 0 4 0 Calibragem d...

Страница 32: ...2 LPI L6 Alarme de baixa press o 1 do press stato M ID3 tP L7 Alarme t rmico da bomba M ID4 LL L8 Alarme de baixo n vel de gua no reservat rio Aus ncia de fluxo de gua A ID6 PII L9 Alarme de protec o...

Страница 33: ...preventiva Para garantir a m xima efici ncia e fiabilidade do refrigerador ao longo do tempo verifique a Z de 6 em 6 meses limpeza do condensador e verifica o da alimenta o el ctrica do compressor den...

Страница 34: ...ENTUPIDO SUBSTITUA O FILTRO ALHETAS DO CONDENSADOR SUJAS LIMPE AS ALHETAS DO CONDENSADOR SUPERF CIE DO CONDENSADOR OBSTRU DA DESOBSTRUA A SUPERF CIE FRONTAL DO CONDENSADOR D BITO DE GUA INSUFICIENTE...

Страница 35: ......

Страница 36: ...fg E mail gsfsupport parker com Parker Hannifin Manufacturing S r l Sede Legale Via Sebastiano Caboto 1 Palazzina A 20094 Corsico MI Italy Sede Operativa Gas Separation and Filtration Division EMEA St...

Страница 37: ...Ap ndice Appendix Appendice Anexo DATE 14 02 2022 Rev 17 CODE 398H272297...

Страница 38: ......

Страница 39: ...mperature Temp rature ambiante Temperatura ambiente Durante el transporte y el almacenamiento During transport and stockage Pendant le transport et l entreposage Durante o transporte e armazenamento T...

Страница 40: ...maximum Temperatura m xima IP Grado de protecci n Protection degree Degr de protection Grau de prote o Salida aire de condensaci n Condensation air outlet Sortie air de condensation Sa da do ar de con...

Страница 41: ...de l eau V lvula de descarga da gua 15 Man metro del agua Water manometer Manom tre eau Man metro de gua 16 Man metro entrada refrigerante Refrigerant suction manometer Manom tre aspiration r frig ra...

Страница 42: ...rifo Cock Robinet Torneira A2 Pantalla local Local display Afficheur local Visor local QS Interruptor seccionador g neral Main disconnector switch Interrupteur sectionneur g n ral Interruptor secciona...

Страница 43: ...icas RO ON OFF a distancia Remote ON OFF ON OFF distance ON OFF remoto PI1 4 Protecci n integral compresor Compressor protection Protection int grale compresseur Protec o integral do compressor A100 M...

Страница 44: ...or KRA1 Contactor resistencia antihielo Antifreeze heater contactor Contacteur r sistance antigel Contactor da resist ncia anti gelo RA1 Resistencia antihielo Antifreeze heater R sistance antigel Resi...

Страница 45: ...7 7 2 Handling 7 3 Operating space PCW420 650 7 2 Handling A B C 1600 mm 4000 mm 7000 mm A B C D E D E 970 mm 1000 mm 7 3 Operating space 1500 mm m m 0 0 5 1 m m 0 0 5 1 1500 mm...

Страница 46: ...2 62 32 F 0 C 86 F 30 C 4 27 F 2 15 C 30 87 PSIg 6 bar 264 1000 PCW510 3968 1800 PCW650 4630 2100 64 MODEL R407C F L A A 460V 10 3ph 60Hz IP lb Kg CO2 MC1 4 EV1 3 P HP1 LP1 PV1 2 P3 P5 PCW420 39 7 2x1...

Страница 47: ...12 62 19 554 5 21 81 19 318 5 12 51 19 2187 86 09 110 4 34 2297 90 43 40 1 57 51 2 01 47 5 1 87 No 8 HOLES 18 1185 46 65 47 5 1 87 95 3 74 1090 42 91 95 3 74 5 2 96 19 227 5 8 94 19 1290 50 79 80 3 15...

Страница 48: ...260 128 35 No 8 HOLES 18 1185 46 65 47 5 1 87 47 5 1 87 95 3 74 95 3 74 1090 42 91 1115 43 90 1115 43 90 948 37 32 555 5 21 85 19 3270 128 74 645 25 39 645 25 39 731 5 28 80 731 5 28 80 903 5 35 57 32...

Страница 49: ...8H114768 398H114769 398H114754 Biogas 398H473645 398H473646 fan motor Centrifugal 3 398H381608 sigh glass 6 398H348022 refrigerant filter body 7 398H206227 Filter cartridge 398H206053 expansion valve...

Страница 50: ...e sensor 6m 29 398H275235 Evaporator temperature sensor 6m 30 398H275235 local display A2 398H275698 main diconnector switch QS 398H256425 compressor automatic switch QF1 4 398H256290 398H256363 compr...

Страница 51: ...13 7 5 Circuit diagram PCW420 650 NP PCW650 PCW650 A1...

Страница 52: ...14 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 1 of 11...

Страница 53: ...15 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 2 of 11...

Страница 54: ...16 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 3 of 11...

Страница 55: ...17 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 4 of 11...

Страница 56: ...18 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 5 of 11...

Страница 57: ...19 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 6 of 11...

Страница 58: ...20 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 7 of 11...

Страница 59: ...21 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 8 of 11...

Страница 60: ...22 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 9 of 11...

Страница 61: ...23 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 10 of 11...

Страница 62: ...24 7 6 Wiring diagram PCW420 510 PCW420 650 Sheet 11 of 11...

Страница 63: ...25 7 6 Wiring diagram PCW650 PCW420 650 Sheet 1 of 11...

Страница 64: ...26 7 6 Wiring diagram PCW650 PCW420 650 Sheet 2 of 11...

Страница 65: ...27 7 6 Wiring diagram PCW650 PCW420 650 Sheet 3 of 11...

Страница 66: ...28 7 6 Wiring diagram PCW650 PCW420 650 Sheet 4 of 11...

Страница 67: ...29 7 6 Wiring diagram PCW650 PCW420 650 Sheet 5 of 11...

Страница 68: ...30 7 6 Wiring diagram PCW650 PCW420 650 Sheet 6 of 11...

Страница 69: ...31 7 6 Wiring diagram PCW650 PCW420 650 Sheet 7 of 11...

Страница 70: ...32 7 6 Wiring diagram PCW650 PCW420 650 Sheet 8 of 11...

Страница 71: ...33 7 6 Wiring diagram PCW650 PCW420 650 Sheet 9 of 11...

Страница 72: ...34 7 6 Wiring diagram PCW650 PCW420 650 Sheet 10 of 11...

Страница 73: ...35 7 6 Wiring diagram PCW650 PCW420 650 Sheet 11 of 11...

Страница 74: ......

Страница 75: ......

Страница 76: ...fg E mail gsfsupport parker com Parker Hannifin Manufacturing S r l Sede Legale Via Sebastiano Caboto 1 Palazzina A 20094 Corsico MI Italy Sede Operativa Gas Separation and Filtration Division EMEA St...

Отзывы: